IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE)
e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 1 Ver. II (Jan. – Feb. 2016), PP 29-34
www.iosrjournals.org
DOI: 10.9790/1676-11122934 www.iosrjournals.org 29 | Page
Voltages and Reactive Power Controls in Power System Network
Using Automatic Voltage Regulator (Avr) and Static Var
Compensator Methods
J. O. Aibangbee
Department of Electrical &Computer Engineering, Bells University of Technology, Ota, Nigeria
Abstract: The intent of this paper is to analyzed voltage and reactive power control in power systems network
using automatic voltage regulator (AVR) and static AVR compensator methods. An overview of reactive power
and voltage control in generation, transmission and distribution systems such as generators excitations -
automatic voltage regulation (AVR) and Static VAR Compensator (SVC) of reactive power was presented.
Voltage and reactive power control involves proper coordination among the voltage and reactive
power control equipment in the distribution system to obtain an optimum voltage profile and optimum reactive
power flows in the system according to the objective function and operating constraints.
These methods enhance voltage controls, system stability and allow maximal utilization of the
transmission system. Minimize reactive power flows, to reduce active as well as reactive power losses in the
system network. Excitation Controls in power systems keep the terminal voltages of the generators close to
reference values as well as all equipment in the system are within acceptable limits and the reactive power flow
is minimized so as to reduce power losses. SVC enhances the system voltage during heavy load condition and
reduces the over-voltage occurring during light load conditions and to prevent voltage collapse.
Keywords: Reactive Power, Voltage Collapse, voltage control, automatic voltage regulator, Static Var
Compensator, system stability.
I. Introduction
In a modern power system, electrical energy from the generating station is delivered to the ultimate
consumers through a network of transmission and distribution. For satisfactory operation of motors, lamps and
other load, it is desirable that consumers are supplies with substantially constant voltage [1]. Too wide variation
of voltage may cause erratic operation or even mal-functioning of consumers’ appliances. The statutory limit of
voltage variation is ± 6% of declared voltage at consumers’ terminal. Voltage control in an electrical power is
importance for proper operation for electrical power equipment to prevent damage such as overheating of
generators and motors, to reduce transmission losses and to maintain the ability of the system to withstand and
prevent voltage collapse [2].
The principal cause of voltage variation at consumer’s premises is the change in load on the supply
system. When the load on the system increases, the voltage at the consumer’s terminal falls due to the increased
voltage drop in (i) Alternator Synchronous impedance (ii) Transmission line (iii) Transformer impedance and
(iv) distribution.
In order to achieve efficient and reliable operation of power system, the control of voltage and reactive
power should satisfy the following objectives:
 Voltages at all terminals of all equipment in the system are within acceptable limits,
 System stability is enhanced to maximize utilization of the transmission system,
 The reactive power flow is minimized so as to reduce I2
R and I2
X losses.
Almost all power transported or consumed in alternating current (AC) networks, supply or consume two
of powers: real power and reactive power. Real power accomplishes useful work while reactive power supports
the voltage that must be controlled for system reliability. Reactive power is essential to move active power
through the transmission and distribution system to the customer. For AC systems voltage and current pulsate at
the system frequency. Although AC voltage and current pulsate at same frequency, they peak at different time
power is the algebraic product of voltage and current. Real power is the average of power over cycle and
measured by volt-amperes or watt. The portion of power with zero average value called reactive power
measured in volt-amperes reactive or vars [3-4].
Voltages and Reactive Power Controls in Power System Network Using Automatic Voltage…
DOI: 10.9790/1676-11122934 www.iosrjournals.org 30 | Page
II. Methods Description
Methods of Voltage Controls
There are several methods of voltage control. In each method, the system voltage is changed in
accordance with the load to obtain a fairly constant voltage at the consumer’s end of the system. Local controls
are employed at turbine –generator units and at selected voltage controlled buses.
2.1 Overview on Different Voltage and Reactive Power Control Methods
Voltage and reactive power control involves proper coordination among the voltage and reactive power
control equipment in the distribution system to obtain an optimum voltage profile and optimum reactive power
flows in the system according to the objective function and operating constraints. Many Utilities operate shunt
capacitors locally by using conventional controllers, e.g., voltage controller for the OLTC and either voltage,
reactive power or time controllers for the capacitors; to perform basic voltage and reactive power control
functions, e.g., to maintain the voltages in the distribution system within the acceptable range and to minimize
power losses. Different voltage and reactive power control methods have been proposed. Properly locating and
sizing shunt capacitors will decrease power losses. As an improvement to the capacitor planning based on the
load size, methods to include customer load profiles and characteristics in the capacitor planning are proposed in
[5]-[6]. Proper capacitor planning will also improve the voltage profile in the distribution system. The capacitor
locating and sizing is studied and executed in the planning stage of the distribution system. In order to enhance
the distribution system further, the capacitor should also be switched properly in the operation stage of the
distribution system [7], using different types of available capacitor control. Most recently, many researchers
have addressed the problem of voltage and reactive power control in distribution systems by focusing on
automated distribution systems, such as in [8]-[9]. At the moment, the voltage and reactive power control based
on automated distribution systems can be divided into two categories: off-line setting control and real time
control [10]. The off-line setting control, for instance, aims to find a dispatch schedule for the capacitor
switching and the OLTC movement based on a one day ahead load forecast. Meanwhile, the real time control,
[11] for instance, aims to control the capacitor and OLTC based on real time measurements and experiences.
The application of dispatch schedule based load forecasting is motivated by the fact that although there is a
random fluctuation in the load variation, the major component of the load variations is related to weather
conditions. Furthermore, there is a deterministic load pattern during the day due to social activities [12].
Therefore, the load profile is quite predictable. It can be forecasted one-day-ahead with an average error less
than 2% [13]. Different objective functions and operating constraints have been proposed in voltage and reactive
power control with automated distribution systems. Nevertheless, all researchers [14] still consider loss
Minimization and keeping the voltage within the acceptable range as the main objective and constraint in the
voltage and reactive power control. Other references, such as, consider minimization of OLTC operations and
capacitor switching as the objective function.
2.2 Voltage Collapse
Voltage collapse typically occurs in power systems which are usually heavily loaded, faulted and/or
has reactive power shortages. Following voltage instability, a power system undergoes voltage collapse if the
post-disturbance equilibrium voltages near loads are below acceptable limits. Voltage collapse may be total
(blackout) or partial. The absence of voltage stability leads to voltage instability and results in progressive
decrease of voltages. Thus abnormal voltage levels in steady state may be the result of voltage instability which
is a dynamic phenomenon.
The main factors causing voltage instability are
1) The inability of the power system to meet demands for reactive power in the heavily stressed system to
keep voltage in the desired range
2) Characteristics of the reactive power compensation devices
3) Action and Coordination of the voltage control devices
4) Generator reactive power limits
5) Load characteristics
6) Parameters of transmission lines and transformer [4].
III. Evaluation Tests
The following methods of voltage control namely AC Excitation, Shunt capacitors and Static VAR
Compensator in A.C. power system network was analyzed.
a) Locations of Voltage Control Equipment
In a modern power system, there are several element betweens the generating station and the
consumers. The voltage control equipment is used at more than one point in the system for two reasons. Firstly,
Voltages and Reactive Power Controls in Power System Network Using Automatic Voltage…
DOI: 10.9790/1676-11122934 www.iosrjournals.org 31 | Page
the power network is very extensive and there is a considerable voltage drop in transmission and distribution
systems. Secondly, the various circuits of the power system have dissimilar load characteristics. For these
reasons, it is necessary to provide individual means of voltage control for each circuit or group of circuits. In
practice, voltage control equipment is used at Generating stations, Transformer stations and Transmission lines.
b) From circuit operating in sinusoidal steady state, real and reactive powers are conveniently calculated from
complex power.
Let the voltage across a circuit element be V = V∠δ and the current into the element be I∠β. Then the complex
power S is the product of the voltage and the conjugate of the current.
S = VI* = V∠δ I∠β * (1)
= V∠(δ − β) = VICos(δ − β) + jVISin(δ − β),
Where (δ − β) is the angle between the voltage and current.
Also S = P + jQ VA. (2)
Hence the magnitude of S = VI of the complex power is called the apparent power. The apparent power
is the maximum real power that can be delivered to a load. The correct implementation of the apparent energy
measurement is bound by the accuracy of the rms measurements [14].
Reactive power is defined in the IEEE Standard Dictionary 100-1996 under the energy “magner” as: Q =
VnInSin∅n
∞
n=1 (3)
Where Vn and In are respectively the voltage and current rms values of the nth harmonics of the line
frequency, and In is the phase difference between the voltage and the current nth harmonics. A convention is
also adopted stating that the reactive energy should be positive when the current is leading the voltage (inductive
load).In an electrical system containing purely sinusoidal voltage and current waveforms at a fixed frequency,
the measurement of reactive power is easy and can be accomplished using several methods without errors.
However, in the presence of non-sinusoidal waveforms, the energy contained in the harmonics causes
measurement errors. According to the Fourier theorem any periodic waveform can be written as a sum of sin
and cosine waves. As energy meters deal with periodic signals at the line frequency both current and voltage
inputs of a single phase meter can be described by
V (t) = Vn 2 Sin(nwot)∞
n=1 (4)
I (t) = Vn 2 Sin(nwot + ∅n)∞
n=1 (5)
Where Vn and In are defined as in Equation 3; the average active power is defined as:
Average active power P = VnIncos⁡(∅n)∞
n=1 (6)
The implementation of the active power measurement is relatively easy and is done accurately in most energy
meters in the field.
IV. Results and Discussion
4.1 Synchronous Alternators Excitation Controls:
Synchronous Alternators Excitation Controls are used in all power systems to keep the terminal
voltages of the generators close to reference values given by the operator or generated by a secondary controller.
For synchronous alternators, the excitation is provided by a device called exciter. An automatic voltage
regulator (AVR) acts on the exciter of a synchronous machine, which supplies the field voltage and
consequently the current in the field winding of the machine and can thereby regulate its terminal voltage.
Under normal conditions the terminal voltages of generators are maintained constant. When there exist voltage
stability problem due to reactive power demand, generators can supply more power to system in the range of
field current limits. The exciter supplies the field voltage in the field winding. Within the capability limits of the
generator, it can regulate the bus voltage.
The voltage of the generator is proportional to the speed and excitation of the generator. The speed
being constant, the excitation is used to control the voltage. Modern AC Synchronous Alternators employs
brushless AC excitation system as shown in Figure 1. A full wave rectifier converts the exciter AC voltage to
DC voltage. The armature of the exciter, the full wave rectifier and the field of the synchronous generator form
the rotating components. The rotating components are mounted on a common shaft.
Voltages and Reactive Power Controls in Power System Network Using Automatic Voltage…
DOI: 10.9790/1676-11122934 www.iosrjournals.org 32 | Page
Figure 1: Brushless AC excitation system
4.2 Transmission System Voltage Control
In practical operation of transmission systems, the voltage needs to be continuously monitored and
controlled to compensate for the daily changes in load, generation and network structure. In fact, the control of
voltage is a major issue in power system operation. It identifies the main objectives of voltage control as:
Voltage at the terminals of all equipment in the system should be kept within acceptable limits, to avoid
malfunction of and damage to the equipment. Keeping voltages close to the values for which stabilizing controls
are designed, to enhance system stability and allow maximal utilization of the transmission system. Minimize
reactive power flows, to reduce active as well as reactive power losses.
1) Shunt Capacitors
Shunt capacitors and reactors provide passive compensation. They are either permanently connected to the
transmission and distribution system or switched. They contribute to voltage control by modifying the network
characteristics. Static VAR Compensator (SVC) provides active compensation. The voltages of the various
buses to which they are connected are link together with the generating units, they establish voltages at specific
points in the system. Voltages at other locations in the system are determined by active and reactive power flows
through various elements, including the passive compensating devices. The primary purposes of transmission
system shunt compensation near load areas are voltage control and load stabilization. Mechanically switched
shunt capacitor banks are installed at major substations in load areas for producing reactive power and keeping
voltage within required limits. For voltage stability shunt capacitor banks are very useful in allowing nearby
generators to operate near unity power factor. This maximizes fast acting reactive reserve. Compared to SVCs,
mechanically switched capacitor banks have the advantage of much lower cost. Switching speeds can be quite
fast. Current limiting reactors are used to minimize switching transients. There are several disadvantages to
mechanically switched capacitors. For voltage emergencies the shortcoming of shunt capacitor banks is that the
reactive power output drops with the voltage squared. For transient voltage instability the switching may not be
fast enough to prevent induction motor stalling. Precise and rapid control of voltage is not possible. Like
inductors, capacitor banks are discrete devices, but they are often configured with several steps to provide a
limited amount of variable control. If voltage collapse results in a system, the stable parts of the system may
experience damaging over voltages immediately following separation. Shunt capacitors banks are always
connected to the bus rather than to the line. They are connected either directly to the high voltage bus or to the
tertiary winding of the main transformer. Shunt capacitor banks are breaker-switched either automatically by a
voltage relays or manually. Figure 2 shows example of capacitor bank.
Voltages and Reactive Power Controls in Power System Network Using Automatic Voltage…
DOI: 10.9790/1676-11122934 www.iosrjournals.org 33 | Page
Figure 2: Typical capacitor bank Figure 3: a) shunt compensation b) Phasor diagram without compensation
c) Phasor diagram with compensation
The primary purpose of transmission system shunt compensation near load areas is voltage control and
load stabilization. In other words, shunt capacitors are used to compensate for I2
X losses in transmission system
and to ensure satisfactory voltage levels during heavy load conditions. Shunt capacitors are used in power
system for power factor correction. The objective of power factor correction is to provide reactive power close
to point where it is being consumed, rather than supply it from remote sources. Figure 3 shows the influence of
shunt compensation on load bus.
Switched shunt capacitors are also used for feeder voltage control. They are installed at appropriate
location along the length of the feeder to ensure that voltages at all points remain the allowable minimum or
maximum limits as the loads vary. For voltage stability, shunt capacitor banks are very useful on allowing
nearby generators to operate near unity power factor. This maximizes fast acting reactive reserve. Shunt
capacitors are installed near the load terminals, in factory substations, in the receiving substations, in switching
substation etc. to provide leading volt-ampere-reactive (VAR) and thus to reduce the line current and total KVA
loading of the substation transformer. By using shunt capacitors line drop is reduced and the voltage regulation
is improved. Shunt capacitors are switch-in when KVA demand on the distribution system rises and voltage of
the bus drops.
2) Static VAR Compensator
Shunt capacitor compensation is required to enhance the system voltage during heavy load condition
while shunt reactors are needed to reduce the over-voltage occurring during light load conditions. Static VAR
Compensator (SVC) can perform these two tasks together utilizing the Thyristor Controlled Reactor (TCR).
SVC is basically a parallel combination of controlled reactor and a fixed capacitor as shown in Figure 4.
The reactor control is done by an anti-parallel thyristor switch assembly. The firing angle of the
thyristors governs the voltage across the inductor, thus controlling the reactor current. Thereby the reactive
power absorbed by the inductor can be controlled. The capacitor, in parallel with the reactor, supplies the
reactive power of QC VAR to the system. If QL is the reactive power absorbed by the reactor, the net reactive
power injection to the bus becomes; Qnet = Qc -QL
In SVC, reactive power QL can be varied and thus reactive power Qnet is controllable. During heavy
load period, QL is lesser than QC while during light load condition, QL is greater than QC. Being static, this
equipment is more advantageous than synchronous compensator.
Voltages and Reactive Power Controls in Power System Network Using Automatic Voltage…
DOI: 10.9790/1676-11122934 www.iosrjournals.org 34 | Page
Figure 4: Static VAR Compensator (SVC)
V. Conclusion
 An automatic voltage regulator (AVR) acts on the exciter of a synchronous machine, which supplies the
field voltage and consequently the current in the field winding of the machine and can thereby regulate its
terminal voltage.
 Voltages at all terminals of all equipment in the system are within acceptable limits,
 System stability is enhanced to maximize utilization of the transmission system,
 The reactive power flow is minimized so as to reduce I2
R and I2
X losses.
 Excitation Controls in power systems keep the terminal voltages of the generators close to reference values
as well as all equipment in the system are within acceptable limits and the reactive power flow is minimized
so as to reduce power losses.
 The SVC and Shunt Capacitors provide fast control and help improve system stability.
References
[1]. Mehta, v. k. “principles of power system”, 8 Edition, S. CHAND Books Ltd, New Delhi 1998.
[2]. Aibangbee J. O. “Power System Controls”, Bells University of Technology; Ota –Nigeria. pp 74-75, 2012.
[3]. Gupta J. B. “A Course on Power System”, 11th
Edition, S.K. Kataria Books Ltd. Delhi 2012.
[4]. Ravinder Kumar and Ankit Dixit “Power System Operation and Control EEE 031” 2014
[5]. Proceedings of Bulk Power System Voltage Phenomena- Voltage Stability and Security. Potosi, MO, September 19-24, 1988.
[6]. Proceedings of NSF Workshop on Bulk Power System Voltage Phenomena-Voltage Stability and Security. Deep Creek Lake,
MD, August 4-7, 1991.
[7]. Proceedings of Bulk Power System Voltage Phenomena 111- Seminar on Voltage Stability, Security and Control. Davos,
Switzerland, August 22-26, 1994.
[8]. Proceedings of the Symposium on Bulk Power System Dynamics and Control IV- Restructuring. Santorini, Greece, August 24-28,
1998.
[9]. Proceedings of Bulk Power Systems Dynamics and Control Security and Reliability in a Changing Environment. Onomichi, Japan,
August 26-31, 2001.
[10]. C.D. Vournas, P.W. Sauer, and M.A. Pai. Relationships between Voltage and Angel Stability of Power Systems. International
Journal of Electrical Power and Energy Systems, 18:493-500, 1996.
[11]. H.P. St. Clair. Practical Concepts in Capability and Performance of Transmission Lines. AIEE Dansactions, 72: 1152-1 157, 1953.
[12]. C.W. Taylor. Power System Voltage Stability. McGraw-Hill, New York, 1994.
[13]. W.R. Lachs. Voltage Collapse in EHV Power Systems. Paper A78057-2, 1978 IEEE PES Winter Meeting, New York, January 28-
February 3, 1978.
[14]. Duncan Glover et al, 2005. “Power system analysis and design” Fourth Edition.

More Related Content

PDF
An Overview of Facts Devices used for Reactive Power Compensation Techniques
PDF
Research Inventy : International Journal of Engineering and Science
PPTX
ELECTRICAL POWER QUALITY ENHANCEMENT OF GRID INTERFACED WITH WIND POWER SYSTE...
PPTX
power quality conditioners
PDF
Power Quality Improvement in Power System using UPFC
PDF
Steady State Operation And Enhancement Of Transient Stability In Hydel Power...
An Overview of Facts Devices used for Reactive Power Compensation Techniques
Research Inventy : International Journal of Engineering and Science
ELECTRICAL POWER QUALITY ENHANCEMENT OF GRID INTERFACED WITH WIND POWER SYSTE...
power quality conditioners
Power Quality Improvement in Power System using UPFC
Steady State Operation And Enhancement Of Transient Stability In Hydel Power...

What's hot (19)

PDF
International Journal of Engineering Research and Development
PPTX
Optimal Placement of FACTS Controller
PDF
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
PDF
Controllers For A VSC-HVDC Link Connected To A Weak AC System
PDF
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
PDF
Power Flow Control using Quadrature Boosters
PDF
Power Quality Improvement by UPQC based on Voltage Source Converters
PPT
POWER QUALITY
PPTX
Design of self tuning pi controller for statcom using bats echolocation algor...
PPTX
NEW STATCOM CONTROL SCHEME FOR POWER QUALITY IMPROVEMENT IN WIND FARM.
PPTX
power quality improvement in distrution system using D statcom
PDF
Simulation and Analysis of a D-STATCOM for Load Compensation and Power Facto...
PDF
Voltage dip mitigation in distribution system by using d statcom
PDF
Online voltage stability margin assessment
PDF
12 16134 paper 064 ijeecs(edit)
PDF
Power Quality Improvement Using FACT Devices
PDF
Unified power quality conditioner for compensating power quality problem ad
PDF
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
PDF
International Journal of Engineering Research and Development
Optimal Placement of FACTS Controller
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
Controllers For A VSC-HVDC Link Connected To A Weak AC System
Design of UPQC with Minimization of DC Link voltage for the Improvement of Po...
Power Flow Control using Quadrature Boosters
Power Quality Improvement by UPQC based on Voltage Source Converters
POWER QUALITY
Design of self tuning pi controller for statcom using bats echolocation algor...
NEW STATCOM CONTROL SCHEME FOR POWER QUALITY IMPROVEMENT IN WIND FARM.
power quality improvement in distrution system using D statcom
Simulation and Analysis of a D-STATCOM for Load Compensation and Power Facto...
Voltage dip mitigation in distribution system by using d statcom
Online voltage stability margin assessment
12 16134 paper 064 ijeecs(edit)
Power Quality Improvement Using FACT Devices
Unified power quality conditioner for compensating power quality problem ad
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
Ad

Viewers also liked (20)

PDF
H1303065861
PDF
Importance of Development of Quality Checklists
PDF
D013112636
PDF
I012636670
PDF
G1303074851
PDF
H1302023840
PDF
G012534551
PDF
Relationship of Kabaddi Performance with Selected Coordinative Ability of the...
PDF
D010212533
PDF
Characteristics analysis of silicon carbide based 1-D Photonic crystal with 2...
PDF
E017131924
PDF
C017251622
PDF
C017351116
PDF
I017225966
PDF
N1304038490
PDF
F1803042939
PDF
Peak to Average Power Ratio Reduction in Mc Cdma System by Using Pulse Shapin...
PDF
L1304028190
PDF
N13030789100
PDF
B1103031217
H1303065861
Importance of Development of Quality Checklists
D013112636
I012636670
G1303074851
H1302023840
G012534551
Relationship of Kabaddi Performance with Selected Coordinative Ability of the...
D010212533
Characteristics analysis of silicon carbide based 1-D Photonic crystal with 2...
E017131924
C017251622
C017351116
I017225966
N1304038490
F1803042939
Peak to Average Power Ratio Reduction in Mc Cdma System by Using Pulse Shapin...
L1304028190
N13030789100
B1103031217
Ad

Similar to D011122934 (20)

PDF
Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...
PDF
Power system operation Question and answers
PDF
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
PDF
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
DOCX
Thyristor switched capacitor
PDF
International Journal of Engineering Research and Development
PDF
Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage S...
DOCX
High_reactive_power_DOC.docx
PDF
Improvement of Power Quality by using Injection Super Capacitor UPQC for BLDC...
PDF
B04931120
PDF
International Journal of Computational Engineering Research(IJCER)
PDF
IRJET - Power Quality Improvement in Distribution Power System using STATCOM
PDF
Voltage collapse mitigation by reactive power
PDF
report of Improvement of the Electric Power Quality Using Series Active and S...
PDF
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
PDF
D010121832
PDF
Power quality enhancement by improving voltage stability using dstatcom
PDF
Comparative Application of Load Tap-Changing Transformer (LTCT) and Shunt Cap...
PDF
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
PDF
40220130406009 2
Concepts of Reactive Power Control and Voltage Stability Methods in Power Sys...
Power system operation Question and answers
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Thyristor switched capacitor
International Journal of Engineering Research and Development
Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage S...
High_reactive_power_DOC.docx
Improvement of Power Quality by using Injection Super Capacitor UPQC for BLDC...
B04931120
International Journal of Computational Engineering Research(IJCER)
IRJET - Power Quality Improvement in Distribution Power System using STATCOM
Voltage collapse mitigation by reactive power
report of Improvement of the Electric Power Quality Using Series Active and S...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
D010121832
Power quality enhancement by improving voltage stability using dstatcom
Comparative Application of Load Tap-Changing Transformer (LTCT) and Shunt Cap...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
40220130406009 2

More from IOSR Journals (20)

PDF
A011140104
PDF
M0111397100
PDF
L011138596
PDF
K011138084
PDF
J011137479
PDF
I011136673
PDF
G011134454
PDF
H011135565
PDF
F011134043
PDF
E011133639
PDF
D011132635
PDF
C011131925
PDF
B011130918
PDF
A011130108
PDF
I011125160
PDF
H011124050
PDF
G011123539
PDF
F011123134
PDF
E011122530
PDF
D011121524
A011140104
M0111397100
L011138596
K011138084
J011137479
I011136673
G011134454
H011135565
F011134043
E011133639
D011132635
C011131925
B011130918
A011130108
I011125160
H011124050
G011123539
F011123134
E011122530
D011121524

Recently uploaded (20)

PDF
CXOs-Are-you-still-doing-manual-DevOps-in-the-age-of-AI.pdf
PDF
Accessing-Finance-in-Jordan-MENA 2024 2025.pdf
PDF
Lung cancer patients survival prediction using outlier detection and optimize...
PDF
The-Future-of-Automotive-Quality-is-Here-AI-Driven-Engineering.pdf
PDF
Planning-an-Audit-A-How-To-Guide-Checklist-WP.pdf
PPTX
Training Program for knowledge in solar cell and solar industry
PDF
Data Virtualization in Action: Scaling APIs and Apps with FME
PPTX
Configure Apache Mutual Authentication
PDF
MENA-ECEONOMIC-CONTEXT-VC MENA-ECEONOMIC
PPTX
Internet of Everything -Basic concepts details
PDF
Transform-Quality-Engineering-with-AI-A-60-Day-Blueprint-for-Digital-Success.pdf
PDF
Co-training pseudo-labeling for text classification with support vector machi...
PDF
INTERSPEECH 2025 「Recent Advances and Future Directions in Voice Conversion」
PDF
NewMind AI Weekly Chronicles – August ’25 Week IV
PDF
Auditboard EB SOX Playbook 2023 edition.
PDF
Dell Pro Micro: Speed customer interactions, patient processing, and learning...
PDF
Convolutional neural network based encoder-decoder for efficient real-time ob...
PDF
AI.gov: A Trojan Horse in the Age of Artificial Intelligence
PDF
“A New Era of 3D Sensing: Transforming Industries and Creating Opportunities,...
PDF
4 layer Arch & Reference Arch of IoT.pdf
CXOs-Are-you-still-doing-manual-DevOps-in-the-age-of-AI.pdf
Accessing-Finance-in-Jordan-MENA 2024 2025.pdf
Lung cancer patients survival prediction using outlier detection and optimize...
The-Future-of-Automotive-Quality-is-Here-AI-Driven-Engineering.pdf
Planning-an-Audit-A-How-To-Guide-Checklist-WP.pdf
Training Program for knowledge in solar cell and solar industry
Data Virtualization in Action: Scaling APIs and Apps with FME
Configure Apache Mutual Authentication
MENA-ECEONOMIC-CONTEXT-VC MENA-ECEONOMIC
Internet of Everything -Basic concepts details
Transform-Quality-Engineering-with-AI-A-60-Day-Blueprint-for-Digital-Success.pdf
Co-training pseudo-labeling for text classification with support vector machi...
INTERSPEECH 2025 「Recent Advances and Future Directions in Voice Conversion」
NewMind AI Weekly Chronicles – August ’25 Week IV
Auditboard EB SOX Playbook 2023 edition.
Dell Pro Micro: Speed customer interactions, patient processing, and learning...
Convolutional neural network based encoder-decoder for efficient real-time ob...
AI.gov: A Trojan Horse in the Age of Artificial Intelligence
“A New Era of 3D Sensing: Transforming Industries and Creating Opportunities,...
4 layer Arch & Reference Arch of IoT.pdf

D011122934

  • 1. IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 1 Ver. II (Jan. – Feb. 2016), PP 29-34 www.iosrjournals.org DOI: 10.9790/1676-11122934 www.iosrjournals.org 29 | Page Voltages and Reactive Power Controls in Power System Network Using Automatic Voltage Regulator (Avr) and Static Var Compensator Methods J. O. Aibangbee Department of Electrical &Computer Engineering, Bells University of Technology, Ota, Nigeria Abstract: The intent of this paper is to analyzed voltage and reactive power control in power systems network using automatic voltage regulator (AVR) and static AVR compensator methods. An overview of reactive power and voltage control in generation, transmission and distribution systems such as generators excitations - automatic voltage regulation (AVR) and Static VAR Compensator (SVC) of reactive power was presented. Voltage and reactive power control involves proper coordination among the voltage and reactive power control equipment in the distribution system to obtain an optimum voltage profile and optimum reactive power flows in the system according to the objective function and operating constraints. These methods enhance voltage controls, system stability and allow maximal utilization of the transmission system. Minimize reactive power flows, to reduce active as well as reactive power losses in the system network. Excitation Controls in power systems keep the terminal voltages of the generators close to reference values as well as all equipment in the system are within acceptable limits and the reactive power flow is minimized so as to reduce power losses. SVC enhances the system voltage during heavy load condition and reduces the over-voltage occurring during light load conditions and to prevent voltage collapse. Keywords: Reactive Power, Voltage Collapse, voltage control, automatic voltage regulator, Static Var Compensator, system stability. I. Introduction In a modern power system, electrical energy from the generating station is delivered to the ultimate consumers through a network of transmission and distribution. For satisfactory operation of motors, lamps and other load, it is desirable that consumers are supplies with substantially constant voltage [1]. Too wide variation of voltage may cause erratic operation or even mal-functioning of consumers’ appliances. The statutory limit of voltage variation is ± 6% of declared voltage at consumers’ terminal. Voltage control in an electrical power is importance for proper operation for electrical power equipment to prevent damage such as overheating of generators and motors, to reduce transmission losses and to maintain the ability of the system to withstand and prevent voltage collapse [2]. The principal cause of voltage variation at consumer’s premises is the change in load on the supply system. When the load on the system increases, the voltage at the consumer’s terminal falls due to the increased voltage drop in (i) Alternator Synchronous impedance (ii) Transmission line (iii) Transformer impedance and (iv) distribution. In order to achieve efficient and reliable operation of power system, the control of voltage and reactive power should satisfy the following objectives:  Voltages at all terminals of all equipment in the system are within acceptable limits,  System stability is enhanced to maximize utilization of the transmission system,  The reactive power flow is minimized so as to reduce I2 R and I2 X losses. Almost all power transported or consumed in alternating current (AC) networks, supply or consume two of powers: real power and reactive power. Real power accomplishes useful work while reactive power supports the voltage that must be controlled for system reliability. Reactive power is essential to move active power through the transmission and distribution system to the customer. For AC systems voltage and current pulsate at the system frequency. Although AC voltage and current pulsate at same frequency, they peak at different time power is the algebraic product of voltage and current. Real power is the average of power over cycle and measured by volt-amperes or watt. The portion of power with zero average value called reactive power measured in volt-amperes reactive or vars [3-4].
  • 2. Voltages and Reactive Power Controls in Power System Network Using Automatic Voltage… DOI: 10.9790/1676-11122934 www.iosrjournals.org 30 | Page II. Methods Description Methods of Voltage Controls There are several methods of voltage control. In each method, the system voltage is changed in accordance with the load to obtain a fairly constant voltage at the consumer’s end of the system. Local controls are employed at turbine –generator units and at selected voltage controlled buses. 2.1 Overview on Different Voltage and Reactive Power Control Methods Voltage and reactive power control involves proper coordination among the voltage and reactive power control equipment in the distribution system to obtain an optimum voltage profile and optimum reactive power flows in the system according to the objective function and operating constraints. Many Utilities operate shunt capacitors locally by using conventional controllers, e.g., voltage controller for the OLTC and either voltage, reactive power or time controllers for the capacitors; to perform basic voltage and reactive power control functions, e.g., to maintain the voltages in the distribution system within the acceptable range and to minimize power losses. Different voltage and reactive power control methods have been proposed. Properly locating and sizing shunt capacitors will decrease power losses. As an improvement to the capacitor planning based on the load size, methods to include customer load profiles and characteristics in the capacitor planning are proposed in [5]-[6]. Proper capacitor planning will also improve the voltage profile in the distribution system. The capacitor locating and sizing is studied and executed in the planning stage of the distribution system. In order to enhance the distribution system further, the capacitor should also be switched properly in the operation stage of the distribution system [7], using different types of available capacitor control. Most recently, many researchers have addressed the problem of voltage and reactive power control in distribution systems by focusing on automated distribution systems, such as in [8]-[9]. At the moment, the voltage and reactive power control based on automated distribution systems can be divided into two categories: off-line setting control and real time control [10]. The off-line setting control, for instance, aims to find a dispatch schedule for the capacitor switching and the OLTC movement based on a one day ahead load forecast. Meanwhile, the real time control, [11] for instance, aims to control the capacitor and OLTC based on real time measurements and experiences. The application of dispatch schedule based load forecasting is motivated by the fact that although there is a random fluctuation in the load variation, the major component of the load variations is related to weather conditions. Furthermore, there is a deterministic load pattern during the day due to social activities [12]. Therefore, the load profile is quite predictable. It can be forecasted one-day-ahead with an average error less than 2% [13]. Different objective functions and operating constraints have been proposed in voltage and reactive power control with automated distribution systems. Nevertheless, all researchers [14] still consider loss Minimization and keeping the voltage within the acceptable range as the main objective and constraint in the voltage and reactive power control. Other references, such as, consider minimization of OLTC operations and capacitor switching as the objective function. 2.2 Voltage Collapse Voltage collapse typically occurs in power systems which are usually heavily loaded, faulted and/or has reactive power shortages. Following voltage instability, a power system undergoes voltage collapse if the post-disturbance equilibrium voltages near loads are below acceptable limits. Voltage collapse may be total (blackout) or partial. The absence of voltage stability leads to voltage instability and results in progressive decrease of voltages. Thus abnormal voltage levels in steady state may be the result of voltage instability which is a dynamic phenomenon. The main factors causing voltage instability are 1) The inability of the power system to meet demands for reactive power in the heavily stressed system to keep voltage in the desired range 2) Characteristics of the reactive power compensation devices 3) Action and Coordination of the voltage control devices 4) Generator reactive power limits 5) Load characteristics 6) Parameters of transmission lines and transformer [4]. III. Evaluation Tests The following methods of voltage control namely AC Excitation, Shunt capacitors and Static VAR Compensator in A.C. power system network was analyzed. a) Locations of Voltage Control Equipment In a modern power system, there are several element betweens the generating station and the consumers. The voltage control equipment is used at more than one point in the system for two reasons. Firstly,
  • 3. Voltages and Reactive Power Controls in Power System Network Using Automatic Voltage… DOI: 10.9790/1676-11122934 www.iosrjournals.org 31 | Page the power network is very extensive and there is a considerable voltage drop in transmission and distribution systems. Secondly, the various circuits of the power system have dissimilar load characteristics. For these reasons, it is necessary to provide individual means of voltage control for each circuit or group of circuits. In practice, voltage control equipment is used at Generating stations, Transformer stations and Transmission lines. b) From circuit operating in sinusoidal steady state, real and reactive powers are conveniently calculated from complex power. Let the voltage across a circuit element be V = V∠δ and the current into the element be I∠β. Then the complex power S is the product of the voltage and the conjugate of the current. S = VI* = V∠δ I∠β * (1) = V∠(δ − β) = VICos(δ − β) + jVISin(δ − β), Where (δ − β) is the angle between the voltage and current. Also S = P + jQ VA. (2) Hence the magnitude of S = VI of the complex power is called the apparent power. The apparent power is the maximum real power that can be delivered to a load. The correct implementation of the apparent energy measurement is bound by the accuracy of the rms measurements [14]. Reactive power is defined in the IEEE Standard Dictionary 100-1996 under the energy “magner” as: Q = VnInSin∅n ∞ n=1 (3) Where Vn and In are respectively the voltage and current rms values of the nth harmonics of the line frequency, and In is the phase difference between the voltage and the current nth harmonics. A convention is also adopted stating that the reactive energy should be positive when the current is leading the voltage (inductive load).In an electrical system containing purely sinusoidal voltage and current waveforms at a fixed frequency, the measurement of reactive power is easy and can be accomplished using several methods without errors. However, in the presence of non-sinusoidal waveforms, the energy contained in the harmonics causes measurement errors. According to the Fourier theorem any periodic waveform can be written as a sum of sin and cosine waves. As energy meters deal with periodic signals at the line frequency both current and voltage inputs of a single phase meter can be described by V (t) = Vn 2 Sin(nwot)∞ n=1 (4) I (t) = Vn 2 Sin(nwot + ∅n)∞ n=1 (5) Where Vn and In are defined as in Equation 3; the average active power is defined as: Average active power P = VnIncos⁡(∅n)∞ n=1 (6) The implementation of the active power measurement is relatively easy and is done accurately in most energy meters in the field. IV. Results and Discussion 4.1 Synchronous Alternators Excitation Controls: Synchronous Alternators Excitation Controls are used in all power systems to keep the terminal voltages of the generators close to reference values given by the operator or generated by a secondary controller. For synchronous alternators, the excitation is provided by a device called exciter. An automatic voltage regulator (AVR) acts on the exciter of a synchronous machine, which supplies the field voltage and consequently the current in the field winding of the machine and can thereby regulate its terminal voltage. Under normal conditions the terminal voltages of generators are maintained constant. When there exist voltage stability problem due to reactive power demand, generators can supply more power to system in the range of field current limits. The exciter supplies the field voltage in the field winding. Within the capability limits of the generator, it can regulate the bus voltage. The voltage of the generator is proportional to the speed and excitation of the generator. The speed being constant, the excitation is used to control the voltage. Modern AC Synchronous Alternators employs brushless AC excitation system as shown in Figure 1. A full wave rectifier converts the exciter AC voltage to DC voltage. The armature of the exciter, the full wave rectifier and the field of the synchronous generator form the rotating components. The rotating components are mounted on a common shaft.
  • 4. Voltages and Reactive Power Controls in Power System Network Using Automatic Voltage… DOI: 10.9790/1676-11122934 www.iosrjournals.org 32 | Page Figure 1: Brushless AC excitation system 4.2 Transmission System Voltage Control In practical operation of transmission systems, the voltage needs to be continuously monitored and controlled to compensate for the daily changes in load, generation and network structure. In fact, the control of voltage is a major issue in power system operation. It identifies the main objectives of voltage control as: Voltage at the terminals of all equipment in the system should be kept within acceptable limits, to avoid malfunction of and damage to the equipment. Keeping voltages close to the values for which stabilizing controls are designed, to enhance system stability and allow maximal utilization of the transmission system. Minimize reactive power flows, to reduce active as well as reactive power losses. 1) Shunt Capacitors Shunt capacitors and reactors provide passive compensation. They are either permanently connected to the transmission and distribution system or switched. They contribute to voltage control by modifying the network characteristics. Static VAR Compensator (SVC) provides active compensation. The voltages of the various buses to which they are connected are link together with the generating units, they establish voltages at specific points in the system. Voltages at other locations in the system are determined by active and reactive power flows through various elements, including the passive compensating devices. The primary purposes of transmission system shunt compensation near load areas are voltage control and load stabilization. Mechanically switched shunt capacitor banks are installed at major substations in load areas for producing reactive power and keeping voltage within required limits. For voltage stability shunt capacitor banks are very useful in allowing nearby generators to operate near unity power factor. This maximizes fast acting reactive reserve. Compared to SVCs, mechanically switched capacitor banks have the advantage of much lower cost. Switching speeds can be quite fast. Current limiting reactors are used to minimize switching transients. There are several disadvantages to mechanically switched capacitors. For voltage emergencies the shortcoming of shunt capacitor banks is that the reactive power output drops with the voltage squared. For transient voltage instability the switching may not be fast enough to prevent induction motor stalling. Precise and rapid control of voltage is not possible. Like inductors, capacitor banks are discrete devices, but they are often configured with several steps to provide a limited amount of variable control. If voltage collapse results in a system, the stable parts of the system may experience damaging over voltages immediately following separation. Shunt capacitors banks are always connected to the bus rather than to the line. They are connected either directly to the high voltage bus or to the tertiary winding of the main transformer. Shunt capacitor banks are breaker-switched either automatically by a voltage relays or manually. Figure 2 shows example of capacitor bank.
  • 5. Voltages and Reactive Power Controls in Power System Network Using Automatic Voltage… DOI: 10.9790/1676-11122934 www.iosrjournals.org 33 | Page Figure 2: Typical capacitor bank Figure 3: a) shunt compensation b) Phasor diagram without compensation c) Phasor diagram with compensation The primary purpose of transmission system shunt compensation near load areas is voltage control and load stabilization. In other words, shunt capacitors are used to compensate for I2 X losses in transmission system and to ensure satisfactory voltage levels during heavy load conditions. Shunt capacitors are used in power system for power factor correction. The objective of power factor correction is to provide reactive power close to point where it is being consumed, rather than supply it from remote sources. Figure 3 shows the influence of shunt compensation on load bus. Switched shunt capacitors are also used for feeder voltage control. They are installed at appropriate location along the length of the feeder to ensure that voltages at all points remain the allowable minimum or maximum limits as the loads vary. For voltage stability, shunt capacitor banks are very useful on allowing nearby generators to operate near unity power factor. This maximizes fast acting reactive reserve. Shunt capacitors are installed near the load terminals, in factory substations, in the receiving substations, in switching substation etc. to provide leading volt-ampere-reactive (VAR) and thus to reduce the line current and total KVA loading of the substation transformer. By using shunt capacitors line drop is reduced and the voltage regulation is improved. Shunt capacitors are switch-in when KVA demand on the distribution system rises and voltage of the bus drops. 2) Static VAR Compensator Shunt capacitor compensation is required to enhance the system voltage during heavy load condition while shunt reactors are needed to reduce the over-voltage occurring during light load conditions. Static VAR Compensator (SVC) can perform these two tasks together utilizing the Thyristor Controlled Reactor (TCR). SVC is basically a parallel combination of controlled reactor and a fixed capacitor as shown in Figure 4. The reactor control is done by an anti-parallel thyristor switch assembly. The firing angle of the thyristors governs the voltage across the inductor, thus controlling the reactor current. Thereby the reactive power absorbed by the inductor can be controlled. The capacitor, in parallel with the reactor, supplies the reactive power of QC VAR to the system. If QL is the reactive power absorbed by the reactor, the net reactive power injection to the bus becomes; Qnet = Qc -QL In SVC, reactive power QL can be varied and thus reactive power Qnet is controllable. During heavy load period, QL is lesser than QC while during light load condition, QL is greater than QC. Being static, this equipment is more advantageous than synchronous compensator.
  • 6. Voltages and Reactive Power Controls in Power System Network Using Automatic Voltage… DOI: 10.9790/1676-11122934 www.iosrjournals.org 34 | Page Figure 4: Static VAR Compensator (SVC) V. Conclusion  An automatic voltage regulator (AVR) acts on the exciter of a synchronous machine, which supplies the field voltage and consequently the current in the field winding of the machine and can thereby regulate its terminal voltage.  Voltages at all terminals of all equipment in the system are within acceptable limits,  System stability is enhanced to maximize utilization of the transmission system,  The reactive power flow is minimized so as to reduce I2 R and I2 X losses.  Excitation Controls in power systems keep the terminal voltages of the generators close to reference values as well as all equipment in the system are within acceptable limits and the reactive power flow is minimized so as to reduce power losses.  The SVC and Shunt Capacitors provide fast control and help improve system stability. References [1]. Mehta, v. k. “principles of power system”, 8 Edition, S. CHAND Books Ltd, New Delhi 1998. [2]. Aibangbee J. O. “Power System Controls”, Bells University of Technology; Ota –Nigeria. pp 74-75, 2012. [3]. Gupta J. B. “A Course on Power System”, 11th Edition, S.K. Kataria Books Ltd. Delhi 2012. [4]. Ravinder Kumar and Ankit Dixit “Power System Operation and Control EEE 031” 2014 [5]. Proceedings of Bulk Power System Voltage Phenomena- Voltage Stability and Security. Potosi, MO, September 19-24, 1988. [6]. Proceedings of NSF Workshop on Bulk Power System Voltage Phenomena-Voltage Stability and Security. Deep Creek Lake, MD, August 4-7, 1991. [7]. Proceedings of Bulk Power System Voltage Phenomena 111- Seminar on Voltage Stability, Security and Control. Davos, Switzerland, August 22-26, 1994. [8]. Proceedings of the Symposium on Bulk Power System Dynamics and Control IV- Restructuring. Santorini, Greece, August 24-28, 1998. [9]. Proceedings of Bulk Power Systems Dynamics and Control Security and Reliability in a Changing Environment. Onomichi, Japan, August 26-31, 2001. [10]. C.D. Vournas, P.W. Sauer, and M.A. Pai. Relationships between Voltage and Angel Stability of Power Systems. International Journal of Electrical Power and Energy Systems, 18:493-500, 1996. [11]. H.P. St. Clair. Practical Concepts in Capability and Performance of Transmission Lines. AIEE Dansactions, 72: 1152-1 157, 1953. [12]. C.W. Taylor. Power System Voltage Stability. McGraw-Hill, New York, 1994. [13]. W.R. Lachs. Voltage Collapse in EHV Power Systems. Paper A78057-2, 1978 IEEE PES Winter Meeting, New York, January 28- February 3, 1978. [14]. Duncan Glover et al, 2005. “Power system analysis and design” Fourth Edition.