DINESH SHARMA
B.TECH.(EEE)
SHARDA UNIVERSITY
 Need for protection
 Nature and causes of faults
 Types of faults
 Fault current calculation using symmetrical
components
 Power system earthing
 Zones of protection
 Primary and back up protection
 Essential qualities of protection
 Typical protection schemes.
 What is the power system ?
 Heavy currents associated with short circuits is to
cause for damage
 If short circuit presents on a system for longer
time , it cause to damage the some of sections in
system
Fire exists
System voltage reduces to low level and generators in
power station may lose synchronism
By un cleared fault to cause for failure of the system
 To protect the system from faults need to use
automatic protective devices like
Circuit breakers
Protection relays ,isolate the faulty element
 C.B can disconnect the faulty element of the system
 Protective relay is to detect and locate a fault and
trip C.B
 Protective relay senses abnormal conditions in
system and gives alarm signal
 Those abnormal conditions are
 short circuits
 Over speed of generators & motors
 Over voltage
 Under frequency
 Loss of excitation
 Over heating of stator& rotor of an alternator
 Causes of fault on over head lines
 Birds bodies touch the phases
 Direct lighting strokes
 Snakes
 Ice
 Snow loading
 Earth quakes
 Causes of faults in case of cables,
transformers, generators
 Failure of solid insulation
 Flash over due to over voltages
AVERAGE 400 KV LINE FAULT FREQUENCY STATISTICS BY
FAULT CAUSE PER 100 KM PERYEAR
 Unsymmetrical faults
 Single phase to ground fault(L-G)
 Line to line fault(L-L)
 Double line to ground fault(L-L-G)
 Open circuited phases fault
 Winding faults
 Symmetrical faults
 3phases to ground fault(LLLG)
 3phase fault
 All 3 phases are short circuited
 In case of symmetrical fault current is equally
shared by the 3phases
 In symmetrical to analysis fault by one phase
only
 Only +Ve sequence component exist in
symmetrical
 Remaining two components always zero.
 Caused by a break in the conducting path
 Occurs when
 one or more phase conductors break
 cable joint or a joint on the over head lines fails
 Fault rises when C.Bs or isolators open but fail
to close one or more phases
 Occurs on the alternator, motor &
transformer windings
 L-G 70-80%
 L-L 17-10%
 LL-G 10-8%
 3 PHASE 3-2%
 Heavy short circuit current cause to damage to
equipment
 Arcs associated with short circuits may cause
fire
 Reduction in the supply voltage of the healthy
feeders
 Loss of industrial loads
 Heating rotating machines due to reduction in
the supplyV&I
 Loss of stability
 Separate protective schemes for each piece of
equipment or element of the power system.
 dependence on the equipment divided in to a
number of the zones
 Each zone covers one or a the most two elements
of the power systems
 The protective zone plan to cover the entire power
system.
 Adjacent protective zones must over lap each
other
 A relatively low extent of over lap reduces the
probability of faults in that region.
 Tripping of too many breakers does not occurs
frequently.
 Every zone have a suitable protection scheme
 If fault occurs in a particular zone, it is duty of
primary relays of the zone to isolate the
faulty element.
 If its fails, back up protection scheme is to
clear the fault.
 The protection schemes improves the
system performance
 It operates after a time delay to give the
primary relay sufficient time to operate.
 When a back up relay operates a larger time
of the power system is disconnected from the
power sources.
 Types of back up relays are
 Remote back up
 Relay back up
 Breaker back up
 It is cheapest and simplest
 It is widely used for back up protection of
transmission lines
 Most desirable
 It will not fail due to the factors causing the
failure of the primary protection
 Additional relay is provided for protection.
 It trips the same CB if the primary relay fails
and this operation takes place with out delay.
 Costly
 Used where back up is not possible.
 Bus bar fault :
When protective relay operates in
response to a fault but the C.B fails to trip,
the fault is treated as a bus bar fault.
 used for bus bar system , where a number of
C.B’S are connected to it.
 At time of bus bar fault , necessary that all
other C.Bs on the bus bar should trip.
A
C D
E
Breaker 5
Fails
1 2 5 6 11 12
T
3 4 7 8 9 10
B F
 The basic requirements of a protective
system are
 Selectivity or discrimination
 Reliability
 Sensitivity
 Stability
 Fast operation
The selectivity of protective system dependence
on
 quality of a protective relay
▪ It is able to discriminate between in the protected section &
normal section.
▪ It should be able to distinguish whether a fault lies with in its
zones of protection or outside the zone.
 The relay able to discriminate between a fault
& transient conditions
 power surges
 inrush of a transformer’s magnetizing current.
 When a transformer is first energized, a
transient current up to 10 to 50 times larger than
the rated transformer current can flow for
several cycles
 inrush happens when the primary winding is
connected at an instant around the zero-crossing
of the primary voltage (which for a pure
inductance would be the current maximum in the
AC cycle).
 In the absence of any magnetic remanance from
a preceding half cycle, the effective magnetizing
force is doubled compared to the steady state
condition
 The typical value of reliability of protective system is
95%
 reliability dependence on
 Robustness
 Simplicity
 In case of relay
▪ Contact pressure
▪ Contact material of relay
 To achieve a high degree of reliability
 Design
 Installation
 Maintenance
 Testing of the various element of the protective system.
 It dependences on pick up current value
 Pick –up current:-
a protective relay should
operate when the magnitude of the
current exceeds the present value.
 A relay should be sensitive to operate
when the operating current just exceeds
its pick up value.
 Protective system should stable for
 Large current due to fault
 Internal fault
 External fault
It means
 Isolate the faulty element quickly.
 To minimize damage to the equipment .
 To maintain system stability
 To avoid the loss of synchronism
 The operating time of the protective system should
not exceed the critical clearing time.
Critical clearing time:- the minimum time taken by
protective relay to clear the fault.
 By fast operation of protection system to avoid
 Burning due to heavy fault current
 Interruption of supply to consumers
 Fall in system voltage it results Loss of industrial loads
 Operating time is usually in one cycle or half
cycle.
 A protective scheme is used to protect an
equipment or a section of the line
 The protective schemes are
 Over current protection
 Distance protection
 Carrier current protection
 Differential protection
 This protection includes one or more over
current relays.
 over current relay operates when the current
exceeds its pick up value.
 It is used for the protection of
 Distribution lines
 Large motors
 It includes number of distance relays of
same or different.
 Distance relay measures the distance
between the relay location and the point of
fault in terms of impedance, reactance
 RelayType Measurement
1. Impedance relay impedance
2. Reactance relay reactance
3. Mho relay admittance
 This protection scheme is used for the
protection of
 transmission lines
 Sub- transmission lines
 In this used relays are distance type.
 Their tripping operation is controlled by the
carrier signal.
 A transmitter and receiver are installed at each
end of transmission line to be protected.
 Information of direction of fault current is
transmitted from one end of the line section to
the other by carrier signal.
 Relays placed at end
 It trips if the fault lies with in their protected
section.
 Do not trip for external fault.
 It is used for the protection of EHV &UHV line
(132kv above)
 C.T’S are placed on both side of each windings of a machine.
 The outputs of their secondaries are applied to the relay
coils.
 The relay compare the current entering & leaving of a
machine winding
 This difference in the current actuates the relay.
 In case of internal fault , the current values are not equal.
 The relay inoperative under normal condition and external
fault.
 It is used for the protection of
 Generators
 Transformers
 Motors of various size
 Bus zones
 In bus zone protection, C.T’S are placed on the both sides of
the bus bar.
 Relations of voltage components in matrix
form
 Relations of current components in matrix
form
 No grounding
 Solid grounding
 Neutral impedance grounding
 delta
 The performance of the system in terms of the
short circuits, protection etc. is greatly affected
by the state of the neutral.
 There are various method of grounding the
neutral of the system.
 Solid grounding
 Resistance grounding
 Reactance grounding
 Voltage transformer grounding
 Zig-zag transformer grounding
 In case of L-G fault at phase C
 charging current = 3*(per phase charging current)
 The voltages of the healthy phases rises to
0.866Vph
 These voltages can be eliminated by connecting
an inductance of suitable value between the
neutral and the ground or Arcing ground.
 The value of the inductive reactance is such
that the fault current balances exactly the
charging current .
 Resonant grounding is also called ground
fault neutralizer or Peterson coil.
 The resonant grounding will reduce the line
interruption due to transient line to ground
fault.
 The neutral is connected directly to the
ground with out any intentional impendence
between neutral and the ground.
 For low voltages up to 600volts and above 33
kV.
 The value of the resistance commonly used is quite
high (in order to limit power loss in resistor during
LG-fault) as compared with the system reactance.
 It is normally used where the charging current is
small i.e., for low voltage short length over head
lines.
 It reduces the ground hazards.
 It has helped in improving the stability of the
system during ground fault by replacing the power
dropped as a result of low voltage, with an
approximating equal power loss in the resistor.
 To limit the stator short current .
 Generators are normally provide with resistance
grounding.
 Reactance grounding system (Xo/X1) >3
 Solid grounding system (Xo/X1) < 3
 Reactance grounding may be used for grounding
the neutral of synchronous motors &
synchronous capacitors and also for circuits
having large charging current
 For medium voltages 3.3kV & 33KV resistance or
reactance grounding is used.
 It is used , if neutral point is requied which
other wise is not available (eg. Delta
connection, bus bar points)
 Voltages of the phases are limited to phase to
ground voltages
 The high voltages due to arcing grounding or
transient line to ground faults are eliminated
 The over voltages due to lighting are
discharged to ground
 It is possible o maintain the supply with a
fault on one line
 Interference with communication lines is
reduced because of the absence of Zero
sequence currents.

Switch gear and protection

  • 1.
  • 2.
     Need forprotection  Nature and causes of faults  Types of faults  Fault current calculation using symmetrical components  Power system earthing  Zones of protection  Primary and back up protection  Essential qualities of protection  Typical protection schemes.
  • 3.
     What isthe power system ?
  • 6.
     Heavy currentsassociated with short circuits is to cause for damage  If short circuit presents on a system for longer time , it cause to damage the some of sections in system Fire exists System voltage reduces to low level and generators in power station may lose synchronism By un cleared fault to cause for failure of the system  To protect the system from faults need to use automatic protective devices like Circuit breakers Protection relays ,isolate the faulty element
  • 7.
     C.B candisconnect the faulty element of the system  Protective relay is to detect and locate a fault and trip C.B  Protective relay senses abnormal conditions in system and gives alarm signal  Those abnormal conditions are  short circuits  Over speed of generators & motors  Over voltage  Under frequency  Loss of excitation  Over heating of stator& rotor of an alternator
  • 9.
     Causes offault on over head lines  Birds bodies touch the phases  Direct lighting strokes  Snakes  Ice  Snow loading  Earth quakes  Causes of faults in case of cables, transformers, generators  Failure of solid insulation  Flash over due to over voltages
  • 12.
    AVERAGE 400 KVLINE FAULT FREQUENCY STATISTICS BY FAULT CAUSE PER 100 KM PERYEAR
  • 14.
     Unsymmetrical faults Single phase to ground fault(L-G)  Line to line fault(L-L)  Double line to ground fault(L-L-G)  Open circuited phases fault  Winding faults  Symmetrical faults  3phases to ground fault(LLLG)  3phase fault
  • 15.
     All 3phases are short circuited  In case of symmetrical fault current is equally shared by the 3phases  In symmetrical to analysis fault by one phase only  Only +Ve sequence component exist in symmetrical  Remaining two components always zero.
  • 16.
     Caused bya break in the conducting path  Occurs when  one or more phase conductors break  cable joint or a joint on the over head lines fails  Fault rises when C.Bs or isolators open but fail to close one or more phases
  • 17.
     Occurs onthe alternator, motor & transformer windings
  • 19.
     L-G 70-80% L-L 17-10%  LL-G 10-8%  3 PHASE 3-2%
  • 20.
     Heavy shortcircuit current cause to damage to equipment  Arcs associated with short circuits may cause fire  Reduction in the supply voltage of the healthy feeders  Loss of industrial loads  Heating rotating machines due to reduction in the supplyV&I  Loss of stability
  • 21.
     Separate protectiveschemes for each piece of equipment or element of the power system.  dependence on the equipment divided in to a number of the zones  Each zone covers one or a the most two elements of the power systems  The protective zone plan to cover the entire power system.  Adjacent protective zones must over lap each other  A relatively low extent of over lap reduces the probability of faults in that region.  Tripping of too many breakers does not occurs frequently.
  • 26.
     Every zonehave a suitable protection scheme  If fault occurs in a particular zone, it is duty of primary relays of the zone to isolate the faulty element.  If its fails, back up protection scheme is to clear the fault.  The protection schemes improves the system performance
  • 27.
     It operatesafter a time delay to give the primary relay sufficient time to operate.  When a back up relay operates a larger time of the power system is disconnected from the power sources.  Types of back up relays are  Remote back up  Relay back up  Breaker back up
  • 28.
     It ischeapest and simplest  It is widely used for back up protection of transmission lines  Most desirable  It will not fail due to the factors causing the failure of the primary protection
  • 29.
     Additional relayis provided for protection.  It trips the same CB if the primary relay fails and this operation takes place with out delay.  Costly  Used where back up is not possible.
  • 30.
     Bus barfault : When protective relay operates in response to a fault but the C.B fails to trip, the fault is treated as a bus bar fault.  used for bus bar system , where a number of C.B’S are connected to it.  At time of bus bar fault , necessary that all other C.Bs on the bus bar should trip.
  • 31.
    A C D E Breaker 5 Fails 12 5 6 11 12 T 3 4 7 8 9 10 B F
  • 32.
     The basicrequirements of a protective system are  Selectivity or discrimination  Reliability  Sensitivity  Stability  Fast operation
  • 33.
    The selectivity ofprotective system dependence on  quality of a protective relay ▪ It is able to discriminate between in the protected section & normal section. ▪ It should be able to distinguish whether a fault lies with in its zones of protection or outside the zone.  The relay able to discriminate between a fault & transient conditions  power surges  inrush of a transformer’s magnetizing current.
  • 34.
     When atransformer is first energized, a transient current up to 10 to 50 times larger than the rated transformer current can flow for several cycles  inrush happens when the primary winding is connected at an instant around the zero-crossing of the primary voltage (which for a pure inductance would be the current maximum in the AC cycle).  In the absence of any magnetic remanance from a preceding half cycle, the effective magnetizing force is doubled compared to the steady state condition
  • 35.
     The typicalvalue of reliability of protective system is 95%  reliability dependence on  Robustness  Simplicity  In case of relay ▪ Contact pressure ▪ Contact material of relay  To achieve a high degree of reliability  Design  Installation  Maintenance  Testing of the various element of the protective system.
  • 36.
     It dependenceson pick up current value  Pick –up current:- a protective relay should operate when the magnitude of the current exceeds the present value.  A relay should be sensitive to operate when the operating current just exceeds its pick up value.
  • 37.
     Protective systemshould stable for  Large current due to fault  Internal fault  External fault
  • 38.
    It means  Isolatethe faulty element quickly.  To minimize damage to the equipment .  To maintain system stability  To avoid the loss of synchronism  The operating time of the protective system should not exceed the critical clearing time. Critical clearing time:- the minimum time taken by protective relay to clear the fault.  By fast operation of protection system to avoid  Burning due to heavy fault current  Interruption of supply to consumers  Fall in system voltage it results Loss of industrial loads  Operating time is usually in one cycle or half cycle.
  • 39.
     A protectivescheme is used to protect an equipment or a section of the line  The protective schemes are  Over current protection  Distance protection  Carrier current protection  Differential protection
  • 40.
     This protectionincludes one or more over current relays.  over current relay operates when the current exceeds its pick up value.  It is used for the protection of  Distribution lines  Large motors
  • 41.
     It includesnumber of distance relays of same or different.  Distance relay measures the distance between the relay location and the point of fault in terms of impedance, reactance  RelayType Measurement 1. Impedance relay impedance 2. Reactance relay reactance 3. Mho relay admittance  This protection scheme is used for the protection of  transmission lines  Sub- transmission lines
  • 42.
     In thisused relays are distance type.  Their tripping operation is controlled by the carrier signal.  A transmitter and receiver are installed at each end of transmission line to be protected.  Information of direction of fault current is transmitted from one end of the line section to the other by carrier signal.  Relays placed at end  It trips if the fault lies with in their protected section.  Do not trip for external fault.  It is used for the protection of EHV &UHV line (132kv above)
  • 43.
     C.T’S areplaced on both side of each windings of a machine.  The outputs of their secondaries are applied to the relay coils.  The relay compare the current entering & leaving of a machine winding  This difference in the current actuates the relay.  In case of internal fault , the current values are not equal.  The relay inoperative under normal condition and external fault.  It is used for the protection of  Generators  Transformers  Motors of various size  Bus zones  In bus zone protection, C.T’S are placed on the both sides of the bus bar.
  • 46.
     Relations ofvoltage components in matrix form  Relations of current components in matrix form
  • 59.
     No grounding Solid grounding  Neutral impedance grounding  delta
  • 64.
     The performanceof the system in terms of the short circuits, protection etc. is greatly affected by the state of the neutral.  There are various method of grounding the neutral of the system.  Solid grounding  Resistance grounding  Reactance grounding  Voltage transformer grounding  Zig-zag transformer grounding
  • 65.
     In caseof L-G fault at phase C  charging current = 3*(per phase charging current)  The voltages of the healthy phases rises to 0.866Vph  These voltages can be eliminated by connecting an inductance of suitable value between the neutral and the ground or Arcing ground.
  • 66.
     The valueof the inductive reactance is such that the fault current balances exactly the charging current .  Resonant grounding is also called ground fault neutralizer or Peterson coil.  The resonant grounding will reduce the line interruption due to transient line to ground fault.
  • 67.
     The neutralis connected directly to the ground with out any intentional impendence between neutral and the ground.  For low voltages up to 600volts and above 33 kV.
  • 68.
     The valueof the resistance commonly used is quite high (in order to limit power loss in resistor during LG-fault) as compared with the system reactance.  It is normally used where the charging current is small i.e., for low voltage short length over head lines.  It reduces the ground hazards.  It has helped in improving the stability of the system during ground fault by replacing the power dropped as a result of low voltage, with an approximating equal power loss in the resistor.  To limit the stator short current .  Generators are normally provide with resistance grounding.
  • 69.
     Reactance groundingsystem (Xo/X1) >3  Solid grounding system (Xo/X1) < 3  Reactance grounding may be used for grounding the neutral of synchronous motors & synchronous capacitors and also for circuits having large charging current  For medium voltages 3.3kV & 33KV resistance or reactance grounding is used.
  • 70.
     It isused , if neutral point is requied which other wise is not available (eg. Delta connection, bus bar points)
  • 71.
     Voltages ofthe phases are limited to phase to ground voltages  The high voltages due to arcing grounding or transient line to ground faults are eliminated  The over voltages due to lighting are discharged to ground
  • 72.
     It ispossible o maintain the supply with a fault on one line  Interference with communication lines is reduced because of the absence of Zero sequence currents.