Pyro Asia Protection Philippines Inc.
FM-200 Hydraulic Flow Calculation Program Results
CHEM-200 Flow Calculation Program Version 10.4.0.0
Agency Listing: UL(ULI) Ex4655, ULC CEx1200, Factory Mutual 3011911
Project Name: Knowles Electronics Project Location: Cebu City Hazard Name: 2nd Floor Room System Information Storage Pressure (bar): Ave Initial Pipe Temp (C): Percent of Agent in Pipe: Quantity of Cylinders: Amount per Cylinder (kg): Altitude Relative to Sea (m): 25.80 21.1 8.7 1 29.9 0
Date: 12/31/2012 3:24:44 PM Project Number: 003 Revision:
Average Cyl Pressure (BAR): Fill Density (kg/cu.m.): Average Discharge Time (sec): Type of Cylinder: Total Amount of Agent (kg):
17.5 769.95 9.8 Beta 95 29.9
Hazard Information Hazard: 2nd Floor Room Concentration Required: 7.00 Nozzle(s): 301 360 Radial Nozzle Hazard Type: Class C Fire Hazard Temp. (C): 21.1 Dimensions (m): 20.0 X 1.0 X 2.7 0.0 X 1.0 X 1.0 Total Agent Required: 29.57 kgs Length (m) 0.0 1.7 2.2 2.2 0.1 Elev (m) 1.0 1.7 0.0 0.0 -0.1 EQL (m) 18.3 1.7 2.9 2.9 0.7 Start Tee MFLD Term (BAR) 17.50 16.60 16.60 14.88 14.88 12.95 12.95 10.75 10.75 10.13 Flow (kgs/sec) 3.98 3.98 3.98 3.98 3.98
Piping Model Results Section Start End 1 2 2 3 3 4 4 5 5 301 Pipe Size (mm) 32 - SCH 40 20 - SCH 40 20 - SCH 40 20 - SCH 40 20 - SCH 40
Concentration Results Enclosure Volume (cu.m) 54.0 Agent Required (kg) 29.57 Agent Discharged (kg) 29.90 Concentration Requested / Achieved 7.00 7.07
Enclosure Name 2nd Floor Room
1 (Continued)
Pyro Asia Protection Philippines Inc.
FM-200 Hydraulic Flow Calculation Program Results
CHEM-200 Flow Calculation Program Version 10.4.0.0
Agency Listing: UL(ULI) Ex4655, ULC CEx1200, Factory Mutual 3011911
Project Name: Knowles Electronics Project Location: Cebu City Hazard Name: 2nd Floor Room
Date: 12/31/2012 3:24:45 PM Project Number: 003 Revision:
Nozzle Information Nozzle ID 301 Size mm (in) 20 mm ( 3/4 ) Stock Number 10371417 Drill (inches) 0.2610 Drill Size G Total Orifice Discharged Area (sq.cm.) (kg) 2.761 29.90
Style F
Error Messages FM200FLC V4.1 10/25/2005 Orifice diameters and pipe sizes are fixed in input data. No Errors Time and date of calculation 15:24:01 12-31-2012 PIPING NOTICE: This flow calculation is only listed and approved for Schedule 40 and Schedule 80 pipe meeting the specifications of American National Standards Institute (ANSI) B36.10 for steel pipe. Millimeter pipe diameter equivalents are given for reference only. Calculation performed with Version 10.4.0.0
Calculation by: KIDDE ASIA PTE LTD NEAL T. VALERIO 70 BENDEMEER ROAD, #02-02 LUZERNE BLDG., SINGAPORE SINGAPORE 339940 SINGAPORE Telephone: 6564247944 Fax: 6564247978
2 (End of Calculation)