INFFUSER®
INDUCTION DIFFUSERS

…Breathing Life
Into Your Building…

1
SB-INF/1.0 (09/12)

DADANCO.COM

®
Our Mission…
“To be the leading specialist in energy efficient and environmentally sustainable HVAC technologies
and technical expertise, with the aim of delivering the most efficient and value added solution.”

Going Beyond Conventional Wisdom…
In the design of a typical HVAC system many decisions are made based largely on past experience and
conventional wisdom. While this often results in a satisfactory system, it may not result in an optimal
“green” design. With the movement toward sustainable building designs, there is an increased emphasis
on improving both the energy efficiency and comfort level of all types of HVAC systems.
Variable Air Volume (VAV) systems typically provide adequate room temperature control, but there
are often concerns about air movement and humidity control at part load conditions. In addition, the
supply fans in an ‘all-air’ HVAC system tend to consume the most energy in a typical North American
commercial building.
DADANCO INFFUSERS offer an opportunity to improve both the energy efficiency and comfort level of
VAV systems, as well as in other conventional HVAC systems in many market sectors including Schools
and Universities, Healthcare and Hospitals, Hotels, Laboratories, Commercial offices, Government,
Institutional and Defense buildings, either for New build or Green renovation.

Contents…
What is an INFFUSER	

Page 3

What is Internal or External entrainment	

Page 4

Why are INFFUSERS “Green”	

Page 5

Induction versus Aspiration 	

Page 6

Common Applications	

Page 7

2
What is an INFFUSER…
DADANCO’s INFFUSERS are quite
IDL20e
(Linear 2–way discharge)

simply an ‘induction diffuser’ that
uses special nozzles located in the
underside of the air plenum to mix
primary air (ducted from the central
air handling plant) with secondary air
that is Induced from either the ceiling
return air plenum (via *External
entrainment) or room (via *Internal
entrainment) to increase the total
amount of air delivered to the space.

When INFFUSERS are used in conjunction with low temperature supply air systems that operate with
primary air temperatures in the range of 48°F-50°F, the correct selection based on the space design
conditions will ensure that the mixed air (primary plus secondary) delivered by the INFFUSER is above
the room dew point, without the need for local fans, filters, controls or power supply at the outlet.
INFFUSERS have been successfully used in conjunction with primary air temperatures as low as 43°F,
however such applications must be referred to DADANCO for approval. INFFUSERS are an ideal
replacement outlet for conditioned spaces that suffer from poor or inadequate air movement. They
are available as either a 4’ long or continuous 1 slot 1-way or 2 slot 2–way linear diffuser or as a 2’ x 2’ 4–
way diffuser, all with the option of either *Internal or *External entrainment. DADANCO’s technology
nozzles rapidly induce secondary air to reduce the momentum and height of the potential core zone,
significantly reducing noise generation.
DADANCO INFFUSERS are whisper
quiet at inlet static pressures in the
range of 0.1 - 0.3” w.c., and are suitable
for use in any air distribution system
where increased air movement and
tempered primary air temperatures
would be of benefit.

(*see entrainment description on page 4)
IDS60e
(Square 4–way discharge)

3
What is Internal or External
entrainment…

1

With Internal entrainment models the
conditioned primary air from the central air

2

handling plant (1) is ducted into the INFFUSER
plenum (2). This air leaves the plenum through

3

a series of nozzles located in its underside into
a sub divided mixing chamber behind the
diffuser (3). This process induces secondary
room air (4) up through the central area of
the diffuser into the Inffuser mixing chamber
directly from the room where it’s mixed with
the primary air. This mixed (and tempered) air

5

(5) is then discharged into the room via the

5

outer areas of the diffuser.

4
Internal Entrainment

1
With External entrainment models the
conditioned primary air from the central
air handling plant (1) is ducted into the
INFFUSER plenum (2). This air leaves the

2

plenum through a series of nozzles located in
its underside. This process
induces secondary air from

3

the ceiling return air plenum
(3) into the discharge path from the
nozzles where it mixes with the primary air.
This mixed (and tempered) air (4) is then

4

discharged into the room via the diffuser.
In both cases the primary air is tempered

4
External Entrainment

by the induced secondary air before the
combination is discharged into the room via
the diffuser.

4
Why are Inffusers “Green”…
In an “all-air” system such as VAV, primary air is typically delivered to the room at 55ºF. Most designers,
striving to reduce energy and save space, never consider the merits of using lower primary air
temperature due to their concerns about achieving occupier comfort while delivering colder air.
On a typical building (at sea level) with

50%

a space design temperature of 75ºF

45%

every ton of cooling needed, 553 cfm
of primary air has to be conditioned
and delivered by the central plant.
When the temperature is lowered by
5ºF to 50ºF (25 ΔT), the air volume is
reduced to 443 cfm (approximately 20%
less to provide the same amount of

40%

% Change in Primary Air Flow

and primary air at 55ºF (20 ΔT), for

1 ( F ) Change
2 ( F ) Change
3 ( F ) Change
4 ( F ) Change
5 ( F ) Change
6 ( F ) Change
7 ( F ) Change
8 ( F ) Change
9 ( F ) Change
10 ( F ) Change

35%
30%
25%
20%
15%
10%
5%
0%
10

12

14

16

18

20

22

24

26

28

30

32

34

36

Initial Delta T (F)

sensible cooling). This graph shows the

Percentage Change in Primary Air Flow when the air temperature is changed relative to the initial ΔT.
When the biggest consumer of energy in the HVAC system is the primary air fan, any reduction in flow
provides energy savings and lower operating costs. As lower primary air temperatures tend to be below
the space dew point, concerns about condensation forming must be a consideration along with the
diffusers’ ability to mix the colder air within the given throw distance in order to avoid drafts and, on VAV
systems under part load conditions, the increased potential for the colder air to dump as the air volume
decreases.
DADANCO’s INFFUSERS use entrainment to temper the primary air and increase the volume delivered
(typically 1–2 times the amount of primary & generally in the 60’s ºF in cooling and 80’s ºF in heating)
meaning that the air is delivered above the dew point, is warmer and as a result, needs less mixing in
the room to avoid drafts. Therefore, the possibility for dumping is dramatically reduced, and by correct
selection, the condensation risk is eliminated. Even with 20% less air volume, the latent cooling capacity
of the air at 50ºF (95% RH) is over 2 times that of air at 55ºF at the same RH, therefore lower primary air
temperatures offer significantly better humidity control. So INFFUSERS are ‘Green’ because they allow
you to save energy by reducing the primary air volume needed to cool the building, reducing the size of
the central air handler and ductwork, saving operation cost. Laboratory tests were conducted at varying
primary air temperatures and room humidity levels. These test results indicate that, with a room design
temperature of 75ºF, moisture did not form on the Inffuser faces using 46ºF primary air until the room’s
relative humidity reached 75%. With adequate latent cooling capacity being provided by the primary
air, this condition will not occur.
5
Induction versus Aspiration…
The induction process is significantly different to aspiration. Aspiration occurs when room air mixes
with the air being discharged from the terminal outlet, which occurs to a varying extent with all types
of diffusers.
The amount of air being induced by the
Primary Air
(Ducted)

INFFUSERS can be closely controlled
and measured by varying the number
and size of nozzles within the unit.
Induction, as opposed to aspiration, is

Secondary Air
(by Induction)

the process of mixing primary and room
air within the INFFUSER

before the

mixed (and tempered) air is discharged
into the room.
The aspiration process relies on mixing
the supply and room air within the

Aspiration

room, in essence using the room as a
mixing chamber.

High aspiration products such as swirl diffusers do not induce air from the room or ceiling return plenum
into the product’s internal mixing chamber prior to discharging into the room, so when primary air is
supplied at 48°F through one of these devices, you have to consider all the inherent issues of delivering
low temperature air significantly below the room dew point into the room.
DADANCO INFFUSERS utilize unique nozzle and fluid dynamics technology to provide very high air
entrainment ratios at low pressure drops and superior performance at low noise levels.
Due to the fact that DADANCO INFFUSERS are an induction device, airflow
measurements should not be taken with an air capture hood. The only way to
accurately measure the primary air flow into the INFFUSER is by reading the
static pressure from the commissioning sampling tube from the INFFUSER
plenum. A ‘primary air flow vs. static pressure’ chart is provided for each unit.
Do not utilize static pressure readings in the duct near the INFFUSER inlet and presume it will be the
same as that in the unit’s primary air plenum for commissioning purposes as this measurement could
be significantly different from that measured through the commissioned sampling tube.

6
Common applications…
Any air distribution system where an increase in the quantity of
supply air delivered to the room at a more temperate temperature
is of benefit such as those spaces that suffer from:
	

•	  eeding more cooling capacity delivered with existing
N
infrastructure.

	

•	 Poor or inadequate air distribution.	

	

•	 Dumping or draft issues under cooling.	

	

•	 Stratification problems under heating.

Any air distribution system being designed to save energy or striving to achieve LEED certification and,
therefore, the use of low temperature primary air (45-50ºF), in order to reduce primary airflow volume
by 20-30%, is of benefit such as in spaces where:
	

•	 There are building constraints that limit space available for the central air handling plant.

	

•	  here are building constraints that limit the space available for supply/return ductwork 
T
terminal outlets.

	

•	 The zones have low to medium sensible cooling and heating load densities.

	

•	  he zone is running at, or near to, minimum fresh air requirements and tight humidity
T
control is essential.
Type

Application

Solution

Improve the energy performance of an existing Reduce primary air temperature and airflow rate leaving
VAV or CAV system.
the cooling coil to maintain the cooling capacity required.
Replace existing diffusers with INFFUSERS to temper the air
being delivered to the conditioned space.

Existing
Building

Air distribution/movement is inadequate and Retain ductwork and replace existing diffusers with INFFUSERS
existing ductwork sizes are not large enough to increase the supply air quantity and air movement being
to permit supply air quantities to be increased. delivered to the conditioned space.
Cooling capacity is inadequate and existing
ductwork sizes are not large enough to permit
supply air quantities to be increased.

Retain ductwork and reduce the primary air temperature for
increased cooling capacity using INFFUSERS to temper the air
being delivered to the conditioned space.

Replacement of fan-powered VAV units Replace fan-powered VAV units with single duct VAV terminals,
to eliminate fan energy and VAV terminal retain ductwork, replace existing diffusers with INFFUSERS to
maintenance considerations.
temper the air being delivered to the conditioned space

New
Building

LEED design where lower temperature primary Design the system for lower primary air temperatures and
air delivers benefits in fan energy savings and air quantities using INFFUSERS to temper the air and deliver
reduced system infrastructure.
higher air circulation rates to the space.
Where internal zone loads are less than 15 Design the system with low temperature (48°F) primary air
Btu/h/sq.ft. and good air circulation and and flow rate of approximately 0.5 cfm/sq. using INFFUSERS
humidity control is required.
to temper the air and deliver higher air circulation rates to the
space.

7
Government, Institutional  Defense Buildings
Hospital  Healthcare………………
Schools  Universities……………
Commercial Offices……………
Green Renovations………
Laboratories………
Hotels……

®

260 North Elm Street
W
 estfield, MA 01085
Ph: (413) 564 – 5657
F
 ax: (413) 568 – 5384
www.dadanco.com
info@dadanco.com
www.facebook.com/dadanco
twitter.com/dadancohvac

Made in the USA

DADANCO INFFUSERS
are produced in Westfield, MA

8

More Related Content

PPTX
Ventilation rate
PPTX
Air distribution Product
PPTX
PDF
Chapter 8 duct design and sealing
PPTX
Types of air conditioning for HVAC application
PDF
Ductwork
PDF
Window Air Conditioners
PPTX
Air conditioning
Ventilation rate
Air distribution Product
Chapter 8 duct design and sealing
Types of air conditioning for HVAC application
Ductwork
Window Air Conditioners
Air conditioning

What's hot (18)

PPTX
Types of air conditioning systems
PPTX
PPTX
Bs mechanical ventilation and air conditioning presentation slides
PPTX
Architecture - Centralized Air Conditioning System
PPTX
Air Conditioning system and types
PPTX
An introduction to ventilation
PPTX
Airconditioning system (ppt)
PDF
Air Conditioning System
PPT
Methods of Auxiliary Ventilation in Underground Mine
PPTX
HEATING VENTILATION AND AIR CONDITIONING SYSTEMS
PDF
Window ac
PPTX
Basics of ventilation by jj
PPTX
PPTX
A.C. Duct
PPTX
PRESENTATION ON DUCT DESIGN
PPT
Design of air conditioning duct
PDF
Building Service Chapter 5
Types of air conditioning systems
Bs mechanical ventilation and air conditioning presentation slides
Architecture - Centralized Air Conditioning System
Air Conditioning system and types
An introduction to ventilation
Airconditioning system (ppt)
Air Conditioning System
Methods of Auxiliary Ventilation in Underground Mine
HEATING VENTILATION AND AIR CONDITIONING SYSTEMS
Window ac
Basics of ventilation by jj
A.C. Duct
PRESENTATION ON DUCT DESIGN
Design of air conditioning duct
Building Service Chapter 5
Ad

Similar to DADANCO Inffuser (20)

PPTX
Management of Poultry House Ventilation by Dr.Muhammad Ashiq Toor
DOCX
ventilation in building
PPTX
Air conditioning equipment and applications of air conditioning
PDF
DADANCO ACTIVE CHILLED BEAMS
PDF
التهوية النفقية وكيفية حساب قدرة سحب المراوح ؟؟؟
PPTX
Lecture 6 & 7 Aseptic Pharmaceutical Manufacturing.pptx
PPTX
An introduction to ventilation
PPT
LECTURE 6 ZONING IN HVAC.ppt
PDF
Low energy consumption hvac systems for green buildings using chilled beam te...
PDF
Brioler management in cold weather part1
PPTX
Air Condtioning Systems HVAC
PDF
ecbc codes for hvuc
PPTX
PPT
Greenhouse environment control system
DOCX
Building Services 1 Report
PPTX
Building Services - Efficient Energy Ventilation System
PPTX
Managing Ventilation In Modern Poultry House
PPTX
Ventilation
PDF
analysis-of-uniformity-and-energy-consumption.pdf
PDF
Overview and Maintenanaces of HVAC system
Management of Poultry House Ventilation by Dr.Muhammad Ashiq Toor
ventilation in building
Air conditioning equipment and applications of air conditioning
DADANCO ACTIVE CHILLED BEAMS
التهوية النفقية وكيفية حساب قدرة سحب المراوح ؟؟؟
Lecture 6 & 7 Aseptic Pharmaceutical Manufacturing.pptx
An introduction to ventilation
LECTURE 6 ZONING IN HVAC.ppt
Low energy consumption hvac systems for green buildings using chilled beam te...
Brioler management in cold weather part1
Air Condtioning Systems HVAC
ecbc codes for hvuc
Greenhouse environment control system
Building Services 1 Report
Building Services - Efficient Energy Ventilation System
Managing Ventilation In Modern Poultry House
Ventilation
analysis-of-uniformity-and-energy-consumption.pdf
Overview and Maintenanaces of HVAC system
Ad

Recently uploaded (20)

PPTX
Module 1 Introduction to Web Programming .pptx
PDF
SaaS reusability assessment using machine learning techniques
PPTX
GROUP4NURSINGINFORMATICSREPORT-2 PRESENTATION
PPT
Galois Field Theory of Risk: A Perspective, Protocol, and Mathematical Backgr...
PPTX
SGT Report The Beast Plan and Cyberphysical Systems of Control
PDF
NewMind AI Weekly Chronicles – August ’25 Week IV
PDF
MENA-ECEONOMIC-CONTEXT-VC MENA-ECEONOMIC
PDF
Advancing precision in air quality forecasting through machine learning integ...
PDF
Early detection and classification of bone marrow changes in lumbar vertebrae...
PPTX
agenticai-neweraofintelligence-250529192801-1b5e6870.pptx
PDF
5-Ways-AI-is-Revolutionizing-Telecom-Quality-Engineering.pdf
PPTX
MuleSoft-Compete-Deck for midddleware integrations
PDF
INTERSPEECH 2025 「Recent Advances and Future Directions in Voice Conversion」
PDF
Planning-an-Audit-A-How-To-Guide-Checklist-WP.pdf
PDF
Produktkatalog für HOBO Datenlogger, Wetterstationen, Sensoren, Software und ...
PDF
The-2025-Engineering-Revolution-AI-Quality-and-DevOps-Convergence.pdf
PDF
“A New Era of 3D Sensing: Transforming Industries and Creating Opportunities,...
PDF
Transform-Quality-Engineering-with-AI-A-60-Day-Blueprint-for-Digital-Success.pdf
DOCX
Basics of Cloud Computing - Cloud Ecosystem
PDF
CXOs-Are-you-still-doing-manual-DevOps-in-the-age-of-AI.pdf
Module 1 Introduction to Web Programming .pptx
SaaS reusability assessment using machine learning techniques
GROUP4NURSINGINFORMATICSREPORT-2 PRESENTATION
Galois Field Theory of Risk: A Perspective, Protocol, and Mathematical Backgr...
SGT Report The Beast Plan and Cyberphysical Systems of Control
NewMind AI Weekly Chronicles – August ’25 Week IV
MENA-ECEONOMIC-CONTEXT-VC MENA-ECEONOMIC
Advancing precision in air quality forecasting through machine learning integ...
Early detection and classification of bone marrow changes in lumbar vertebrae...
agenticai-neweraofintelligence-250529192801-1b5e6870.pptx
5-Ways-AI-is-Revolutionizing-Telecom-Quality-Engineering.pdf
MuleSoft-Compete-Deck for midddleware integrations
INTERSPEECH 2025 「Recent Advances and Future Directions in Voice Conversion」
Planning-an-Audit-A-How-To-Guide-Checklist-WP.pdf
Produktkatalog für HOBO Datenlogger, Wetterstationen, Sensoren, Software und ...
The-2025-Engineering-Revolution-AI-Quality-and-DevOps-Convergence.pdf
“A New Era of 3D Sensing: Transforming Industries and Creating Opportunities,...
Transform-Quality-Engineering-with-AI-A-60-Day-Blueprint-for-Digital-Success.pdf
Basics of Cloud Computing - Cloud Ecosystem
CXOs-Are-you-still-doing-manual-DevOps-in-the-age-of-AI.pdf

DADANCO Inffuser

  • 1. INFFUSER® INDUCTION DIFFUSERS …Breathing Life Into Your Building… 1 SB-INF/1.0 (09/12) DADANCO.COM ®
  • 2. Our Mission… “To be the leading specialist in energy efficient and environmentally sustainable HVAC technologies and technical expertise, with the aim of delivering the most efficient and value added solution.” Going Beyond Conventional Wisdom… In the design of a typical HVAC system many decisions are made based largely on past experience and conventional wisdom. While this often results in a satisfactory system, it may not result in an optimal “green” design. With the movement toward sustainable building designs, there is an increased emphasis on improving both the energy efficiency and comfort level of all types of HVAC systems. Variable Air Volume (VAV) systems typically provide adequate room temperature control, but there are often concerns about air movement and humidity control at part load conditions. In addition, the supply fans in an ‘all-air’ HVAC system tend to consume the most energy in a typical North American commercial building. DADANCO INFFUSERS offer an opportunity to improve both the energy efficiency and comfort level of VAV systems, as well as in other conventional HVAC systems in many market sectors including Schools and Universities, Healthcare and Hospitals, Hotels, Laboratories, Commercial offices, Government, Institutional and Defense buildings, either for New build or Green renovation. Contents… What is an INFFUSER Page 3 What is Internal or External entrainment Page 4 Why are INFFUSERS “Green” Page 5 Induction versus Aspiration Page 6 Common Applications Page 7 2
  • 3. What is an INFFUSER… DADANCO’s INFFUSERS are quite IDL20e (Linear 2–way discharge) simply an ‘induction diffuser’ that uses special nozzles located in the underside of the air plenum to mix primary air (ducted from the central air handling plant) with secondary air that is Induced from either the ceiling return air plenum (via *External entrainment) or room (via *Internal entrainment) to increase the total amount of air delivered to the space. When INFFUSERS are used in conjunction with low temperature supply air systems that operate with primary air temperatures in the range of 48°F-50°F, the correct selection based on the space design conditions will ensure that the mixed air (primary plus secondary) delivered by the INFFUSER is above the room dew point, without the need for local fans, filters, controls or power supply at the outlet. INFFUSERS have been successfully used in conjunction with primary air temperatures as low as 43°F, however such applications must be referred to DADANCO for approval. INFFUSERS are an ideal replacement outlet for conditioned spaces that suffer from poor or inadequate air movement. They are available as either a 4’ long or continuous 1 slot 1-way or 2 slot 2–way linear diffuser or as a 2’ x 2’ 4– way diffuser, all with the option of either *Internal or *External entrainment. DADANCO’s technology nozzles rapidly induce secondary air to reduce the momentum and height of the potential core zone, significantly reducing noise generation. DADANCO INFFUSERS are whisper quiet at inlet static pressures in the range of 0.1 - 0.3” w.c., and are suitable for use in any air distribution system where increased air movement and tempered primary air temperatures would be of benefit. (*see entrainment description on page 4) IDS60e (Square 4–way discharge) 3
  • 4. What is Internal or External entrainment… 1 With Internal entrainment models the conditioned primary air from the central air 2 handling plant (1) is ducted into the INFFUSER plenum (2). This air leaves the plenum through 3 a series of nozzles located in its underside into a sub divided mixing chamber behind the diffuser (3). This process induces secondary room air (4) up through the central area of the diffuser into the Inffuser mixing chamber directly from the room where it’s mixed with the primary air. This mixed (and tempered) air 5 (5) is then discharged into the room via the 5 outer areas of the diffuser. 4 Internal Entrainment 1 With External entrainment models the conditioned primary air from the central air handling plant (1) is ducted into the INFFUSER plenum (2). This air leaves the 2 plenum through a series of nozzles located in its underside. This process induces secondary air from 3 the ceiling return air plenum (3) into the discharge path from the nozzles where it mixes with the primary air. This mixed (and tempered) air (4) is then 4 discharged into the room via the diffuser. In both cases the primary air is tempered 4 External Entrainment by the induced secondary air before the combination is discharged into the room via the diffuser. 4
  • 5. Why are Inffusers “Green”… In an “all-air” system such as VAV, primary air is typically delivered to the room at 55ºF. Most designers, striving to reduce energy and save space, never consider the merits of using lower primary air temperature due to their concerns about achieving occupier comfort while delivering colder air. On a typical building (at sea level) with 50% a space design temperature of 75ºF 45% every ton of cooling needed, 553 cfm of primary air has to be conditioned and delivered by the central plant. When the temperature is lowered by 5ºF to 50ºF (25 ΔT), the air volume is reduced to 443 cfm (approximately 20% less to provide the same amount of 40% % Change in Primary Air Flow and primary air at 55ºF (20 ΔT), for 1 ( F ) Change 2 ( F ) Change 3 ( F ) Change 4 ( F ) Change 5 ( F ) Change 6 ( F ) Change 7 ( F ) Change 8 ( F ) Change 9 ( F ) Change 10 ( F ) Change 35% 30% 25% 20% 15% 10% 5% 0% 10 12 14 16 18 20 22 24 26 28 30 32 34 36 Initial Delta T (F) sensible cooling). This graph shows the Percentage Change in Primary Air Flow when the air temperature is changed relative to the initial ΔT. When the biggest consumer of energy in the HVAC system is the primary air fan, any reduction in flow provides energy savings and lower operating costs. As lower primary air temperatures tend to be below the space dew point, concerns about condensation forming must be a consideration along with the diffusers’ ability to mix the colder air within the given throw distance in order to avoid drafts and, on VAV systems under part load conditions, the increased potential for the colder air to dump as the air volume decreases. DADANCO’s INFFUSERS use entrainment to temper the primary air and increase the volume delivered (typically 1–2 times the amount of primary & generally in the 60’s ºF in cooling and 80’s ºF in heating) meaning that the air is delivered above the dew point, is warmer and as a result, needs less mixing in the room to avoid drafts. Therefore, the possibility for dumping is dramatically reduced, and by correct selection, the condensation risk is eliminated. Even with 20% less air volume, the latent cooling capacity of the air at 50ºF (95% RH) is over 2 times that of air at 55ºF at the same RH, therefore lower primary air temperatures offer significantly better humidity control. So INFFUSERS are ‘Green’ because they allow you to save energy by reducing the primary air volume needed to cool the building, reducing the size of the central air handler and ductwork, saving operation cost. Laboratory tests were conducted at varying primary air temperatures and room humidity levels. These test results indicate that, with a room design temperature of 75ºF, moisture did not form on the Inffuser faces using 46ºF primary air until the room’s relative humidity reached 75%. With adequate latent cooling capacity being provided by the primary air, this condition will not occur. 5
  • 6. Induction versus Aspiration… The induction process is significantly different to aspiration. Aspiration occurs when room air mixes with the air being discharged from the terminal outlet, which occurs to a varying extent with all types of diffusers. The amount of air being induced by the Primary Air (Ducted) INFFUSERS can be closely controlled and measured by varying the number and size of nozzles within the unit. Induction, as opposed to aspiration, is Secondary Air (by Induction) the process of mixing primary and room air within the INFFUSER before the mixed (and tempered) air is discharged into the room. The aspiration process relies on mixing the supply and room air within the Aspiration room, in essence using the room as a mixing chamber. High aspiration products such as swirl diffusers do not induce air from the room or ceiling return plenum into the product’s internal mixing chamber prior to discharging into the room, so when primary air is supplied at 48°F through one of these devices, you have to consider all the inherent issues of delivering low temperature air significantly below the room dew point into the room. DADANCO INFFUSERS utilize unique nozzle and fluid dynamics technology to provide very high air entrainment ratios at low pressure drops and superior performance at low noise levels. Due to the fact that DADANCO INFFUSERS are an induction device, airflow measurements should not be taken with an air capture hood. The only way to accurately measure the primary air flow into the INFFUSER is by reading the static pressure from the commissioning sampling tube from the INFFUSER plenum. A ‘primary air flow vs. static pressure’ chart is provided for each unit. Do not utilize static pressure readings in the duct near the INFFUSER inlet and presume it will be the same as that in the unit’s primary air plenum for commissioning purposes as this measurement could be significantly different from that measured through the commissioned sampling tube. 6
  • 7. Common applications… Any air distribution system where an increase in the quantity of supply air delivered to the room at a more temperate temperature is of benefit such as those spaces that suffer from: • eeding more cooling capacity delivered with existing N infrastructure. • Poor or inadequate air distribution. • Dumping or draft issues under cooling. • Stratification problems under heating. Any air distribution system being designed to save energy or striving to achieve LEED certification and, therefore, the use of low temperature primary air (45-50ºF), in order to reduce primary airflow volume by 20-30%, is of benefit such as in spaces where: • There are building constraints that limit space available for the central air handling plant. • here are building constraints that limit the space available for supply/return ductwork T terminal outlets. • The zones have low to medium sensible cooling and heating load densities. • he zone is running at, or near to, minimum fresh air requirements and tight humidity T control is essential. Type Application Solution Improve the energy performance of an existing Reduce primary air temperature and airflow rate leaving VAV or CAV system. the cooling coil to maintain the cooling capacity required. Replace existing diffusers with INFFUSERS to temper the air being delivered to the conditioned space. Existing Building Air distribution/movement is inadequate and Retain ductwork and replace existing diffusers with INFFUSERS existing ductwork sizes are not large enough to increase the supply air quantity and air movement being to permit supply air quantities to be increased. delivered to the conditioned space. Cooling capacity is inadequate and existing ductwork sizes are not large enough to permit supply air quantities to be increased. Retain ductwork and reduce the primary air temperature for increased cooling capacity using INFFUSERS to temper the air being delivered to the conditioned space. Replacement of fan-powered VAV units Replace fan-powered VAV units with single duct VAV terminals, to eliminate fan energy and VAV terminal retain ductwork, replace existing diffusers with INFFUSERS to maintenance considerations. temper the air being delivered to the conditioned space New Building LEED design where lower temperature primary Design the system for lower primary air temperatures and air delivers benefits in fan energy savings and air quantities using INFFUSERS to temper the air and deliver reduced system infrastructure. higher air circulation rates to the space. Where internal zone loads are less than 15 Design the system with low temperature (48°F) primary air Btu/h/sq.ft. and good air circulation and and flow rate of approximately 0.5 cfm/sq. using INFFUSERS humidity control is required. to temper the air and deliver higher air circulation rates to the space. 7
  • 8. Government, Institutional Defense Buildings Hospital Healthcare……………… Schools Universities…………… Commercial Offices…………… Green Renovations……… Laboratories……… Hotels…… ® 260 North Elm Street W estfield, MA 01085 Ph: (413) 564 – 5657 F ax: (413) 568 – 5384 www.dadanco.com [email protected] www.facebook.com/dadanco twitter.com/dadancohvac Made in the USA DADANCO INFFUSERS are produced in Westfield, MA 8