Evaluation of Combustible Dust Hazards
during a Process Hazards Analysis (PHA)
Mayur Patel
DuPont Engineering, India
&
S. Dharmavaram
DuPont Engineering Research & Technology, USA
8th Global Congress on Process Safety
Houston, Texas, April 1-4, 2012
Topics
Basic Concepts: Combustible Dust Hazards
Planning and preparing to conduct a PHA
Team selection and training
Review of process safety information
Hazards Identification
Hazards identification techniques
Field tour
Hazard, Hazardous events and major lines of defense
Consequence Analysis
Hazards Evaluation
Methodology selection
Application
3/13/2012
Basic Concepts
Dust Fire and Explosion Hazard
3/13/2012
What Materials Can Form Combustible Dust Clouds?
Fine solids consisting of materials that
are not stable oxides:
Most natural and synthetic materials (e.g.,
food grains, sugar, flour, many plastics and
chemicals)
Some metals (e.g., aluminum, magnesium)
Stable oxides (TiO2, SiO2, CaCO3) do not
pose a dust explosion hazard
Screening tests can be conducted in
various test equipment to determine
whether a material should be classified
as a combustible dust
3/13/2012
Explosible Dust Concentration
MEC is orders of
magnitude above dust-inair concentrations that
are of concern from a
hygiene point of view
Typical MEC
~10-100 g/m3
Mass of Powder/Dust per unit Volume [g/m3]
(Ref: Dust Explosions in the Process Industries, R.K. Echhoff)
3/13/2012
Particle Size Distribution
Log: Difficult
To Light, Burns Slowly
Kindling: Easier to
Light, Burns Quickly
Dust: Lights Easily,
Burns VERY Fast
(Ref: Dust Explosions in the Process Industries, R.K. Echhoff)
3/13/2012
Potential Sources of Ignition
We must consider all possible ignition sources, including:
Hot surfaces
Open flames
Mechanical sparks
Electrical arcs
Self-Heating of material
Chemical reactions
Electrostatic discharges
3/13/2012
Key Challenges:
Evaluation of Dust Fire and Explosion Hazards
during a PHA
3/13/2012
Scope of the PHA study
Look beyond process equipment
Include building and facility in which
the process equipment is located
Common facilities such as central
dust extraction and collection systems
should be evaluated
Concerns of fugitive dust emissions
and dust layer hazards must be
addressed
An example on the important this is:
West Pharmaceuticals Secondary
dust explosions and fires
3/13/2012
10
Team Selection and Training
Individuals with appropriate skills,
knowledge and experience on
combustible dust hazards and
prevention & mitigation systems
Full-time or ad-hoc team members
PHA Resource or Process Technology
person (if trained)
Provide training on Overview of
Combustible Dust Hazards to the PHA
team
3/13/2012
11
Review of Process Safety Information
Flammability or explosion
characteristics of combustible solid
materials
Minimum Explosible Concentration
(MEC)
Auto Ignition Temperature Dust
Layer (AIT-Layer)
Auto Ignition Temperature Dust
Cloud (AIT-Cloud)
Minimum Ignition Energy (MIE)
Dust Deflagration Index (Kst value)
Limiting Oxygen Concentration (LOC)
3/13/2012
Remember Size Matters!!!
Finer Particles => Lower MEC,
Lower MIE, Higher Kst
Do Not Miss to Review
Effects of Product Moisture
Environmental Effects
Review compliance with
RAGAGEPs, like NFPA-654 , NFPA68, NFPA-69, etc.
Consult a subject matter expert
if in doubt
12
Review of Process Safety Information
Specific Powder Testing
Prior Test Results
Manufacturer Specific Test
Data/Information
Published Literature
3/13/2012
Increasing Confidence
Assessing Dust Flammability Properties
13
Review of Process Safety Information
Ask if PHA team has knowledge and
experience required for interpretation of
data for the process under review
Ask about all the dust flammability or
explosion data that may be required
Ask if data available represents the finest
material within the process under review
Ask if there is a potential for mixture with
other solid materials
Ask if there is a potential for a hybrid
mixture
Ask if additional electrostatic charging or
thermal stability information is required
3/13/2012
Ref: Investigation report, Combustible dust hazard study, CSB-USA
14
Review of Process Safety Information
Obtain and review design, installation, inspection
and maintenance related information for existing
explosion prevention and protection systems
Explosion Prevention
Nitrogen Gas Inerting
Local Exhaust Ventilation and Collection system
Elimination of all sources of ignition
Explosion Protection
Explosion Relief Venting
Explosion Suppression
Explosion Containment
Explosion Isolation
(Ref: Dust Explosions in the Process Industries, R.K. Eckhoff)
3/13/2012
15
Hazard Identification Techniques
Review process safety information
Review of combustible dust incidents
Review Management of Change (MOC) documents
Review previous PHAs or PHAs involving similar equipment or
facilities
PHA team experience
3/13/2012
16
Field Tour
Some common field tour items:
Location of the explosion vent
panel(s) and exclusion zone
Location of sources of dust
releases
Accumulation of combustible
solid materials Look at
horizontal surfaces which may
not be easily accessible
Electrical apparatus in an
electrically classified area
3/13/2012
17
Hazardous Events and Consequence Analysis
Common dust fire and explosion
events:
Flash-fires
Primary dust explosions
Explosion propagation (in
conjunction with primary dust
explosion)
Secondary dust explosions
Important to pay attention to
thermal decomposition or
degradation of solid materials
3/13/2012
18
Consequences of Venting
Consider secondary effects:
Vented pressure waves
Vented fireball
Vented unburned dusts and
combustion gases
Effects of reaction forces
Estimation of the dimension of the
fire-ball and the maximum external
pressure should be performed and
documented in a PHA to ensure that
explosions are vented to a safe
location.
3/13/2012
19
Hazard Evaluation
Commonly used Hazard Evaluation methods:
What-If Analysis
Checklist Analysis
What-If/Checklist Analysis
Hazard & Operability (HAZOP)
Failure Mode & Effect Analysis (FMEA)
Fault Tree Analysis (FTA)
Event Tree Analysis (ETA)
Cause-Consequence Analysis
3/13/2012
20
Hazard Evaluation: What-if/Checklist Method
What-if/Checklist is a logical choice for
combustible dust handling operations and facilities
Greater emphasis on the use of checklist analysis to
uncover all combustible dust concerns
Checklist:
stimulates additional What-if questions
helps ensure that the design, installation and
maintenance is in accordance with RAGAGEPs
helps identify paths to combustible dust fire and
explosion events
helps identify gaps in safeguards that may be
missed by utilizing other methodologies
3/13/2012
21
Hazard Evaluation: What-if/Checklist Method
Develop a purpose-built checklist for the
operations, equipment and installations that
handle combustible solid materials
Involve individuals having appropriate
knowledge and expertise to develop
purpose-built checklist(s)
Checklist well-suited for the PHA team with
limited knowledge and experience of
combustible dust hazards and prevention/
mitigation systems
Use purpose-built checklists as dynamic
documents that are updated periodically, for
example after incident investigations and
when RAGAGEPs change
3/13/2012
22
Hazard Evaluation: What-if/Checklist Method
Example of a
purpose-built
checklist
Checklist - Dust Collector
1 Is dust collector located indoor or outdoor?
Is dust collector protected with appropriate explosion protection
2 systems in accordance with NFPA standards? Is design basis of the
explosion protection systems well documented?
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
3/13/2012
19
Is appropriate risk analysis performed and documented where explosion
protecion is not used in accordance with NFPA standards?
Is explosion isolation provided to prevent propagation of an explosion to
the connected euipment or to the operating areas?
Is the exhaust fan associated with the unit located on the clean air side
of the collector? Consult expert if this is not the case.
Is dust collector constructed from non-combustible material (except for
filter media)?
Is dust collector constructed to minimize internal ledges or other points
of dust accumulation?
Is access doors or openings provided to permit inspection, cleaning and
maintenance? Are they leak tight?
Are all conductive (and metal) components (including access doors, filter
support cages) adequately grounded? Is bonding and gounding checked
periodically?
Is explosion relief panel(s) (if used) vent to a safe location?
What if there is an ignition occurs in the dust collector?
What if the 'filter support cage' (if used) is not grounded?
What if an ember enters the bags?
What if the filter bag leaks through?
What if the air pulsation stops working?
What if the filter bags plugs to cause higher pressure differential across
the bags?
What if there is too high level of powder in the bottom hopper of the
dust collector?
What if the powder is left in the bottom hopper of the dust collector for
a longer period of time?
What if the explosion relief panel(s) leaks through?
23
Hazard Evaluation: What-if/Checklist Method
Do not use
checklist to
simply provide
Yes/No/Not
Applicable
answers but use
it to identify
potential
concerns of dust
fire/explosion
within the
process being
studied.
3/13/2012
Read item from checklist
Does it apply to the equipment
or operation being reviewed?
No
Does it generate a new question?
No
Document question and go on to
next item
Go to next item
Go to next item
24
Hazard Evaluation: Other Methods
Application could easily become cumbersome
for dust handling operations
Could confuse the PHA team
Not effective in ensuring that a process is
designed in accordance with codes and
standards
Not effective in identifying all gaps in
safeguards
Well-defined structure can give a false sense
of security but can we include all the
important deviations or failure modes to
uncover all combustible dust concerns?
3/13/2012
25
Hazard Evaluation: Other Methods
Consider:
How can we uncover potential for a
secondary dust explosion by application
of HAZOP or FMEA structure?
How can we uncover concerns of dust
flash-fires while charging combustible
powder to vessel by application of
HAZOP or FMEA structure?
How can we uncover risk of static
caused ignition due to any hidden
ungrounded conductive item by
application of HAZOP or FMEA
structure?
3/13/2012
26
Hazard Evaluation Other Methods
Lack of good initiating event frequency data for dust
explosion and fire events
Limits the effectiveness of semi-quantitative risk analysis
(for example ETA or LOPA) and quantitative risk analysis (for
example FTA) for dust-related events
YES
Secondary
Dust Explosion
YES
NO
Ignition?
Combustible
Dust is
Released
Reportable
Environmental
Incident
NO
NO
No dust-related
event
Re-dispersion?
YES
Operator
Controls?
Cleaning
3/13/2012
No dust-related
event
27
Qualitative Risk Analysis
Dust explosions tend to be high
consequence and low frequency
events
PHA team must be careful
while applying qualitative risk
analysis for dust explosion events
3/13/2012
CONSEQUENCES
Do not underestimate the
hazard and consider catastrophic
dust explosion events to be not
credible
LIKELIHOOD
LOW
MEDIUM
HIGH
HIGH
MEDIUM
LOW
28
Summary
PHA Team is responsible for identifying, evaluating and
controlling combustible dust hazards; and thus to analyze
and minimize Process Risk
Always look beyond process equipment
Involve appropriate skills, knowledge and experience on
combustible dust hazards
Verify minimum safe venting and levels of dust
accumulation during a field tour
Review detailed process safety information for:
Correct interpretation & application of test data
Use checklist to check compliance with RAGAGEPs
Use What-if/Checklist methodology for Hazards
Evaluation with emphasis on purpose-built checklists
Do not underestimate the combustible dust hazards and
consider catastrophic dust explosion events to be
credible when analyzing the risk.
3/13/2012
29
3/13/2012