UBC DIVISION-III(Wind design)
S.No
1
2
Description
H = Height of the building
W = Width of the building
Units
m
m
50
40
considered for tulsyan
Condition:
Structure is sensitive to wind exited osillation
If H / W > 5 & Height > 121.9 m
3(a)
H/W
3(b)
Height of building
4(a)
Selected exposure type
4(b)
Ce =Combined height,exposure & gust factor coeff.
5(a)
Selected type of method
5(b)
Cq = Pressure coefficient
6(a)
Basic wind speed
qs = wind stagnation pressure
7(a)
C
1.8
(for 50 m height)
Method -2(Projected area) as we wont used gabled type structu
structure over 40 feet height
mph
1.4
0.7
0.5
1.2
70
psf
KN/m2
12.6
0.60354
Iw = Wind importance factor
Design wind pressure = Ce Cq qs Iw
note
1
1.25
No Wind oscillations
No Wind oscillations
1.25
KN/m2
Kg/cm2
(for vertical projected area)
(for horizontal projected area)
(top storey of partially enclosed structure)
(combined)
(from fig 16.1 based on the type of region)
(table = 16F)
(for essential or hazardous facility)(table 16
1.901151
0.0193797248
If H / W > 5 & Height > 121.9 m then the structure has to be designed by the appreoved
national standard
Terms related to wind design
considered for tulsyan
(table -16G)
we wont used gabled type structure &
al projected area)
ontal projected area)
y of partially enclosed structure)
16.1 based on the type of region)
ntial or hazardous facility)(table 16-K)