IDMT:
A power transformer feeds an 11 KV bus bar through a circuit breaker.
The bus bar feeds two outgoing feeders through two circuit breakers.
Current transformers housed in the transformer & the feeders circuit
breakers are assumed to have turns ratios of 1000/1 & 500/1
respectively. The earth relays on all circuit breakers have plug settings
of 20%, the time multiplier setting being 0.2 for the feeders. A single
phase to earth fault of 1000A occurs on one of the outgoing feeders.
Find the operating time of the feeder relay & suggest suitable time
multiplier, which could be adopted for the transformer relay in order to
ensure adequate discrimination.
Use the standard IDMT time current characteristics, attached.
Take a minimum grading margin of 0.3 seconds.
Solution:
Given that PMS (plug setting) = 20% = 0.2
TMS (for feeders) = 0.2
fault current 1000
= =10 A
CM = Current multiplier = CT ratioPMS 5000.2
From the graph when I (on x-axis) = 10 & TMS =0.2
Then operating time = 0.5 sec (for feeder)
Operating time for transformer = operating time for feeder + margin =
0.5+0.3=0.8 sec
fault current 1000
CM (for transformer)= CT ratioPMS = 10000.2 =5 A
With operating time = 0.8 & current 5 , from graph
TMS for transformer = 0.2
10 MVA transformer, feeds an 11 KV bus bar through a circuit breaker.
The bus bar feeds two outgoing feeders through other circuit breakers.
Current transformers housed in the transformer & the feeders circuit
breakers are assumed to have turns ratios of 525/1 & 325/1
respectively. The earth relays on all circuit breakers have plug settings
of 20%, the time multiplier setting being 0.2 for the feeders. A single
phase to earth fault of 404A occurs on one of the outgoing feeders.
Find the operating time of the feeder relay & suggest suitable time
multiplier, which could be adopted for the transformer relay in order to
ensure adequate discrimination.
Use the standard IDMT time current characteristics (attached).
Take a minimum grading margin of 0.4 seconds.
Solution:
Given that PMS (plug setting) = 20% = 0.2
TMS (for feeders) = 0.2
fault current 404
= =6.2 A
CM = Current multiplier = CT ratioPMS 3250.2
From the graph when I (on x-axis) = 6.2 & TMS =0.2
Then operating time = 0.7 sec (for feeder)
Operating time for transformer = operating time for feeder + margin =
0.7+0.4=1.1 sec
fault current 404
CM (for transformer)= CT ratioPMS 5250.2 =3.85 A
=
With operating time = 1.1 & current 3.85 , from graph
TMS for transformer = 0.2
In the system shown below relays on all circuit breakers have plug
settings of 100%, the time multiplier setting being 0.1 for R3. Given
the 3-phase fault levels shown, determine suitable time multiplier
settings for relays R2 &R1.
Use the standard IDMT time current characteristics (attached).
Take a minimum grading margin of 0.4 seconds.
Solution (not sure !!):
PMS=100%=1
TMS = 0.1 for R3
fault current 1100
= =22 A
CM= CT ratioPMS 501
Then from graph, operating time =0.22 sec
R2 operating time = R3 operating time + margin = 0.22+0.4=0.62 sec
2300
CM for R2 = 1001 =23 A
Then TMS of R2 from graph using time = 0.62 & current =23,, is 0.2
R1 operating time = 0.62 + 0.4 = 1.02
CM= 13000/400 = 32.5
TMS for R1= 0.4