4.type and Specification: Solar Inverter Parameters Specifications

The document outlines the specifications and features of a solar inverter, highlighting its stability, low failure rate, and extensive protection features such as over-voltage and short circuit protection. It details various models with different power outputs and battery types, as well as charging parameters and operational efficiencies. Additionally, it includes information on the inverter's communication interfaces, cooling mechanisms, and safety certifications.

Uploaded by

Ramses Puno
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
106 views5 pages

4.type and Specification: Solar Inverter Parameters Specifications

The document outlines the specifications and features of a solar inverter, highlighting its stability, low failure rate, and extensive protection features such as over-voltage and short circuit protection. It details various models with different power outputs and battery types, as well as charging parameters and operational efficiencies. Additionally, it includes information on the inverter's communication interfaces, cooling mechanisms, and safety certifications.

Uploaded by

Ramses Puno
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd

stability, low failure rate, long life, normal use life can reach more than eight years;

9 、 Perfect protection features: Low voltage protection, high voltage protection, high temperature
protection, short circuit protection, leakage protection, over-current protection, over-load protection,
low voltage recovery, high voltage recovery, Intelligent temperature control fan, fault alarm, fault
recovery etc comprehensive protection

10 、 Power efficiency designing,resisting harmonic wave and inductive load ,safe and stable.

11 、 The frequency of 50/60HZ automatic selection,give priority to use AC and DC with automatic
adjustment.display dynamic schematic diagram,comprehensive functions.easier to use.

12 、 Pure copper transformer , blind post and wire.High density conformal coating.Double ball
bearing mute dc fan,Large LCD screen,Large current terminals,Best electric components,best
packing,safe,efficient and high level.

4.Type and specification


Specification Type Discribtion
DC12V-AC220V 300W , 600W , 800W , 1KW , 1.5KW , 2KW

3KW 1 : AC voltage :
DC24V-AC220V 300W , 600W , 800W , 1KW , 1.5KW , 2KW AC110V/100V/120V/230V/

3KW , 4KW , 5KW , 6KW 240V
300W , 600W , 800W , 1KW , 1.5KW , 2KW 2 : Charge from Utility

DC48V-AC220V 3KW , 4KW , 5KW , 6KW , 7KW , 8KW Grid , UPS function

10KW , 12KW 3 : Frequency 50HZ/60HZ ,
( postscript : DC36V
DC72V-AC220V 1.5KW and ,any
2KWother would
, 3KW be customized.)
, 4KW , 5KW , 6KW automatic selection

7KW , 8KW , 10KW , 12KW
5.Parameters

Solar inverter parameters specifications


Power Specifications 300W~12KW
DC Input Specifications
Rated Voltage Specifications DC12/24/48/72V-AC220V DC12/24/48/72V-AC110V
10V-16V (DC12V)
Operating Voltage
20V-32V (DC24V)
Range(Normal Operating
40V-64V (DC48V)
Battery Voltage)
60V-96V (DC72V)
10.5Vdc ± 0.3Vdc ( 12V )
Low Voltage Alarm(alarm to
21.0Vdc ± 0.6Vdc ( 24V )
alert users when battery’s
voltage is over low) 42.0Vdc ± 1.2Vdc ( 48V )
63.0vdc ± 1.8Vdc ( 72V )
10.0Vdc ± 0.3Vdc ( 12V )
Low Voltage Shut off (shut off
20.0Vdc ± 0.6Vdc ( 24V )
when battery’s voltage is over
low) 40.0Vdc ± 1.2Vdc ( 48V )
60.0Vdc ± 1.8Vdc ( 72V )
Low Voltage Recovery 12.0Vdc ± 0.3Vdc (12V)
(Automatic Boot when 24.0Vdc ± 0.3Vdc (24V)
battery’s voltage returns to 48.0Vdc ± 0.3Vdc (48V)
normal) 72.0Vdc ± 0.3Vdc (72V)
High Voltage Alarm and shut 16Vdc ± 0.3Vdc ( 12V )
off ( alarms and shut off when 32Vdc ± 0.6Vdc ( 24V )
the battery’s voltage is over 64Vdc ± 1.2Vdc ( 48V )
high) 96Vdc ± 1.8Vdc ( 72V )
15.5Vdc ± 0.3Vdc ( 12V )
High Voltage Recovery
31.0Vdc ± 0.6Vdc ( 24V )
(Automatic boot when battery’s
voltage returns to normal) 62.0Vdc ± 1.2Vdc ( 48V )
93.0Vdc ± 1.8Vdc ( 72V )
Inverter Efficiency ≥90%
DC-priority type, battery low
voltage conversion point when 11Vdc ± 0.3Vdc ( 12V )
there is utility electricity bypass 22Vdc ± 0.6Vdc ( 24V )
( battery voltage is lower than 44Vdc ± 1.2Vdc ( 48V )
this, turn to utility electricity to 66Vdc ± 1.8Vdc ( 72V )
supply)
DC-priority type, after
turning to utility electricity to
supply, the battery low 13.5Vdc ± 0.3Vdc ( 12V )
voltage recovery point (when 27.0Vdc ± 0.6Vdc ( 24V )
the battery’s voltage is higher 54.0Vdc ± 1.2Vdc ( 48V )
than this, turn to battery to 81.0Vdc ± 1.8Vdc ( 72V )
supply electricity)
AC Input Specifications
Rated Voltage Specifications 220VAC System 110VAC System
Sine wave (utility electricity Sine wave (utility electricity
Input Voltage Waveform
or generator) or generator)
Rated Input Voltage 220Vac/230Vac/240Vac 110Vac/120Vac/130Vac
Low Voltage Shut off 180Vac±4% 85Vac±4%
Low Voltage Recovery 195Vac ±4% 90Vac ±4%
High Voltage Shut off 260Vac±4% 135Vac±4%
High Voltage Recovery 255Vac±4% 130Vac±4%
Three Stages:
Utility Electricity Charging rule Constant current charging (constant stage)→constant
voltage(constant voltage stage)→float (constant voltage stage)
Utility Electricity Supply
≥98%
Efficiency
Conversion Time (AC to DC) <4ms
Conversion Time (DC to AC) <8ms
AC output specifications
Rated output voltage (V) 220Vac/230Vac/240Vac 110Vac/120Vac/130Vac
Output Voltage Range ±10% rms
Rated output frequency(Hz) 50Hz ± 0.3Hz/60Hz ± 0.3Hz(Optional)
Power Factor 1.0
Output Waveform Pure sine wave
Waveform distortion
≤3% ( Linear load )
rate( THD )
Dynamic Response( 0 ~ 100% ) 5%
Peak Factor ( CF ) 3:1
(110%<Load<125%) ±10% : after 15 minutes disconnecting
the output voltage
Overload Protection (125%<Load<150%) ±10% : after 1 minute disconnecting the
(SMPS load) output voltage
(Load>150%) ±10% : after 20 seconds disconnecting the
output voltage
Other notes
Continuous operation time Continuous operation
Normal Boot no-load Depletion ≤Rated Power×2.5%
No-load Depletion of
≤6W
energy-saving mode
Safety Certification CE(EN62040-1) EMC : EN62040-2, C2
Communication Interface RS232 / (Customizable )
Cooling Temperature-controlled variable speed fan cooling (Ventilation
condition)
Noise( dB 、 1 meter ) < 60dB
Ambient temperature ( ºC ) -10 ~ +45
Storage Temperature( ºC ) -20 ~ +55
Using Environment Humidity 0-95% relative humidity ( No condensation )
Altitude( m ) ≤5000( More than 1000 m, derating )
Display Way LED Indicator +LCD Display
Alarm Way Buzzer sounds alarm
Protection Functions Low voltage protection, high voltage protection, high
temperature protection, short circuit protection, leakage
protection, overcurrent protection, overload protection, low
recovery, high recovery, intelligent temperature control, solid
barrier alarm
Protection Level IP20 / Customizable

6 、 The battery type


set
Because of the batteries have many types, different types of them have different charging parameters,
to effectively protect batteries, we specially design a rotary switch of selected batteries types on the
inverter’s panel. As long as to select the corresponding gear of battery’s type, our inverter can be
guaranteed the most suitable charging specification.

Gear description:

Description of Open-circuit Floating Charging


Switch
corresponding Voltage Voltage
Gears
batter’s type 12V 24V 48V 12V 24V 48V

0 Cancell Charge Not charging (cancell utility grid charging function)


1 Gel USA 14.0 28.0 56.0 13.7 27.4 54.8
2 AGM 1 14.1 28.2 56.4 13.4 26.8 53.6
3 AGM 2 14.6 29.2 58.4 13.7 27.4 54.8
4 Sealed lead acid 14.4 28.8 57.6 13.6 27.2 54.4
5 Gel EURO 14.4 28.8 57.6 13.8 27.6 55.2
6 Open lead acid 14.8 29.6 59.2 13.3 26.6 53.2
7 Calcuim 15.1 30.2 60.4 13.6 27.2 54.4
8 De-acidification 15.5 31.0 62 Shut off after 4 hours
9 Not used - - - -

7. Specification of utility grid charging


mode Specification
Model
1KW 2KW 3KW 4KW 5KW 6KW
12
DC Voltage 24V 12V 24V 12V 24V 24V 48V 24V 48V 24V 48V
V
35
Charge current 20A 65A 35A 75A 45A 65A 35A 70A 40A 75A 50A
A
48
DC Voltage 72V 48V 72V 48V 72V 72V 72V 72V
V

Charge current 9A 6A 15A 10A 30A 15A 20A 25A 30

MCB 10A 20A 30A 30A 30A 30A


Specification
Model
8KW 10KW 12KW
DC Voltage
48V 60V 72V 48V 60V 72V 48V 60V 72V
Charge current
(±5A) 60 50 40 70A 60A 50A 80A 70A 60A

MCB 50A
Initial Charge
According to battery type
Voltage
Charger
short-circuit Circuit Breaker
protection
Constant current charging( Constant current stage) → constant voltage
Charging Rule
charging (constant voltage stage) → float charging (constant voltage stage)
 Boost CC Stage : If AC input is applied, the charger will run at full current in CC
mode until the charger reaches the boost voltage.
 Boost CV Stage: the charger will keep the boost voltage in Boost CV mode .Then
drop the voltage down to the float voltage. The timer has a minimum time of 1 hour
Charge Stage and a maximum time of 12 hours.
Transition  Float Stage: In float mode, the voltage will stay at the float voltage.
Definitions  If the AC is reconnected or the battery voltage drops below 12Vdc/24Vdc, the
charger will reset the cycle above.
 If the charger maintains the float state for 10 days, the charger will reset the
cycle.

8 、 Status description

(1) 、 LCD panel description