5306 4 2001 CO2 System PDF
5306 4 2001 CO2 System PDF
Fire extinguishing
installations and
equipment on
premises
Part 4: Specification for carbon dioxide
systems
ICS 13.220.20
Contents
Page
Foreword iii
Introduction 1
1 Scope 1
2 Normative references 1
3 Terms and definitions 3
4 Characteristics and uses of carbon dioxide 5
5 Types of system 5
6 Planning 6
7 Working documents 6
8 Commissioning and acceptance 7
9 Inspection, maintenance, testing and training 10
10 Total flooding systems 11
11 Local application systems 21
12 Manual hose systems 26
13 System components 27
14 System operation 28
15 Safety precautions 29
16 Carbon dioxide supply 33
17 Quantity of carbon dioxide 34
18 Storage containers 34
19 Pipework 36
20 Installation of pipework 40
21 Marking of pipework 43
Annex A (normative) Door fan test for determination of minimum hold time 44
Annex B (informative) Service schedule 50
Annex C (normative) Determination of carbon dioxide concentrations for
flammable liquids and gases 51
Annex D (informative) Examples of calculation of carbon dioxide
requirements 56
Annex E (informative) Determination of carbon dioxide pipe and orifice size 57
Bibliography 69
Figure 1 Calculated CO2 loss rate based on an assumed 21 C temperature
within the enclosure and 21 C ambient outside 14
Figure 2 Aiming position for angled discharge nozzles 26
Figure 3 Label to be displayed at manual control 32
Figure 4 Label to be displayed at entrances to hazard 33
Figure C.1 Cup burner apparatus 55
Figure E.1 Pressure drop in pipeline for 20.7 bar storage pressure 61
Figure E.2 Pressure drop in pipeline for 51.7 bar storage pressure 62
Table 1 Volume factors 16
Table 2 Minimum carbon dioxide concentration for extinction 17
Table 3 Hazard factors 18
Table 4 Extended discharge gas quantities for enclosed recirculation:
rotating electrical machines 20
Table 5 Aiming factors for nozzles installed at an angle (based on 150 mm
freeboard) 26
Table 6 Safety precautions for total flooding systems 29
BSI 07-2001 i
BS 5306-4:2001
Page
Table 7 Carbon dioxide requirements 34
Table 8 Monitoring facilities 35
Table 9 Closed sections of pipework 37
Table 10 Open-ended pipework 38
Table 11 Pipe fittings for closed and open ended pipework section
High pressure systems 39
Table 12 Pipe fittings for closed and open ended pipework section
Low pressure systems 39
Table 13 Maximum pipework support spacings 41
Table 14 Safety clearances to enable operation, inspection, cleaning,
repairs, painting and maintenance work to be carried out 43
Table E.1 Values of Y and Z 58
Table E.2 Values of Y and Z for 51.7 bar storage 59
Table E.3 Discharge rate of equivalent orifice area for low pressure
storage (20.7 bar) 64
Table E.4 Equivalent length of threaded pipe fittings 64
Table E.5 Equivalent length of welded pipe fittings 65
Table E.6 Elevation correction factors for low pressure systems 65
Table E.7 Elevation correction factors for high pressure systems 65
Table E.8 Discharge rate of equivalent orifice area for high pressure
storage (51.7 bar) 66
Table E.9 Equivalent orifice sizes 67
ii BSI 07-2001
BS 5306-4:2001
Foreword
Summary of pages
This document comprises a front cover, an inside front cover, pages i to iv,
pages 1 to 69 and a back cover.
The BSI copyright notice displayed in this document indicates when the
document was last issued.
Introduction
It is important that the fire protection of a building or plant is considered as a whole. Carbon dioxide (CO2)
systems form only a part, though an important part, of the available facilities, but it should not be assumed
that their adoption necessarily removes the need to consider supplementary measures, such as the
provision of portable fire extinguishers or other mobile appliances for first aid or emergency use or to deal
with special hazards.
CO2 has for many years been a recognized effective medium for the extinction of flammable liquid fires and
fires in the presence of electrical and ordinary class A hazards, but it should not be forgotten, in the
planning of comprehensive schemes, that there may be hazards for which these mediums are not suitable,
or that in certain circumstances or situations there may be dangers in their use, requiring special
precautions.
Advice on these matters can be obtained from the appropriate fire authority, the Health and Safety
Executive or other enforcing authority under the Health and Safety at Work etc. Act 1974 [1], and insurers.
In addition, reference should be made as necessary to other parts of BS 5306.
It is essential that fire extinguishing equipment is carefully maintained to ensure instant readiness when
required. This routine is liable to be overlooked or given insufficient attention by supervisors. It is,
however, neglected at peril to the lives of occupants of the premises and at the risk of crippling financial
loss. The importance of maintenance cannot be too highly emphasized.
1 Scope
This part of BS 5306 specifies requirements and gives recommendations for the provision of carbon dioxide
fire extinguishing systems in buildings or industrial plant. These systems are designed to convey carbon
dioxide from a central source on the premises as and when required for the extinction of fire or the
protection of particular plant or parts of the premises against possible fire risk.
This part of BS 5306 does not apply to carbon dioxide portable fire extinguishers or to wheeled appliances
for conveying carbon dioxide in containers.
NOTE 1 Requirements and recommendations for carbon dioxide portable fire extinguishers (together with portable fire
extinguishers of other types) are given in BS EN 3-1 to -5 and BS 5306-3.
This standard gives requirements and characteristic data for carbon dioxide, the types of fires for which it
is a recommended extinguishing medium, and requirements and recommendations for three established
types of piped system embodying different concepts and employing different methods for the application of
carbon dioxide, i.e.:
a) the total flooding system;
b) the local application system; and
c) the manual hose reel system.
Two methods of operation, i.e. manual and automatic, are also specified. Requirements and
recommendations are given on the selection of a system, on operational methods, and on the design,
maintenance and efficient operation of installations. Reference is also made to the part that carbon dioxide
systems plays in general schemes of fire protection of premises, having regard to safety as well as efficiency.
NOTE 2 Unless otherwise stated in the text all pressures are in bar gauge.
1 bar = 105 N/m2 = 100 kPa.
2 Normative references
The following normative documents contain provisions which, through reference in this text, constitute
provisions of this part of this British Standard. For dated references, subsequent amendments to, or
revisions of, any of these publications do not apply. For undated references, the latest edition of the
publication referred to applies.
BS 21, Specification for pipe threads for tubes and fittings where pressure-tight joints are made on the
threads (metric dimensions).
BS 381C:1996, Specification for colours for identification, coding and special purposes.
BS 476-4, Fire tests on building materials and structures Part 4: Non-combustibility test for materials.
BSI 07-2001 1
BS 5306-4:2001
BS 476-20, Fire tests on building materials and structures Part 20: Method for determination of the fire
resistance of elements of construction (general principles).
BS 476-21, Fire tests on building materials and structures Part 21: Methods for determination of the fire
resistance of loadbearing elements of construction.
BS 476-22, Fire tests on building materials and structures Part 22: Methods for determination of the fire
resistance of non-loadbearing elements of construction.
BS 476-23, Fire tests on building materials and structures Part 23: Methods for determination of the
contribution of components to the fire resistance of a structure.
BS 1387, Specification for screwed and socketed steel tubes and tubulars and for plain end steel tubes
suitable for welding or for screwing to BS 21 pipe threads.
BS 1640-3:1968, Specification for steel butt-welding pipe fittings for the petroleum industry
Part 3: Wrought carbon and ferritic alloy steel fittings Metric units.
BS 1710, Specification for identification of pipelines and services.
BS 1821, Specification for class I oxy-acetylene welding of ferritic steel pipework for carrying fluids.
BS 2051-1, Tube and pipe fittings for engineering purposes Part 1: Copper and copper alloys capillary
and compression tube fittings for engineering purposes.
BS 2051-2, Tube and pipe fittings for engineering purposes Part 2: Specification for olive type copper alloy
compression tube fittings.
BS 2633, Specification for Class I arc welding of ferritic steel pipework for carrying fluids.
BS 2915, Specification for bursting discs and bursting disc devices.
BS 3410, Specification for metal washers for general engineering purposes.
BS 3601, Specification for carbon steel pipes and tubes with specified room temperature properties for
pressure purposes.
BS 3602-1, Steel pipes and tubes for pressure purposes: carbon and carbon manganese steel with specified
elevated temperature properties Part 1: Specification for seamless and electric resistance welded
including induction welded tubes.
BS 3605-2, Austenitic stainless steel pipes and tubes for pressure purposes Part 2: Specification for
longitudinally welded tubes.
BS 3799:1974, Specification for steel pipe fittings, screwed and socket-welding for the petroleum industry.
BS 4320, Specification for metal washers for general engineering purposes Metric series.
BS 4368-1, Compression couplings for tubes Part 1: Split collet compression fittings.
BS 4422-4, Glossary of terms associated with fire Part 4: Fire extinguishing equipment.
BS 4677, Specification for arc welding of austenitic stainless steel pipework for carrying fluids.
BS 4800:1989, Schedule of paint colours for building purposes.
BS 5355, Specification for filling ratios and developed pressures for liquefiable and permanent gases.
BS 5430-1, Periodic inspection, testing and maintenance of transportable gas containers (excluding
dissolved acetylene containers) Part 1: Specification for seamless steel containers of water capacity
0.5 litres and above.
BS 5839-1, Fire detection and alarm systems for buildings Part 1: Code of practice for system design,
installation and servicing
BS 6266, Code of practice for fire protection for electronic data processing installations.
BS 7273-1, Code of practice for the operation of fire protection measures Part 1: Electrical actuation of
gaseous total flooding extinguishing systems.
BS 7273-2, Code of practice for the operation of fire protection measures Part 2: Mechanical actuation of
gaseous total flooding and local application extinguishing systems.
BS 7671, Requirements for electrical installations IEE Wiring Regulations Sixteenth edition.
2 BSI 07-2001
BS 5306-4:2001
BS EN 856, Rubber hoses and hose assemblies Rubber-covered spiral wire reinforced hydraulic type
Specification.
BS EN 1057, Copper and copper alloys Seamless, round copper tubes for water and gas in sanitary and
heating applications.
BS EN 1515-1, Flanges and their joints Bolting Part 1: Selection of bolting.
BS EN 1435, Non-destructive examination of welds Radiographic examination of welded joints.
BS EN 1964-1, Transportable gas cylinders Specification for the design and construction of refillable
transportable seamless steel gas cylinders of water capacities from 0,5 litre up to and including 150 litres
Part 1: Cylinders made of seamless steel with an Rm value of less than 1 100 MPa.
BS EN 1964-3, Transportable gas cylinders Specification for the design and construction of refillable
transportable seamless steel gas cylinders of water capacities from 0,5 litre up to and including 150 litres
Part 3: Cylinders made of seamless stainless steel with an Rm value of less than 1 100 MPa.
BS EN 10241:2000, Steel threaded pipe fittings.
BS EN 10242:1995, Threaded pipe fittings in malleable cast iron.
BS EN 12094 (all parts), Fixed firefighting systems Components for gas extinguishing systems.
BS EN 12094-8, Fixed firefighting systems Components for gas extinguishing systems
Part 8: Requirements and test methods for flexible connectors for CO2 systems.
BS EN 12449, Copper and copper alloys Seamless, round tubes for general purposes.
BS EN 25923, Fire extinguishing media Carbon dioxide (ISO 5923).
PD 5500, Specification for unfired fusion welded pressure vessels.
PD 6550 (all parts), Explanatory supplement to BS 5500:1988 Specification for unfired fusion welded
pressure vessels Section three Design.
ANSI B16.5:1996, Steel pipe flanges and flanged fittings.
ANSI B16.9:1993, Factory-made wrought steel buttwelding fittings.
ANSI B16.11:1997, Forged steel fittings, socket-welding and threaded.
API 5B, Specification for threading, gauging and thread inspection of casing, tubing and line pipe threads.
API 5L, Specification for line pipe.
ASTM A105M, Specification for carbon steel forgings for piping applications.
ASTM A106-77, Specification for seamless carbon steel pipe for high temperature service.
ASTM A234/A234M, Specification for piping fittings of wrought carbon steel and alloy steel for moderate
and high temperature service.
3 Terms and definitions
For the purposes of this part of BS 5306, the terms and definitions given in BS 4422-4 and the following
apply.
3.1
authority
organization, office or individual responsible for approving equipment, installations or procedures
3.2
automatic operation
method of operation in which a fire extinguishing system, under specified conditions, functions without
intervention by a human operator
3.3
automatic/manual to manual only changeover switch
means of converting a fire extinguishing system from automatic/manual to manual only actuation or vice
versa
NOTE This may be in the form of a manual switch on the control panel or other units, or a personnel door interlock.
BSI 07-2001 3
BS 5306-4:2001
3.4
closed section of pipework
section between two valves which may be intentionally or unintentionally closed, or between valves and
carbon dioxide storage containers including filling and gas balance lines
3.5
competent person
person capable of carrying out the inspection and maintenance procedures of clause 9, by reason of
experience and access to the requisite information, training, tools and equipment
3.6
deep-seated fire
fire involving solids subject to smouldering
3.7
filling density
mass of extinguishant per unit volume of container
3.8
high pressure storage
storage of carbon dioxide at ambient temperature, nominally 58 bar at 20 C
3.9
local application system
automatic or manual fire extinguishing system in which a fixed supply of carbon dioxide is permanently
connected to fixed piping with nozzles arranged to discharge the carbon dioxide directly to a fire occurring
in a defined area that has no enclosure surrounding it, or is only partially enclosed, and that does not
produce an extinguishing concentration throughout the entire volume containing the protected hazard
3.10
low pressure storage
storage of carbon dioxide in pressure containers at a controlled low temperature of 18 C
NOTE The pressure in this type of storage is approximately 21 bar.
3.11
manual operation
method of operation in which a fire extinguishing system, under specified conditions, functions by means
of intervention of a human operator
3.12
manual hose reel system
manual fire extinguishing system consisting of a hose, stowed on a reel or a rack, with a manually operated
discharge nozzle assembly, all connected by a fixed pipe to a supply of carbon dioxide
3.13
material conversion factor (MCF)
numerical factor used when the minimum design concentration of carbon dioxide for the material at risk
exceeds 34 %, to increase the basic quantity of carbon dioxide [as obtained by application of the volume
factor (see 3.19)] required for protection against surface fires
3.14
open-ended pipework
pipework between a valve (including a relief valve) and open nozzles which cannot be under a continuous
pressure
3.15
pilot container
container whose contents are only used for system actuation and whose contents do not form part of the
quantity of extinguishant required
4 BSI 07-2001
BS 5306-4:2001
3.16
surface fire
fire involving flammable liquids, gases or solids not subject to smouldering
3.17
total flooding system
automatic or manual fire extinguishing system in which a fixed supply of carbon dioxide is permanently
connected to fixed piping with nozzles arranged to discharge the carbon dioxide into an enclosed space in
order to produce a concentration sufficient to extinguish fire throughout the entire volume of the enclosed
space
3.18
user
person(s) responsible for or having effective control over the fire safety provisions adopted in or appropriate
to the premises or the building
3.19
volume factor
numerical factor that, when applied to the volume of an enclosure, indicates the basic quantity of carbon
dioxide (subject to a minimum appropriate to the volume of the enclosure) required for protection against
surface fires
4 Characteristics and uses of carbon dioxide
4.1 General
Carbon dioxide for use in fire extinguishing systems shall conform to BS EN 25923.
COMMENTARY AND RECOMMENDATIONS ON 4.1. Carbon dioxide at atmospheric pressure is a colourless,
odourless and electrically non-conducting inert gas which is almost 1.5 times as dense as air. It is stored as
a liquid under pressure, and 1 kg of liquid carbon dioxide expanded to atmospheric pressure will produce
about 0.52 m3 of free gas at a temperature of 10 C.
Carbon dioxide extinguishes fire by reducing the oxygen content of the atmosphere to a point where it will
not support combustion. Reducing the oxygen content from the normal 21 % in air to 15 % will extinguish
most surface fires, though for some materials a greater reduction is necessary. In some applications the
cooling effect of carbon dioxide will assist extinction.
Carbon dioxide may be used to fight fires of classes A and B as defined in BS EN 2. Class C fires may also
be extinguished by carbon dioxide but in these cases the risk of explosion after extinction should be carefully
considered.
Carbon dioxide may be ineffective on fires involving material such as metal hydrides, reactive metals such
as sodium, potassium, magnesium, titanium and zirconium, and chemicals containing oxygen available for
combustion, such as cellulose nitrate.
Carbon dioxide is suitable for use on fires involving live electrical apparatus.
4.2 Electrostatic discharge
Carbon dioxide systems shall not be designed, installed or recommended for inerting explosive
atmospheres. Carbon dioxide systems shall not be test discharged into areas containing explosive
atmospheres.
COMMENTARY AND RECOMMENDATIONS ON 4.2. The discharge of carbon dioxide is known to produce
electrostatic charges which, under certain conditions, could create a spark.
5 Types of system
CO2 systems shall conform to the requirements of one of the following types:
a) total flooding system;
b) local application system;
c) manual hose reel system.
BSI 07-2001 5
BS 5306-4:2001
COMMENTARY AND RECOMMENDATIONS ON CLAUSE 5. In the selection of the type of carbon dioxide
extinguishing system account should be taken of:
a) the degree of hazard to personnel arising from the CO 2 discharge;
b) the nature of the hazard;
c) the location and degree of enclosure of the hazard;
d) operating requirements dictating either manual or automatic operation;
e) other factors discussed in clauses 10, 11 and 12.
6 Planning
Where a fixed carbon dioxide extinguishing system is being considered for new or existing buildings the
appropriate authority shall be consulted.
Where a fire detection and control system is used in conjunction with a CO2 system it shall conform to the
requirements of BS 5839-1, BS 6266 and BS 7273-1 and -2 where appropriate.
COMMENTARY AND RECOMMENDATIONS ON CLAUSE 6. The appropriate authority should be informed as early
as possible of the type of carbon dioxide system to be installed and the system design engineers should be
fully informed of the protection required in any area, whether total flooding, local application or hose reel.
There may be other requirements of the authority which should be incorporated into the planning stages of
the contract.
7 Working documents
7.1 General
Working documents shall be prepared only by persons fully experienced in the design of fire extinguishing
systems.
Deviation from working documents shall require the permission of the appropriate authority.
7.2 Requirements
Working documents shall include the following items:
a) drawings, to an indicated scale, of extinguishant distribution system including containers, location of
containers, piping and nozzles, any valves and pressure reducing devices, and pipe hanger spacing;
b) name of owner and occupant;
c) location of building in which hazard is located;
d) location and construction of protected enclosure walls and partitions;
e) enclosure cross-section, full height or schematic diagram, including raised access floor and suspended
ceiling;
f) type of extinguishant being used;
g) extinguishing or inerting concentration, design concentration and maximum concentration;
h) description of occupancies and hazards being protected;
i) specification of containers used, including capacity, storage pressure and mass including
extinguishant;
j) description of nozzle(s) used including inlet size, orifice port configuration, and orifice size/code;
k) description of pipe valves and fittings used including material specifications, grade, and pressure
rating;
l) equipment schedule or bill of materials for each piece of equipment or device showing device name,
manufacturer, model or part number, quantity and description;
m) isometric view of extinguishant distribution system showing the length and diameter of each pipe
segment and node reference numbers relating to the flow calculations;
n) enclosure pressurization and venting calculations (total flooding systems only);
o) description of fire detection, actuation and control systems.
6 BSI 07-2001
BS 5306-4:2001
[Link] An adequate quantity of carbon dioxide to satisfy the design requirement shall be provided. For
total flooding systems the actual enclosure volumes shall be checked against those indicated on the system
drawings to ensure the proper quantity of extinguishant. Fan rundown and damper closure time shall be
taken into consideration.
BSI 07-2001 7
BS 5306-4:2001
[Link] Unless the total piping contains no more than one change in direction fitting between the storage
container and the discharge nozzle, and where all piping is physically checked for tightness, the following
tests shall be carried out.
a) All open ended piping shall be pneumatically tested in a closed circuit for a period of 10 min at 3 bar.
At the end of 10 min, the pressure drop shall not exceed 20 % of the test pressure.
NOTE 1 Pressure testing is not required where the piping has been physically checked for tightness and there is no more than
one change in direction between the container and the nozzle.
b) All closed sections of pipework shall be hydrostatically tested to a minimum of 190 bar for high
pressure systems and 36 bar for low pressure systems. At the end of 2 min there shall be no leakage. On
completion of the test, the tested sections shall be purged to remove moisture.
NOTE 2 It is recommended that hydrostatic testing is carried out at the manufacturers works.
NOTE 3 Pressure testing is not required where the piping between the manifold and a valve has been physically checked for
tightness and there is no more than one change in direction between the manifold and the valve.
CAUTION Pneumatic pressure testing creates a potential risk of injury to personnel in the area, as a
result of airborne projectiles if rupture of the piping system occurs. Prior to conducting the pneumatic
pressure test, the protected area shall be evacuated and appropriate safeguards shall be provided for test
personnel.
[Link] A test using nitrogen, or suitable alternative, shall be performed on the piping network to verify
that flow is continuous and that the piping and nozzles are unobstructed.
[Link] Fusible link systems shall be tested to ensure that control cable lines are free and that operating
control weights develop sufficient energy to operate container and/or direction valve control mechanisms.
[Link] Pneumatic detection systems shall be tested with a manometer to ensure correct breathing rate
and leak free capillary lines.
[Link] Nameplates and instruction plates shall be checked to ensure they are correctly worded.
[Link] Detectors shall be activated in accordance with the manufacturers instructions to ensure correct
operation and subsequent activation of control mechanisms.
8.1.4 Review of enclosure integrity
All total flooding systems shall have the enclosure checked to locate and then effectively seal any
significant air leaks that could result in a failure of the enclosure to hold the specified extinguishant
concentration level for the specified holding period (see also 10.4.1 and 10.5). Unless otherwise required by
the appropriate authority, the test specified in Annex A shall be used.
8.1.5 Review of electrical components
[Link] All wiring systems shall be properly installed in accordance with BS 7671 (IEE Wiring Regulations)
and the system drawings. A.c. and d.c. wiring shall not be combined in a common conduit unless properly
shielded and grounded.
[Link] All field circuitry shall be measured for ground fault and short circuit condition. When measuring
field circuitry, all electronic components (such as detectors or special electronic equipment for other
detectors or their mounting bases) shall be removed and jumpers properly installed to prevent the
possibility of damage within these devices. Components shall be re-instated after measuring.
[Link] Adequate and reliable primary standby sources of energy, which conform to the requirements
of 8.1.9, shall be used to provide for operation of the detection, signalling, control and actuation
requirements of the system.
[Link] All auxiliary functions such as alarm sounding or displaying devices, remote annunciators, air
handling shutdown, power shutdown, etc., shall be checked for proper operation in accordance with system
requirements and design specifications.
Alarm devices shall be installed so that they are audible and visible under normal operating and
environmental conditions.
NOTE Where possible, all air-handling and power cut-off controls should be of the type that once interrupted require manual restart
to restore power.
8 BSI 07-2001
BS 5306-4:2001
[Link] Where alarm silencing is provided it shall not affect other auxiliary functions such as air handling
or power cut-off, if required in the design specification.
[Link] The detection devices shall be checked to ensure that the types and locations are as specified in the
system drawings and are in accordance with the manufacturers requirements.
[Link] Manual release devices shall be checked to ensure that they are properly installed, and are readily
accessible, accurately identified, and properly protected to prevent damage.
[Link] All manual release devices used to release extinguishants shall be checked to ensure that they
require two separate and distinct actions for operation. All manual release devices shall be properly
identified. Particular care shall be taken where manual release devices for more than one system are in
close proximity and could be confused or the wrong system actuated. Manual release devices in this
instance shall be clearly identified as to which hazard enclosure they protect.
[Link] For systems with a main/reserve capability, the main/reserve switch shall be checked to ensure that
it is properly installed, readily accessible, and clearly identified.
[Link] For systems using hold switches, the switches shall be checked to ensure that they are of the
deadman type requiring constant manual pressure, are properly installed, readily accessible within the
hazard area, and clearly identified.
[Link] The control panel shall be checked to ensure that it is properly installed and readily accessible.
8.1.6 Preliminary functional tests
[Link] Where a system is connected to a remote central alarm station, the station shall be notified that the
fire system test is to be conducted and that an emergency response by the fire department or alarm station
personnel is not required. All personnel concerned at the end-users facility shall be notified that a test is
to be conducted and instructed as to the sequence of operation.
[Link] Each extinguishant storage container release mechanism and selector valves, where fitted, shall be
disabled or removed so that activation of the release circuit will not release extinguishant. The release
circuit shall be reconnected with a functional device in lieu of each extinguishant storage container release
mechanism.
NOTE Functional devices may include suitable lamps, flash bulbs, or circuit breakers. Pneumatically actuated functional devices
may include pressure gauges. The manufacturers recommendations should be referred to in all cases.
[Link] Pneumatic equipment shall be checked for integrity to ensure proper operation.
BSI 07-2001 9
BS 5306-4:2001
9.1.4 Enclosure
At least every 12 months it shall be determined if penetrations or other changes to the protected enclosure
have occurred that could affect leakage and carbon dioxide performance. If this is not possible, it shall be
positively established that no changes to the enclosure have occurred. This shall be evaluated by repeating
the test for enclosure integrity in accordance with Annex A.
10 BSI 07-2001
BS 5306-4:2001
Where the integrity test reveals increased leakage that would result in an inability to retain the carbon
dioxide for the required period, remedial action shall be carried out.
Where it is established that changes to the volume of the enclosure or to the type of hazard within the
enclosure, or both, have occurred, the system shall be redesigned to provide the original degree of
protection.
9.2 Maintenance
9.2.1 General
The user shall carry out a programme of inspection, arrange a service schedule and keep records of
inspections and servicing.
NOTE The continued capability for effective performance of a fire fighting system depends on fully adequate service procedures
with, where possible, periodic testing.
9.3 Training
All persons who may be expected to inspect, test, maintain, or operate fire extinguishing systems shall be
trained and kept adequately trained in the functions they are expected to perform.
Personnel working in an enclosure protected by a gaseous extinguishant shall receive training in the
operation and use of the system, and on safety issues.
10 Total flooding systems
10.1 Uses
Total flooding systems shall conform to clause 6, clause 7, clause 8 and clause 9, unless otherwise specified
in this clause, and may be used to extinguish or control the following fires:
a) surface fires involving flammable liquids, gases and solids;
b) deep-seated fires involving solids subject to smouldering.
10.2 General design
10.2.1 The quantity of carbon dioxide, which will vary according to the hazard and permitted openings,
shall be sufficient to reduce the oxygen content of the atmosphere within the enclosure to a point where
combustion can no longer be sustained. The rate of application and the time necessary to maintain the
extinguishing concentration shall be determined according to the hazard, and as specified in 10.4, 10.5,
and 10.6.
The distribution of the carbon dioxide shall be arranged so that it is evenly and thoroughly mixed with the
existing atmosphere.
COMMENTARY AND RECOMMENDATIONS ON 10.2.1. Special venting may be required to avoid excessive pressure
build-up resulting from the volume of carbon dioxide discharged into the hazard area (see 10.3.3).
BSI 07-2001 11
BS 5306-4:2001
10.3 Enclosure
10.3.1 General
The protected volume of an enclosure shall be enclosed by elements of construction having a fire resistance
of not less than 30 min when tested in accordance with BS 476-20, -21, -22 and -23, whichever is
appropriate, and classified as non-combustible when tested in accordance with BS 476-4. Where openings
can be closed, they shall be arranged to close before or at the start of gas discharge. Where carbon dioxide
can flow freely between two or more interconnected volumes, the quantity of carbon dioxide shall be the
sum of quantities calculated for each volume using the respective volume and material conversion factors.
If one volume requires higher than normal concentration, the higher concentration shall be used in all
interconnected volumes. The volume of the enclosure shall be the gross volume. The only permitted
reductions shall be permanent, impermeable building elements within the enclosure.
All total flooding systems shall have the enclosure checked to locate and then effectively seal any
significant air leaks that could result in a failure of the enclosure to hold the specified extinguishant
concentration level for the specified holding period (see also 10.4.1 and 10.5). Unless otherwise required by
the relevant authority, the test specified in Annex A shall be used.
COMMENTARY AND RECOMMENDATIONS ON 10.3.1. A well enclosed space is required to maintain the
extinguishing concentration of carbon dioxide.
NOTE Rooms with associated cable/floor voids are not considered as interconnected volumes.
12 BSI 07-2001
BS 5306-4:2001
where
BSI 07-2001 13
BS 5306-4:2001
1000
900
800
700
600
500
400
100%
300
80%
200 70%
60%
1 50%
100
90
80 40%
70
60
30%
50
40
30 20%
20
10%
10
1 2 3 4 5 6 7 8 9 10
2
Key
1 Leakage rate in kilograms of CO2/min/m2
2 Height in metres of atmosphere above centre line of opening
Figure 1 Calculated CO2 loss rate based on an assumed 21 C temperature within the
enclosure and 21 C ambient outside
14 BSI 07-2001
BS 5306-4:2001
where
A is the required vent area in square metres (m2);
M CO is the mass flow rate of CO2 in kilograms per second (kg/s);
2
M CO = 300/60 = 5 kg/s
2
1 3
HOM = ---------------------------------------------------------------------------------- = 0.6559m /kg
{ ( 0.66 1.29 ) + ( 0.34 1.98 ) }
%P = 100 Pa
5 0.505 2
A = ---------------------------------------------- = 0.312m
( 100 0.655 9 )
In some instances, particularly where hazardous materials are involved, relief openings are already
provided for explosion venting. These and other openings often provide adequate venting.
NOTE 1 Some or all of the required vent area (A) may be provided by the inherent natural leakage of the enclosure.
Determine the additional vent area (if any) to be installed from:
Additional vent area = A 0.863 (ELA)
Where ELA is the enclosures equivalent leakage area (ELA) determined by the fan integrity test. It follows
that if A is less than or equal to 0.863 of the ELA then no additional vent area is required.
NOTE 2 Where over pressurization vents are required these should be of the self-closing type.
BSI 07-2001 15
BS 5306-4:2001
16 BSI 07-2001
BS 5306-4:2001
BSI 07-2001 17
BS 5306-4:2001
COMMENTARY AND RECOMMENDATIONS ON 10.5. In some instances, a much longer holding period may be
necessary to ensure that all smouldering is extinguished and material is sufficiently cooled to prevent
re-ignition. Any possible leakage should be given special consideration since no allowance is included in the
basic factors listed in Table 3.
Ventilation fans should be switched off and dampers closed in conjunction with the discharge of carbon
dioxide.
The flooding factors specified in Table 3 result from practical tests for specific hazards under average use
and storage conditions.
18 BSI 07-2001
BS 5306-4:2001
BSI 07-2001 19
BS 5306-4:2001
Protected volume
kg m3 m3 m3 m3 m3 m3 m3 m3
45 34 28 23 17 14 11 9 6
68 51 43 34 28 21 17 14 11
91 68 55 45 37 28 24 18 14
113 93 69 57 47 37 30 23 17
136 130 88 68 57 47 37 28 20
159 173 116 85 71 57 47 34 26
20 BSI 07-2001
BS 5306-4:2001
11.2.3 Where adjacent hazards cannot be isolated and fire spread is likely, they shall be treated as one
hazard.
COMMENTARY AND RECOMMENDATIONS ON 11.2.3. Without prejudice to statutory provisions which are
applicable to the design of the plant, that may require the containment and/or enclosure of flammable
materials and operations involving manipulation of them, consideration should be given to enclosing the
area including the provision of a low wall or bund. This will not only retain the extinguishing medium, but
will also reduce the chances of fire entering or leaving the protected space.
Care should be taken to cover the whole hazard, particularly any surrounding areas liable to splashing,
dripping, leakage or spillage, and to include all associated materials and/or equipment, such as freshly
coated stock, drain boards, hoods and ducts, that might extend fire outside, or lead fire into, the protected
space.
BSI 07-2001 21
BS 5306-4:2001
22 BSI 07-2001
BS 5306-4:2001
11.4.3 For high pressure systems, if a part of the hazard is to be protected by total flooding, the discharge
rate, QF, in kilograms per minute (kg/min) for the total flooding portion shall be calculated from the
equation:
MF
Q F = ----------------
1.4T L
where
MF is the total quantity of carbon dioxide for the total flooding portion in kilograms (kg);
TL is the liquid discharge time for the local application portion in minutes.
BSI 07-2001 23
BS 5306-4:2001
EXAMPLE OF CALCULATION
Hazard: quench tank (material conversion factor, MCF = 1)
Surface dimensions:
width: 0.92 m;
length: 2.13 m.
Nozzle location: assume that a survey indicates that nozzles can be positioned anywhere from 0.92 m
to 1.83 m away from the liquid surface without interfering with the operation.
From the manufacturers list of approved nozzles [a series of rated nozzles with their respective area of
coverage at a given height above the surface to be protected and a given flow rate in kilograms per minute
(kg/min)] select the minimum number of nozzles that will cover an area of 2.13 m 0.92 m. Assume that
the list has a nozzle which has a rated coverage of 1.08 m2 at a height of 1.52 m and a rated flow of
22.3 kg/min. Two nozzles will then cover a length of 2.16 m and a width of 1.08 m.
Total flow rate = 2 22.3 = 44.6 kg/min.
Carbon dioxide requirement = 44.6 0.5 1.4 (includes vapour) = 31.2 kg.
11.8 Volume method
11.8.1 General
The total discharge rate of local application systems shall be based on the volume of an assumed enclosure
entirely surrounding the hazard. The assumed enclosure shall be based on an actual closed floor unless
special provisions are made to take care of openings in the floor.
The assumed walls and ceiling of this enclosure shall be at least 600 mm from the main hazard, unless
actual walls are involved, and they shall enclose all areas of possible leakage, splashing or spillage. No
deductions shall be made for solid objects within this volume.
A minimum dimension of 1.2 m shall be used in calculating the volume of the assumed enclosure.
NOTE It is assumed that the hazard is not subjected to winds or forced draughts sufficient to dissipate the carbon dioxide.
COMMENTARY AND RECOMMENDATIONS ON 11.8.1. The volume method of system design is used where the fire
hazard consists of three-dimensional irregular objects that cannot be easily reduced to equivalent surface
areas.
11.8.2 System discharge rate
The total discharge rate for the basic system shall be equal to 16 kg/min/m3 of assumed volume for
enclosures with no walls.
If the assumed enclosure is partly defined by permanent continuous walls extending at least 600 mm above
the hazard (where the walls are not normally a part of the hazard), the discharge rate shall be
proportionately reduced to not less than 4 kg/min/m3 for walls completely surrounding the enclosure. In
computing the quantity of carbon dioxide required, the total discharge rate shall be multiplied by the
discharge time and, where applicable, the material conversion factor from Table 2.
NOTE Examples of calculations are given in Annex D.
COMMENTARY AND RECOMMENDATIONS ON 11.8.2. Nozzles should be located and directed so as to retain the
discharging carbon dioxide within the hazard volume by suitable coordination between nozzles and objects
in the hazard volume. Nozzles should be located so as to compensate for any possible effects of air currents,
winds or forced draughts.
11.9 Distribution system
11.9.1 General
The piping shall be designed in accordance with clause 19 and clause 20 to deliver the required rate of
application at each nozzle.
24 BSI 07-2001
BS 5306-4:2001
COMMENTARY AND RECOMMENDATIONS ON 11.9.1. Where long pipelines are required or where the piping may
be exposed to higher than normal temperatures, the quantity of carbon dioxide should be increased by an
amount sufficient to compensate for liquid carbon dioxide vaporized in cooling the piping. The pipeline
should be as direct as practicable with a minimum number of bends.
High pressure storage temperatures may range from 0 C to 46 C without requiring special methods of
compensating for changing flow rates.
NOTE Annex E gives a method and examples of pipe size determination.
BSI 07-2001 25
BS 5306-4:2001
Table 5 Aiming factors for nozzles installed at an angle (based on 150 mm freeboard)
Discharge anglea Aiming factor
45 to 60 0.25
60 to 75 0.25 to 0.375
75 to 90 0.375 to 0.5
90 (perpendicular) 0.5 (centre)
a Degrees from plane of hazard surface.
Nozzle discharging
at preselected rate
a) and pressure
b)
X
150
45
300
NOTE 1 The diagram shows nozzles discharging at a) 90 with the aiming point at the centre of the protected surface, and
at b) 45 with the aiming point at 0.25 of the width of the protected surface, into a tray containing liquid fuel with a freeboard
of 150 mm.
NOTE 2 X is the preselected height used to determine the flow rate required.
26 BSI 07-2001
BS 5306-4:2001
Where manual hose reels are installed in addition to fixed fire protection systems, the carbon dioxide supply
for the manual hose reel should be in addition to the quantity supplying the fixed fire protection system.
12.2 Hazard to personnel
Where the discharge of a manual hose reel system may lead to personnel being exposed to high
concentrations of carbon dioxide the safety precautions of clause 15 shall be applied.
COMMENTARY AND RECOMMENDATIONS ON 12.2. As stated in 4.2, the discharge of large amounts of carbon
dioxide to fight fire may create a hazard to personnel. The quantity of carbon dioxide that will be discharged,
related to the volume and geometry of the total enclosure, should be taken into account. If it is considered
that the developed concentration of carbon dioxide could be hazardous to personnel, the safety precautions
set out in clause 15 should be applied, and personnel escape routes should also be considered.
12.3 Location and spacing of manual hose reels
12.3.1 Manual hose reels shall be located where they will be accessible during a fire and within reach of
the protected hazards. Actuating controls shall be located at the hose reel station. Reels shall be ready for
immediate use.
12.3.2 If multiple hose reel stations are used, they shall be spaced so that any area within the hazard is
covered by one or more hose reels.
12.4 Rate and duration of discharge
12.4.1 General
The rate and duration of discharge and consequently the amount of carbon dioxide shall be determined by
the type and potential size of the hazard. A manual hose reel system shall have sufficient quantity of carbon
dioxide to permit its effective (liquid phase) use for at least 1 min.
12.4.2 Simultaneous use of hose reels
Where simultaneous use of two or more hose lines is possible, a sufficient quantity of carbon dioxide shall
be available to supply the maximum number of nozzles that are likely to be used at any one time for at
least 1 min.
12.5 Equipment design
12.5.1 Hose
Hoses used on systems with high pressure supply shall be designed in accordance with BS EN 856 for a
working pressure of 190 bar. Hoses used on systems with a low pressure supply shall operate safely at a
working pressure of 27 bar.
12.5.2 Discharge nozzle assembly
Hose reels shall be equipped with a discharge nozzle assembly intended for use by one person. This shall
incorporate a quick opening shut-off valve to control the flow of carbon dioxide through the nozzle for
directing the discharge, which shall be provided with a suitable insulated handle.
COMMENTARY AND RECOMMENDATIONS ON 12.5.2. For ease of manipulation the discharge nozzle assembly
should be attached to the hose by a swivel connection.
12.6 Charging the hose reel
All controls for actuating the system shall be located in the immediate vicinity of the hose reel storage.
NOTE Except when the hose line is in actual use, pressure should not be permitted to remain in the system.
COMMENTARY AND RECOMMENDATIONS ON 12.6. Operation of manual hose reel systems depends upon
manual actuation and manual manipulation of a discharge nozzle. Speed and simplicity of operation is,
therefore, essential for successful extinction.
13 System components
Principal components shall conform to and be installed in accordance with the appropriate part of
BS EN 12094 and the manufacturers instructions.
BSI 07-2001 27
BS 5306-4:2001
All devices shall be designed for the service they will encounter and shall not be readily rendered
inoperative or susceptible to accidental operation. Devices shall normally be designed to function properly
from 20 C to +50 C or shall be marked to indicate their temperature limitations.
Where the pressure of a permanent gas from pilot containers is used as a means of releasing the system,
the container shall be continuously monitored and a fault alarm given in the event of pressure loss in excess
of 10 %.
Where the pressure of a liquified gas from pilot containers is used as a means of releasing the system, the
container shall be continuously monitored and a fault alarm given in the event of excessive weight loss or
be duplicated.
COMMENTARY AND RECOMMENDATIONS ON CLAUSE 13. Various operating devices are necessary to control the
flow of the extinguishing agent to operate the associated equipment. These include container valves,
distribution valves, automatic and manual controls, delay devices, pressure trips and switches and
discharge nozzles.
All devices, especially those having external moving parts, should be located, installed or suitably protected
so that they are not subject to mechanical, chemical or other damage that would render them inoperable.
14 System operation
14.1 Manual control
Provision shall be made for manual operation of the fire fighting system by means of a control situated
outside the protected space or adjacent to the main exit from the space.
In addition to any means of automatic operation, the system shall be provided with the following:
a) one or more means, remote from the containers, of manual operation;
b) a manual device for providing direct mechanical actuation of the system; or
c) an electrical manual release system in which the control equipment monitors for abnormal conditions
in the power supply and provides a signal when the power source is inadequate.
Manual operation shall cause simultaneous operation of the appropriate automatically operated valves
for CO2 release and distribution.
The manual operation device shall incorporate a double action or other safety device to restrict accidental
operation. The device shall be provided with a means of preventing operation during maintenance of the
system.
NOTE The choice of means of operation will depend on the nature of the hazard to be protected. Automatic fire detection and alarm
equipment will normally be provided on a manual system to indicate the presence of a fire.
Mechanical manual devices that cause direct release of gas shall not be positioned inside the protected
area.
COMMENTARY AND RECOMMENDATIONS ON 14.1. Manual controls should be located so as to be conveniently
and easily accessible at all times, including at the time of fire, and should preferably be outside the protected
space.
Emergency manual operation of individual system components is usually by manual direct operation of the
device to be operated.
14.2 Automatic operation
14.2.1 Automatic systems shall be controlled by appropriate automatic fire detection and release devices
selected according to the requirements of the particular hazard.
COMMENTARY AND RECOMMENDATIONS ON 14.2.1. Electrically, pneumatically or mechanically operated
devices may be used.
14.2.2 Electrically operated devices shall conform to BS 7273-1.
The power supply shall be independent of the supply for the hazardous area. Where this is not practicable,
pneumatic or mechanical devices shall be used, or the system shall be provided with emergency secondary
power supplies with automatic changeover in case the primary supply fails.
14.2.3 Mechanical or pneumatically operated devices shall conform to BS 7273-2.
28 BSI 07-2001
BS 5306-4:2001
14.2.4 Where two or more rapid response fire detectors, such as those for detecting smoke or flame are used,
the system shall be designed to operate only after two separate fire signals have been initiated.
14.2.5 Automatic operation shall cause the system alarm and the house fire alarm to operate.
15 Safety precautions
15.1 General
Suitable safeguards shall be provided to protect persons in areas where the atmosphere may be made
hazardous by the leakage or discharge, either planned or accidental, of carbon dioxide from a fire
extinguishing system (see 15.9).
15.2 Total flooding systems
15.2.1 Safety precautions for total flooding systems
Safety precautions for total flooding systems shall be in accordance with Table 6.
Table 6 Safety precautions for total flooding systems
Occupancy Door lock Automatic/manual Manual Auto System status System isolated
changeover changeover valve (3) valve (4) unit (5) lamps (6)
switch (1) switch (2)
Normally
occupied Yes Yes Yes or (4) Yes or (3) Yes Yes
Not
normally
occupied Recommended Yes or (3) Yes or (2) Optional Yes Optional
Door lock changeover switch (1) shall include an internal escape override. A contacted keep as opposed to
a contacted lock shall be used.
Manual valve (3) is a monitored manual only valve sited in the supply line from the carbon dioxide
containers.
Automatic valve (4) is a monitored normally closed valve sited in the supply line from the carbon dioxide
containers, that will open only on receipt of a signal from the detection system or manual release system.
A means of manually operating the valve shall be provided. A means of isolating the valve shall be
provided.
The relevant authority shall be consulted as to the most appropriate valve to be used on any project.
15.2.2 Areas normally occupied
The automatic discharge of the system shall be prevented when persons are or may be present within the
protected space or any adjacent area that could be rendered hazardous by discharge of the gas
(see Table 6). Provision shall be made for the manual operation of the fire extinguishing system by means
of a control situated outside the protected space or adjacent to the main exit from the space.
While the connection between the fire detection system and the gas release is interrupted, the operation of
the fire detector shall activate the fire alarm.
Entry into a protected space shall normally only be made when the total flooding system has been placed
under manual control.
The system shall not be returned to fully automatic control until all persons have left the space.
15.2.3 Areas not normally occupied but which may be entered
Safety requirements for areas not normally occupied but which may be entered shall be in accordance
with Table 6.
During periods of entry the automatic discharge of carbon dioxide shall be prevented. The system shall be
returned to automatic control as soon as all persons have left the space.
BSI 07-2001 29
BS 5306-4:2001
30 BSI 07-2001
BS 5306-4:2001
15.4.4 Odorizers
To enable CO2 to be detected during and following a discharge an odorizer shall be provided.
COMMENTARY AND RECOMMENDATIONS ON 15.4.4. Whilst odorizers provide an indication of CO2 during or
following a discharge, consideration should be given to the provision of CO2 detection to detect slow leakage
into the protected area or at the container location.
15.5 Confined spaces
As entry into confined spaces poses additional hazards because of restrictions on freedom of movement,
ventilation and on escape or rescue, before entry into floor or ceiling voids, ducts, process vessels or
similarly confined spaces that are protected by a gas flooding system, the operation of the system shall be
prevented as in 15.4.2.
COMMENTARY AND RECOMMENDATIONS ON 15.5. Entry into confined spaces for any purpose should be
controlled by a permit-to-work system. Provision should be made for ensuring that the atmosphere within
the space is safe for entry and will remain so for the duration of entry. In cases where effective ventilation
cannot be ensured, the permit should specify the respiratory protective equipment to be used and any other
special precautions to be observed to ensure safe working conditions.
Attention is drawn to the Factories Act 1961, Section 30 [2].
15.6 Warning signs
Appropriate signs, as illustrated in Figure 3 or Figure 4, shall be prominently displayed at each manual
control point (Figure 3) and at each entrance (Figure 4) to the area protected by the system.
15.7 Exits
Adequate means of egress from a protected space shall be provided. Doors at exits shall open outwards and
shall be self-closing. All exit doors shall open readily from the inside and any that have to be secured shall
be fitted with panic bolts or latches.
COMMENTARY AND RECOMMENDATIONS ON 15.7. These requirements are in addition to any imposed under the
Fire Precautions Act 1971 [3].
The means of egress from a protected space should be kept clear at all times.
15.8 Manual hose reels
A notice with the wording Only for use by trained personnel shall be mounted on or adjacent to manual
hose reels.
COMMENTARY AND RECOMMENDATIONS ON 15.8. The use of manual hose reels for the application of carbon
dioxide may present a hazard to personnel. This method of fire control should be used only by trained
personnel who have been adequately instructed and trained in the use of the equipment and in the safety
precautions to be adopted. All persons other than those fighting the fire should be evacuated prior to the use
of manual hose reels. Particular precautions are required where ventilation is restricted, in order to guard
against hazards that may arise from the fire or the extinguishing medium. The provision of self-contained
breathing apparatus for trained personnel should be considered.
BSI 07-2001 31
BS 5306-4:2001
Dimensions in millimetres
CO2 RELEASE
Manual
Control Point
White background
Red background
C0
210
2 Red letters
CAUTION !
Ensure all
personnel are Black background
evacuated
before Red letters
releasing C0 2
75
32 BSI 07-2001
BS 5306-4:2001
Dimensions in millimetres
Yellow background
CAUTION !
White background
Do NOT enter unless
automatic release
is isolated
Black letters
C0
210
2 When alarm sounds
evacuate hazard area
After CO 2 discharge
Black background do NOT re-enter until
thoroughly ventilated
210
BSI 07-2001 33
BS 5306-4:2001
COMMENTARY AND RECOMMENDATIONS ON CLAUSE 16. Carbon dioxide obtained by converting dry ice to
liquid will not usually conform to these requirements unless it has been processed to remove excess oil and
waste.
17 Quantity of carbon dioxide
17.1 In a high pressure system, the amount of carbon dioxide in the system shall be sufficient for the largest
single hazard to be protected, or group of hazards to be protected simultaneously, and shall be determined
as specified in clause 10, clause 11 and clause 12.
17.2 In a low pressure system, to compensate for possible variations in filling or discharge tolerances and
gas residues, the amount of carbon dioxide in the system shall be increased by at least 10 % over the
amount sufficient for the largest single hazard to be protected, or group of hazards to be protected
simultaneously determined as specified in clauses 10, clause 11 and clause 12. In addition, for low pressure
installations, the equivalent quantity of carbon dioxide that may remain liquid in the piping between the
storage container and the nozzle pipework after completion of the designed discharge period shall be
calculated and added to the required quantity of carbon dioxide.
17.3 Where more than one zone is protected by one battery of containers by means of distribution valves,
or in other situations where there may be a need to recharge the plant quickly, consideration shall be given
to the provision of additional reserve containers which may be free-standing spares or be permanently
connected to the fixed piping system. In either case the containers supplied shall be equal in quantity to
the initial bank.
COMMENTARY AND RECOMMENDATIONS ON CLAUSE 17. The determined quantity of carbon dioxide required
for fixed fire extinguishing installations should be available at all times and not be used for other purposes
including manual hose reel systems.
18 Storage containers
18.1 Storage conditions
18.1.1 Arrangements shall be made for container and valve assemblies and accessories to be accessible for
inspection, testing and other maintenance when required.
18.1.2 Containers shall be adequately mounted and suitably supported according to the systems
installation manual so as to provide for convenient individual servicing of the container and its contents.
18.1.3 Containers shall be located as near as practical to the enclosure they protect, preferably outside the
enclosure.
NOTE Containers can be located within the enclosure only if sited so as to minimize the risk of exposure to fire and explosion.
18.1.4 Storage containers shall not be located so as to be subject to severe weather conditions or to potential
damage due to mechanical, chemical, or other causes. Where potentially damaging exposures or
unauthorized interference are likely, suitable enclosures or guards shall be provided.
NOTE Direct sunlight has the potential to increase the container temperature above that of the surrounding atmospheric
temperature.
18.1.5 Each container shall be connected to the manifold via a non-return valve to enable individual
containers to be removed from the system without interruption of the general protection.
18.1.6 The containers shall be secured against reaction when the carbon dioxide is discharged.
34 BSI 07-2001
BS 5306-4:2001
18.1.7 The general ambient storage temperatures shall not exceed the following limits unless the system
is designed for proper operation with storage temperatures outside the appropriate range:
a) for total flooding systems: not more than 55 C or less than 18 C;
b) for local application systems: not more than 46 C or less than 0 C.
COMMENTARY AND RECOMMENDATIONS ON 18.1.7. External heating or cooling may be used to keep the
temperature within the range.
18.1.8 Safeguards shall be employed to prevent inadvertent single action operation of the manual container
release mechanism.
18.2 High pressure storage
18.2.1 The carbon dioxide shall be stored in rechargeable containers designed, constructed, tested and
marked in accordance with BS EN 1964-1 or BS EN 1964-3 as appropriate.
18.2.2 Filling ratios in accordance with BS 5355 shall be used.
18.2.3 Each container or container valve shall be provided with a bursting disc that conforms to BS 2915
and that will operate at a pressure of 190 bar 5 %, to vent the container.
18.2.4 Carbon dioxide containers for fire fighting purposes shall be painted signal red in accordance with
reference 537 of BS 381C:1996 or reference 04E53 of BS 4800:1989.
18.2.5 All containers in any one battery shall be of the same size and contain the same mass of carbon
dioxide.
18.3 Low pressure storage
18.3.1 The container shall be designed to maintain carbon dioxide at a nominal temperature of 18 C,
corresponding to a pressure of 20.7 bar.
18.3.2 The pressure vessel shall be designed, constructed, tested and certified in accordance with PD 5500
or the relevant part of PD 6550. The vessel shall be tested before leaving the manufacturers works by an
approved authority, and a test certificate shall be provided for the client.
18.3.3 The pressure vessels shall be equipped with a refrigeration system capable of maintaining the
maximum contents of the vessel at a temperature of 18 C, taking into account the adverse effect of the
maximum ambient temperature likely to be encountered on any particular location.
COMMENTARY AND RECOMMENDATIONS ON 18.3.3. The refrigerator should preferably be air cooled and should
be provided with the monitoring facilities shown in Table 8.
Table 8 Monitoring facilities
Switching condition Operating pressure
bar
Low pressure, warning on 18
Low pressure, warning off 19
High pressure, warning on 22
High pressure, warning off 21
18.3.4 The audible warning connected with refrigeration monitoring shall not be connected to the electrical
circuit supplying the refrigerator.
18.3.5 Where the servicing of a refrigerator cannot be provided in less than 36 h, a complete duplicate
refrigerator with changeover switching shall be provided.
BSI 07-2001 35
BS 5306-4:2001
18.3.6 A device shall be provided to indicate the carbon dioxide content in the vessel.
COMMENTARY AND RECOMMENDATIONS ON 18.3.6. For this purpose, the vessel may be placed on a weighing
machine or be equipped with an automatic contents indicator. Where electrically operated indicators are
provided, a monitored system should be used. Consideration should be given to the provision of alarm
contacts on the contents gauge or weighing machine to give audible warning that it is necessary to recharge
the vessel.
18.3.7 Each pressure vessel of less than 20 t capacity shall be equipped with at least two relief valves set
to relieve pressure at 24 bar.
The relief valves shall be mounted in pairs on a two-way changeover valve arranged to ensure that one
relief valve always provides protection against excessive pressure within the vessel. It shall not be possible
for the two-way changeover valve to isolate both relief valves at the same time.
Vessels over 20 t capacity shall be provided with four relief valves arranged in pairs, set to relieve pressure
at 24 bar, each pair to be provided with a changeover valve.
Extended balance and filling lines should also be fitted with relief devices.
Relief valves shall be fitted so that the discharge, in the event of operation, will not injure or endanger
personnel. If necessary, the discharge shall be piped to an area where it will not become a hazard.
The location of the vessel shall be such that there is always sufficient ventilation to permit the refrigerator
to function satisfactorily. If the vessel is located within a closed space, pressure-relieving devices shall be
piped to atmosphere. In extremely cold locations where it is possible for the carbon dioxide to cool below a
temperature of 24 C, heating equipment shall be provided to maintain the temperature of the vessel
contents within the limits already specified.
COMMENTARY AND RECOMMENDATIONS ON 18.3.7. Recharging with carbon dioxide following a discharge
should be possible within 36 h. Otherwise increased capacity or a reserve tank should be provided.
Carbon dioxide supplied from a mobile tanker at a temperature significantly lower than that found within
the vessel is likely to cause over-filling of the vessel at normal operating temperatures and thus cause the
relief devices to operate.
19 Pipework
19.1 General
Pipework shall be non-combustible and able to withstand the expected pressures and temperatures
without damage.
Threaded steel pipework and fittings, except those conforming to BS 3799, shall be galvanized inside and
out.
NOTE 1 Copper, copper alloy or stainless steel tube may be used without additional protection against corrosion.
Pipes and fittings shall be free of burrs, spelter and rust. Stainless steel, copper and copper alloy pipe and
fittings for high pressure and low pressure systems shall conform to BS 3605-2 and BS EN 12449
(see note 2). Other steel pipe and fittings shall be as given in Table 9, Table 10, Table 11 and Table 12.
NOTE 2 The grade of stainless steel, copper and copper alloy should be chosen in consultation with the manufacturer with regard
to the duty to be performed.
For high pressure systems, container and valve manifolds shall be hydraulically tested at the
manufacturers works to a minimum pressure of 190 bar. For low pressure systems container and valve
manifolds shall be hydraulically tested to a minimum pressure of 33 bar. The installer shall provide for the
issue of a test certificate.
19.2 Flanges
19.2.1 High pressure systems
[Link] For closed sections of pipework, flanges shall be of forged carbon steel, raised face, conforming to
class 900 of ANSI B16.5:1996.
[Link] For open sections of pipe, flanges shall be of forged carbon steel, raised face, conforming to
class 300 of ANSI B16.5:1996.
36 BSI 07-2001
BS 5306-4:2001
BSI 07-2001 37
BS 5306-4:2001
38 BSI 07-2001
BS 5306-4:2001
19.5 Fittings
19.5.1 High pressure systems
Fittings for high pressure systems shall be in accordance with Table 11.
Table 11 Pipe fittings for closed and open ended pipework section High pressure systems
Nominal pipe size Type of fitting Grade or Material Conforms to
Closed sections of pipework
Up to and including 40 mm Forged steel, screwed, 3 000 lb WPA or WPB BS 3799:1974
ASTM A105N ANSI B16.11:1996
Wrought steel, butt welded WPA or WPB BS 1640-3:1968
All sizes up to 150 mm Forged steel, socket welded, 3 000 lb WPA or WPB BS 3799:1974
ASTM A105N ANSI B16.11:1996
Open sections of pipework
Up to and including 20 mm Screwed fittings Malleable iron BSEN10242:1995a
Up to and including 40 mm Screwed fittings Wrought steel BSEN10241:2000
Wrought steel, butt welded WPA or WPB BS 1640-3:1968
All sizes up to 150 mm Forged steel, screwed, 3 000 lb WPA or WPB BS 3799:1974
ASTM A105N ANSI B16.11:1996
Forged steel, socket welded, 3 000 lb WPA or WPB BS 3799:1974
ASTM A105N ANSI B16.11:1996
a Fittings conforming to BS EN 10242 may be used on open section pipework greater than 20 mm provided that they are suitably
certified by the manufacturer for the anticipated pressure.
BSI 07-2001 39
BS 5306-4:2001
40 BSI 07-2001
BS 5306-4:2001
COMMENTARY AND RECOMMENDATIONS ON 20.3. Additional supports should be provided where there are
extra loads, such as valves. If the pipework is located in a potentially explosive risk area, the piping system
should be hung from supports that are least likely to be displaced.
20.4 Pipe anchors
Anchors used in low pressure systems shall be designed for the working temperature and be able to
withstand the dynamic and static forces involved.
COMMENTARY AND RECOMMENDATIONS ON 20.4. Care should be taken to ensure that the anchor bolts, and the
supporting structure to which the anchor points are fixed, are adequate to take the proposed load.
20.5 Welding of pipework
Welding shall conform to BS 2633 or BS 4677 for metal arc welding or, as appropriate, with BS 1821 for
oxyacetylene welding except as modified by 20.12.
COMMENTARY AND RECOMMENDATIONS ON 20.5. Where welding is carried out in the vicinity of valves fitted
with seats and seals that can be damaged by heat from the weld, the seats and seals should be removed
during the welding operation.
20.6 Pressure relief devices
Where there is a possibility of liquid carbon dioxide entrapment in pipework (as, for example, between
valves) a suitable excess pressure relief device shall be fitted. For low pressure systems the devices shall
be designed to operate at 24 bar 5 %. For high pressure systems the device shall be designed to operate
at 150 bar 5 %.
In a low pressure system, if excess pressure relief is provided through a relief valve, this valve shall be
fitted at the top of a vertical standpipe of not less than 300 mm length to ensure that it is not in contact
with liquid carbon dioxide.
COMMENTARY AND RECOMMENDATIONS ON 20.6. Safety relief devices should be fitted so that the discharge, in
the event of operation, will not injure or endanger personnel and, if necessary, the discharge should be pipes
to an area where it will not become a hazard to personnel.
20.7 Distribution valves
If several risks are protected separately but connected to one carbon dioxide supply source, a distribution
valve shall be provided for each risk. Distribution valves shall be capable of being opened when subjected
to the maximum carbon dioxide pressure. Valves shall be equipped so that they can be opened manually.
All valves shall be designed for the intended use, particularly in respect of flow capacity and operation.
Valves shall be rated for equivalent length in terms of the pipe or tubing sizes with which they will be used.
They shall only be used in accordance with the manufacturers instructions relating to temperature and
other limitations.
BSI 07-2001 41
BS 5306-4:2001
Valves used in high pressure systems and those that are constantly under pressure shall be designed for a
working pressure of 126 bar. The 126 bar working pressure is based on the developed pressure of CO2 at
50 C and on a filling density of 0.667 kg/l.
Valves used in low pressure systems shall be designed for a working pressure of 24 bar.
20.8 Discharge nozzles
Discharge nozzles shall be manufactured in corrosion-resistant material and be of adequate strength to
withstand expected working temperatures and pressures.
Discharge nozzles shall be permanently marked with the appropriate orifice code number (see Annex E) to
show the equivalent single orifice diameter. The markings shall be readily discernible after installation.
Discharge nozzles shall be provided with frangible discs or blow-out caps where clogging by foreign
materials is likely. These devices shall provide an unobstructed opening upon system operation.
COMMENTARY AND RECOMMENDATIONS ON 20.8. The discharge nozzle normally consists of the selected orifice
and any associated shield or baffle. As the size of the nozzle decreases, so the risk of blockage by dirt
increases, and care should be taken to use suitable filters.
20.9 Carbon dioxide pipe and orifice size determination
The design of the piping distribution system shall be based on the flow rate desired at each nozzle.
COMMENTARY AND RECOMMENDATIONS ON 20.9. The problem of computing pipe sizes for carbon dioxide
systems is complicated by the fact that the pressure drop is non-linear with respect to the pipeline.
The flow rate desired at each nozzle will determine the required flow rate in the branch lines and the main
pipeline. From practical experience, it is possible to estimate the approximate pipe sizes required. The
pressure at each nozzle can then be determined from suitable flow curves.
The equations on which flow curves are based, together with derived tables and figures and a detailed
discussion of their application, are given in Annex E. Use should be made of these data in the determination
of orifice sizes and other details of piping systems.
20.10 Electrical earthing
All exposed metalwork in CO2 systems that are housed within electrical substations or switchrooms shall
be efficiently earthed to prevent the metalwork becoming electrically charged.
COMMENTARY AND RECOMMENDATIONS ON 20.10. Adequate earthing of CO2 systems, wherever located, will
minimize the risk of electrostatic discharge. BS 5958-1 gives basic information on earthing practice.
20.11 Electrical hazards
Where exposed electrical conductors are present, clearances no smaller than those given in Table 14 shall
be provided, where practicable, between the electrical conductors and all parts of the CO2 system that may
be approached during maintenance. Where these clearance distances cannot be achieved, warning notices
shall be provided and a safe system of maintenance work shall be adopted.
COMMENTARY AND RECOMMENDATIONS ON 20.11. The system should be arranged so that all normal
operations can be carried out with safety to the operator.
Where CO2 systems are to be installed in substations or switchrooms, reference should be made to Table 14.
42 BSI 07-2001
BS 5306-4:2001
Nominal system Basic electrical Safety working Safety working Insulation height Phase-to-phase
voltage/BIL/SIL clearance clearance clearance (pedestrian clearance
(phase-to-earth) (vertical) (horizontal) access)
KV m m m m m
6.6/75 0.5 2.9 2.3 2.1 0.25
11/95 0.5 2.9 2.3 2.1 0.25
33/170 0.5 2.9 2.3 2.1 0.43
66/325 0.7 3.1 2.5 2.1 0.78
132/550/650 1.1 3.5 2.9 2.1 1.4
275/1 050/850 2.1 4.8 3.9 2.4 2.4
400/1 425/1 050 2.8 5.5 4.6 2.4 3.6
NOTE See notes to Table 3 and BS 7354:1990, 5.3 from which this table is derived.
COMMENTARY AND RECOMMENDATIONS ON 20.12. All welded joints in pipework not under continuous
pressure should be visually inspected.
All taper threaded screw joints should be examined for adequate engagement and tightness.
All flanged connections should be checked for full engagement of the nuts on the bolts and for tightness.
21 Marking of pipework
21.1 All pipework shall be marked in accordance with BS 1710.
COMMENTARY AND RECOMMENDATIONS ON 21.1. Valves and other components with moving parts should not
be painted.
21.2 Where pipework is continuously pressurized with carbon dioxide, it shall be prominently marked at
suitable intervals (of not more than 2 m) with a label or adhesive tape reading PRESSURIZED CO2.
BSI 07-2001 43
BS 5306-4:2001
Annex A (normative)
Door fan test for determination of minimum hold time
A.1 Principle
A fan is temporarily located within an access opening to pressurize and depressurize the enclosure. A series
of pressure and air flow measurements is made from which the leakage characteristics of the enclosure are
established. The predicted hold time is calculated using these leakage characteristics on the following
assumptions:
a) that leakage occurs under the worst conditions, i.e. when one half of the effective leakage area is at
the maximum enclosure height and represents the inward leakage of air, and the other half (the lower
leakage area) of the total equivalent leakage area is at the lowest point in the enclosure and represents
the outward leakage of extinguishant/air;
b) that all leak flow is one-dimensional, i.e. ignoring stream functions;
c) that flow through any particular leak area is either into or out of the enclosure and respectively either
from or into an infinitely large space;
d) that the system is at sea-level, at a temperature of 20 C, and atmospheric pressure is 1,013 bar
absolute.
A.2 Apparatus
A.2.1 Fan unit, consisting of a frame which will fit into and seal an access opening in the enclosure, and
one or more variable speed fans, with low flow facilities, capable of giving a differential pressure of not less
than 25 Pa across the enclosure boundary.
A.2.2 Two pressure measuring devices, one to measure enclosure differential pressure and one to measure
fan flow pressure.
A.2.3 Flexible tubing, for connecting the pressure measuring devices.
A.2.4 Chemical smoke pencils and/or smoke generator.
A.2.5 Two thermometers, to measure ambient temperatures.
A.2.6 Signs, reading DO NOT OPEN PRESSURE TEST IN PROGRESS and DO NOT CLOSE
PRESSURE TEST IN PROGRESS.
NOTE Additional apparatus, such as measuring tapes, torches, ladders, tools to remove floor and ceiling tiles, computer or other
calculating device, may be necessary or convenient.
44 BSI 07-2001
BS 5306-4:2001
BSI 07-2001 45
BS 5306-4:2001
46 BSI 07-2001
BS 5306-4:2001
for pressurization:
1 2 1 2
Pc 20 + 273 T e + 273
Ql = Qf --------------- ----------------------- ----------------------- (A.2)
1.013 T c + 273 T o + 273
where
Pc is the atmospheric pressure during fan caliboration in pascals (Pa);
Ql is the air flow rate, temperature and pressure corrected in cubic metres per second (m3/s);
Qf is the measured air flow rate through the fan in cubic metres per second (m3/s);
Tc is the atmospheric pressure during calibration of the fan unit in degrees celcius (C);
Te is the air temperature inside the enclosure in degrees celcius (C);
To is the air temperature outside the enclosure in degrees celcius (C);
For each set of results (pressurization and depressurization) express the fan test results in the form:
n
Ql = k1 Pf (A.3)
where
k1 is the leakage characteristic [see equation (A.8)] in cubic metres per second pascal to the
power n [m3/(sPan)];
Pf is the differential pressure produced by the fan in pascals (Pa).
and check that the correlation coefficients of each set are not less than 0.99 using the method of least
squares. The two sets will almost always have different values of k1 and n.
A.7.5.2 Density of extinguishant/air mixture
Calculate the density of the extinguishant/air mixture at 20 C at the design concentration using the
equation:
e c a ( 100 c )
mi = ---------- + -----------------------------
100 100 (A.4)
where
c is the design concentration of extinguishant in air for the enclosure in percent volume by
volume (% V/V);
a is the air density (1.205 at 20 C and 1.013 bar) in kilograms per cubic metres (kg/m3);
e is the extinguishant density at 20 C and 1.013 bar atmospheric pressure in kilograms per
cubic metres (kg/m3);
mi is the extinguishant/air mixture density at initial concentration c, 20 C and 1.013 bar
atmospheric pressure in kilograms per cubic metres (kg/m3).
For enclosures with mixing, calculate the density of the extinguishant/air mixture at 20 C at 80 % of the
minimum design concentration using the equation:
e 0.77c min a ( 100 0.77c min )
mf = ----------------------------------- + --------------------------------------------------
100 100 (A.5)
where
cmin is the minimum concentration of extinguishant in air for the enclosure in percent volume
by volume (% V/V);
mf is the extinguishant/air mixture density at the concentration cmin 20 C and 1.013 bar
atmospheric pressure in kilograms per cubic metres (kg/m3).
BSI 07-2001 47
BS 5306-4:2001
Calculate the corresponding extinguishant air column pressure at the base of the enclosure using the
following equation:
P m = g n H o ( mi a ) (A.6)
where
Pm is the CO2/air column pressure in pascals (Pa);
gn is the gravitational acceleration (= 9.81) in metres per second squared (m/s2);
Ho is the overall height of the enclosure in metres (m);
A.7.5.3 Leakage characteristics
Determine the average values of the leakage characteristics k1 and n, as follows:
( 1nQ lm 1nQ lm 2 )
n = ----------------------------------------------------
-
ln2 (A.7)
where
n is the leakage characteristic (dimensionless);
Pmi is the initial CO2/air column pressure in pascals (Pa);
Qlm is the mean value of Ql at Pf = Pm in cubic metres per second (m3/s).
where
k4 is the simplifying constant in Pam3/kg;
Pb is the bias pressure in pascals (Pa).
48 BSI 07-2001
BS 5306-4:2001
n
( n + 1 )/n 1 n
V mi 2g n H o ( m a ) + 2P b ( m a )
t = ---------- ----------------------------------------------------------------------------------------------------------------- d m (A.13)
Fk 2 mf F 1 n
m + a -------------
1 F
Solve the equation by a method of approximation, for example by using Simpsons rule using an even
number (not less than 20) of intervals.
A.7.6 Report
Prepare a written report containing the following information:
a) the enclosure leak flow characteristics (i.e. the average values of k1, and n);
b) the design concentration of extinguishant;
c) the gross volume of the enclosure;
d) the quantity of extinguishant provided;
e) the height of the enclosure;
f) the height of the highest hazard;
g) the predicted minimum hold time and whether or not the value conforms to the requirement of 10.5,
i.e. whether it is less than 20 min or the higher necessary value, as appropriate;
h) the sketch plan used in the evaluation of the enclosure (see clause 5);
i) the current calibration data for the fan unit and the pressure measuring devices, and if available
corresponding certificates;
j) the test results, including a record of the test measurements and any appropriate computer printout.
A.8 Treatment of enclosures with predicted minimum hold times less than the recommended
value
A.8.1 General
If the predicted minimum hold time, calculated in accordance with A.7, is less than as recommended in 10.5
then A.8.3 and A.8.4 shall be implemented in sequence.
A.8.2 Estimation of leakage area
To illustrate the scale of the problem calculate the effective leakage area Ae from the equation:
Q1 a n a n
A e = --------n ------ = k 1 ------ (A.14)
Pf 2 2
It is usually not possible to measure Ae or ko (which will be between 0.61 and 1.00, dependent upon the
geometry of the leakage paths).
BSI 07-2001 49
BS 5306-4:2001
Annex B (informative)
Service schedule
An example of a suitable service schedule is as follows.
a) Every 3 months Test and service all electrical detection and alarm systems.
b) Every 6 months Perform the following checks and inspections.
1) Externally examine pipework to determine its condition. Replace or pressure test and repair as
necessary pipework showing corrosion or mechanical damage.
2) Check all control valves for correct manual function and automatic valves additionally for correct
automatic function.
3) Externally examine containers for signs of damage or unauthorized modification, and for damage to
system hoses.
4) Check contents of pilot containers. Liquefied gas type should be within 10 % and non-liquefied
within 5 % of correct charge. Replace or refill any showing a greater loss.
5) Carbon dioxide containers, check weigh or use a liquid level indicator to verify correct content of
containers. Replace or refill any showing a loss of more than 10 %.
c) Every 12 months Carry out a check of enclosure integrity using the method given in Annex A. If the
measured aggregate area of leakage has increased from that measured during installation which would
adversely affect system performance, carry out work to reduce the leakage.
d) As required by BS 5430, but otherwise when convenient, remove the containers and pressure test
when necessary.
50 BSI 07-2001
BS 5306-4:2001
Annex C (normative)
Determination of carbon dioxide concentrations for flammable liquids and
gases
C.1 Principle
The minimum requirements for determining the flame extinguishing concentration of a gaseous
extinguishant in air for flammable liquids and gases employing the cup burner apparatus are set out.
Diffusion flames of fuels burning in a round reservoir (cup) centrally positioned in a coaxially flowing air
stream are extinguished by addition of a gaseous extinguishant to the air.
C.2 Apparatus
C.2.1 General
The cup burner apparatus for determining the flame extinguishing concentration of a gaseous
extinguishant in air for flammable liquids and gases shall be arranged and constructed as in Figure C.1,
employing the dimensions shown; the tolerance for all dimensions shall be 5 % unless otherwise indicated.
C.2.2 Cup, round, constructed of glass, quartz or steel, having an outside diameter in the range of 28 mm
to 31 mm, with a wall thickness of 12 mm and a 45 chamfer ground into the top edge. The cup shall have
an internal means of temperature measurement of the fuel at a location of 2 mm to 5 mm below its top, and
a means of heating the fuel. A cup intended for use with gaseous fuels shall have a means of attaining a
uniform gas flow at the top of the cup (e.g. the cup may be packed with refractory materials).
C.2.3 Chimney, of round glass or quartz construction, having an inside diameter of 85 mm 2 mm, a wall
thickness of 2 mm to 5 mm and a height of 533 mm.
C.2.4 Diffuser, with a means of fitting to the bottom end of the chimney and a means of admitting a
premixed stream of air and extinguishant. The diffuser shall have a means of uniformly distributing the
air-extinguishant flow across the cross-section of the chimney.
C.2.5 Fuel supply (liquids), capable of delivering liquid fuel to the cup while maintaining a fixed, but
adjustable, liquid level therein.
C.2.6 Fuel supply (gases), capable of delivering the fuel at a controlled and fixed rate to the cup.
C.2.7 Manifold, capable of receiving air and extinguishant and delivering them as a single mixed stream
to the diffuser.
C.2.8 Air supply, for delivering air to the manifold which allows adjustment of the air flow rate and has a
calibrated means of measuring the air flow rate.
C.2.9 Extinguishant supply, for delivering extinguishant to the manifold which allows adjustment of the
extinguishant flow rate and has a calibrated means of measuring the extinguishant flow rate.
C.2.10 Delivery system, capable of delivering a representative and measurable sample of the agent to the
cup burner in gaseous form.
C.3 Materials
C.3.1 Air, clean, dry and oil-free. The oxygen concentration shall be 20.9 0.5 % v/v. The source and oxygen
content of the air employed shall be recorded.
NOTE Air supplied in commercial high-pressure cylinders may have an oxygen content significantly different from 20.9 % v/v.
BSI 07-2001 51
BS 5306-4:2001
C.4.3 Operate the heating arrangement for the cup to bring the fuel temperature to (25 1) C or to
(5 1) C above the open cup flash point, whichever is higher.
C.4.4 Adjust the air flow to achieve a flow rate of 10 l/min.
C.4.5 Ignite the fuel.
C.4.6 Allow the fuel to burn for a period of 90 s to 120 s before beginning the flow of the extinguishant.
During this period, adjust the liquid level in the cup so that the fuel level is at the top of the cup.
C.4.7 Begin the flow of extinguishant. Increase the extinguishant flow rate in increments until flame
extinguishment occurs, and record the extinguishant and air flow rates at extinguishment.
NOTE 1 The flow rate increment should result in an increase in the flow rate of no more than 2 % of the previous value.
Adjustments in the extinguishant flow rate shall be followed by a brief waiting period (10 s) to allow the
new proportions of extinguishant and air in the manifold to reach the cup position. During this procedure,
the liquid level in the cup shall be maintained at the top of the cup.
NOTE 2 On an initial run it is convenient to employ relatively large flow increments to ascertain the approximate extinguishant
flow required for extinguishment, and on subsequent runs to start at a flow rate close to the critical and to increase the flow by small
amounts until extinguishment is achieved.
C.4.8 Determine the extinguishing concentration of the extinguishant in accordance with C.6.
C.4.9 Prior to subsequent tests remove the fuel from the cup and remove any deposits of residue or soot
that may be present on the cup.
C.4.10 Repeat C.4.1 to C.4.9 employing air flow rates of 20, 30, 40 and 50 l/min.
C.4.11 Determine the plateau region in the extinguishing concentration/air flow plot (i.e. the range of air
flows over which the extinguishing concentration is at a maximum and is independent of the air flow) by
plotting the extinguishing concentration as determined in C.6 versus the air flow rate.
C.4.12 Place the flammable liquid in the fuel supply reservoir.
C.4.13 Admit fuel to the cup adjusting the liquid level to within 5 mm to 10 mm of the top of the cup.
C.4.14 Operate the heating arrangement for the cup to bring the fuel temperature to (25 1) C above the
open cup flash point, whichever is higher.
C.4.15 Adjust the air flow to achieve a flow rate which is on the plateau region determined in accordance
with C.4.11.
C.4.16 Ignite the fuel.
C.4.17 Allow the fuel to burn for a period of 60 s to 120 s before beginning flow of extinguishant. During
this period, adjust the liquid level in the cup so that the fuel level is at the top of the cup.
C.4.18 Begin the flow of extinguishant. Increase the extinguishant flow rate in increments until flame
extinguishment occurs, and record the extinguishant and air flow rates at extinguishment.
NOTE 1 The flow rate increment should result in an increase in the flow rate of no more than 2 % of the previous flow rate.
Adjustments in the extinguishant flow rate shall be followed by a brief waiting period (10 s) to allow the
new proportions of extinguishant and air in the manifold to reach the cup position.
NOTE 2 On an initial run it is convenient to employ relatively large flow increments to ascertain the approximate extinguishant
flow required for extinguishment, and on subsequent runs to start at a flow rate close to the critical and to increase the flow by small
amounts until extinguishment is achieved.
C.4.19 Prior to subsequent tests remove the fuel from the cup and remove any deposits of residue or soot
that may be present on the cup.
C.4.20 Determine the extinguishing concentration of the extinguishant for the case of unheated fuel in
accordance with C.7 by establishing the average of five tests.
C.4.21 Repeat steps C.4.11 to C.4.19 with the fuel temperature at 5 C below the boiling point of the fuel,
or 200 C, whichever is lower.
C.4.22 Determine the extinguishing concentration of the extinguishant for the case of heated fuel in
accordance with C.7 by establishing the average of five tests.
52 BSI 07-2001
BS 5306-4:2001
C.5.7 Upon flame extinguishment shut off the flow of flammable gas.
C.5.8 Prior to subsequent tests remove deposits of residue or soot if present on the cup.
C.5.9 Determine the extinguishing concentration of the extinguishant in accordance with C.6.
C.5.10 Repeat steps C.5.3 to C.5.8 at air flow rates of 20, 30, 40 and 50 l/min.
C.5.11 Determine the plateau region in the extinguishing concentration/air flow plot (i.e. the range of air
flows over which the extinguishing concentration is at a maximum and is independent of the air flow) by
plotting the extinguishing concentration as determined in C.5.9 versus the air flow rate.
C.5.12 Adjust the air flow rate to a value on the plateau in the extinguishing concentration/air flow plot.
C.5.13 Begin fuel flow to the cup and adjust the flow rate to attain a gas velocity nominally equal to the air
velocity past the cup.
C.5.14 Ignite the fuel.
C.5.15 Allow the fuel to burn for a period of 60 s before beginning flow of extinguishant.
C.5.16 Begin the flow of extinguishant. Increase the extinguishant flow rate in increments until flame
extinguishment occurs, and record the air, extinguishant and fuel flow rates at extinguishment.
NOTE 1 The extinguishant flow rate increment should result in an increase in the flow rate of no more than 2 % absolute.
Adjustments in the extinguishant flow rate are to be followed by a brief waiting period (10 s) to allow the
new proportions of extinguishant and air in the manifold to reach the cup position.
NOTE 2 On an initial run it is convenient to employ relatively large flow increments to ascertain the approximate extinguishant
flow required for extinguishment, and on subsequent runs to start at a flow rate close to the critical and to increase the flow by small
amounts until extinguishment is achieved.
C.5.17 Upon flame extinguishment shut off the flow of flammable gas.
C.5.18 Prior to the subsequent tests remove deposits of residue or soot if present on the cup.
C.5.19 Determine the extinguishing concentration of the extinguishant for the case of unheated fuel in
accordance with C.7 by establishing the average of five tests.
C.5.20 Repeat steps C.5.12, C.5.13, C.5.14, C.5.15, C.5.16, C.5.17 and C.5.18 with the fuel temperature
adjusted to 150 C.
C.5.21 Determine the extinguishing concentration of the extinguishant for the case of heated fuel in
accordance with C.7 by establishing the average of five tests.
BSI 07-2001 53
BS 5306-4:2001
54 BSI 07-2001
BSI 07-2001
Dimensions in millimetres
85 31
Heating wire
between inner
25
and outer walls
70
Thermocouple
tube
252
12
235
Levelling jack
330
Heater
terminal
36
90
Air Carbon
BS 5306-4:2001
dioxide
75
10
Annex D (informative)
Examples of calculation of carbon dioxide requirements
D.1 Total flooding systems
The following are examples of the calculation of carbon dioxide requirements for total flooding systems.
EXAMPLE 1
Volume of space 60 m3
Type of combustible Petroleum spirit
Openings 0.5 m2 at 1 m below ceiling
CO2 concentration (see Table 2) 34 %
Volume factor (see Table 1) 0.9 m3/kg
Basic quantity CO2 60 0.9 = 54 kg
Material conversion factor (see Table 2) 1.0 (therefore no conversion required)
Additional CO2 for openings 58 0.5 = 29 kg
Total CO2 required 54 + 29 = 83 kg
EXAMPLE 2
Volume of space 300 m3
Type of combustible Ethylene oxide
Openings 1 m2 at 1 m below ceiling
CO2 concentration (see Table 2) 53 %
Volume factor (see Table 1) 0.8 m3/kg
Basic quantity CO2 300 0.8 = 240 kg
Material conversion factor (see Table 2) 1.75
Converted quantity of CO2 1.75 240 = 420 kg
Additional CO2 for openings 1.75 110 1 = 193 kg
Total CO2 required 420 + 193 = 613 kg
1) The assumed walls and ceiling of the enclosure should be at least 0.6 m from the main hazard unless actual walls are
involved, and should enclose all areas of possible leakage, splashing or spillage.
56 BSI 07-2001
BS 5306-4:2001
6.1
= ----------- 100 71 %
8.54
Discharge rate for 71 % enclosure:
= 42) + {(1 0.71) (16 4)}2)
= 7.48 (kg/min)/m3
Discharge rate:
= 12.63 7.48
= 94.47 kg/min
Carbon dioxide requirement:
= 94.47 0.5 1.4
= 66.13 kg
[0.5 represents 0.5 min discharge. 1.4 allows for the vapour (see 11.3.2)]
EXAMPLE 2
Hazard: printer with four sides and top open (no continuous solid walls; material conversion factor = 1).
Dimensions:
width: 1.22 m
length: 1.52 m
height: 1.22 m
Assumed volume:
= (1.22 + 0.62) + 0.62)) (1.52 + 0.6 + 0.6) (1.22 + 0.6)
= 11.98 m3
Percent perimeter enclosed = 0 %
Discharge rate for 0 % enclosure = 16 (kg/min)/m3 3)
Discharge rate = 11.98 16 = 191.7 kg/min
Carbon dioxide requirement:
= 191.7 0.5 1.4
= 134.2 kg
[0.5 represents 0.5 min discharge; 1.4 allows for the vapour (see 11.3.2)]
Annex E (informative)
Determination of carbon dioxide pipe and orifice size
E.1 General
Computer programs are generally used to perform calculations to determine pipework pressures and to
calculate nozzle orifice sizes. The calculation program should be based on the parameters contained in this
annex.
E.2 Pressure drop in the pipeline
The following equation or derived curves may be used to determine the pressure drop in the pipeline:
5 5.25
2 10 0.872 5 ( D Y)
Q = ---------------------------------------------------------------
1.25
L + 0.043 19 ( D Z)
where
Q is the flow rate in kilograms per minute (kg/min);
D is the inside pipe diameter (actual) in millimetres (mm);
2) The assumed walls and ceiling of the enclosure should be at least 0.6 m from the main hazard unless actual walls are involved,
BSI 07-2001 57
BS 5306-4:2001
where
P1 is the storage pressure in bar;
P is the pressure at the end of pipe line in bar;
i is the density at pressure P1 in kilograms per cubic metre (kg/m3);
ln is the natural logarithm
In the design of piping systems, pressure drop values can best be obtained for curves of pressure versus
equivalent length for various flow rates and pipe sizes.
E.3 Values of Y and Z
The storage pressure is an important factor in carbon dioxide flow. In low pressure storage the starting
pressure in the storage vessel will drop by an amount depending on whether all or only part of the supply
is discharged. Because of this, it will be about 19.7 bar. The flow equation is based on absolute pressure,
therefore 20.7 bar is used for calculations necessary for low pressure systems.
In high pressure systems the storage pressure depends on ambient temperature. Normal ambient
temperature is assumed to be 21 C. At this temperature, the average pressure in the cylinder during
discharge of the liquid portion will be approximately 51.7 bar. This pressure is used for calculations
involving high pressure systems.
Using the above base pressures of 20.7 bar and 51.7 bar, values have been determined for the Y and Z
factors in the flow equation. These are given in Table E.1 and Table E.2.
Table E.1 Values of Y and Z
Pressure Y factor, in (barkg)/m3, for a pressure, in bar Z
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
bar (barkg)/m3
58 BSI 07-2001
BS 5306-4:2001
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
bar (barkg)m3
BSI 07-2001 59
BS 5306-4:2001
Q 454 2
------- = --------------- = 0.165 ( kg/min )/mm
D
2 2 758
L 152 1.25
-------------- = --------------- = 1.075 m/mm
D
1.25 141.3
Starting pressure is 20.7 bar and L/D1.25 = 0, shown on Figure E.1 at S1. The terminal pressure is found
to be about 15.7 bar at point T1 where the Q/D2 value of 0.165 intersects the L/D1.25 value of 1.075.
If this line terminates in a single nozzle, the equivalent orifice area should be matched to the terminal
pressure in order to control the flow rate at the desired level of 454 kg/min.
Referring to Table E.3, it will be noted that the discharge rate will be 0.991 3 (kg/min)/mm2 of equivalent
orifice area when the orifice pressure is 15.9 bar. The required equivalent orifice area of the nozzle is thus
equal to the total flow rate divided by the rate per square millimetre.
From Figure E.1 the starting pressure of 15.7 bar (terminal pressure of main line) intersects the Q/D2
line 0.136 at point S2 giving an L/D1.25 value of 1.6. The terminal pressure is found by moving down the
Q/D2 line a distance of 0.59 on the L/D1.25 scale, i.e. L/D1/25 = 1.60 + 0.59 = 2.19, to the point T2 where
terminal pressure is 11.4 bar. With this new terminal pressure and flow rate of 227 kg/min the required
nozzle area at the end of each branch line is obtained from Table E.3 and is approximately 368 mm2.
It should be noted that this is only slightly less than the single large nozzle example, but that the discharge
rate is halved by the reduced pressure.
60 BSI 07-2001
BS 5306-4:2001
S1
20.7
20
19 Q
/D 2
=0
18 .07
(kg
0.0 /m
17 8 in)
/m
Pressure (bar)
m 2
T1 S2
0.0
16
0.1
9
0
0.1
2
15
0.14
0.16
0.18
0.20
14
0.25
0.30
0.40
0.50
13
T2
12
11
10
9
8
0 0.5 1 2 3 4 5 6 7 8
L 1 25 1 25
/D (m / mm )
Figure E.1 Pressure drop in pipeline for 20.7 bar storage pressure
BSI 07-2001 61
BS 5306-4:2001
51.7
Q
50 /D 2=
0.07
(kg/m
in)/ m
m2
0.0
8
0.0
45 9
0.1
Pressure (bar)
0.1
40 2
0.1
4
0.1
0.1
6
35
0.2
0.25
0.30
8
0.35
0
0.40
0.45
0.50
30
25
20
15
0 0.5 1 2 3 4 5 6 7 8
L 1 25 1 25
/D (m / mm )
Figure E.2 Pressure drop in pipeline for 51.7 bar storage pressure
62 BSI 07-2001
BS 5306-4:2001
Correction factors are given in Table E.6 and Table E.7 for low pressure and high pressure systems
respectively. The correction is subtracted from the terminal pressure when the flow is upward and added
to the terminal pressure when the flow is upward and added to the terminal when the flow is downward.
The terminal pressure at the outlet having been determined, appropriately sized nozzles can be selected.
For low pressure systems the discharge rate through equivalent orifices should be based on the values
given in Table E.3. Design nozzle pressures should be not less than 10 bar.
For high pressure systems, the discharge rate through equivalent orifices should be based on the values
given in Table E.8. Design nozzle pressures at 21 C storage should be not less than 20 bar.
E.9 Calculation of equilibrium in low pressure systems
In high pressure systems the delay in achieving equilibrium flow will generally be insignificant. In low
pressure systems the delay time and amount of carbon dioxide vaporized in cooling the pipe should be
calculated and the equilibrium flow rate increased accordingly to deliver the desired quantity within the
design time after the start of the discharge. Delay time and mass of carbon dioxide vaporized during this
period may be calculated as follows.
Delay time, Dt, (in s) (low pressure systems):
wcp ( T 1 T 2 ) 16 850V
D t = ----------------------------------- + -----------------------
0.507R R
Mass vaporized (low or high pressure systems):
wcp ( T 1 T 2 )
W = -----------------------------------
H
where:
W is the mass of carbon dioxide vaporized in kilograms (kg);
W is the mass of piping in kilograms (kg);
cp is the specific heat capacity of metal in pipe in kilojoules per kilogram kelvin [kJ/(kgK)]
(0.46 for steel);
T1 is the average pipe temperature before discharge in degrees Celsius (C);
T2 is the average carbon dioxide temperature in degrees Celsius (C);
NOTE Assume 15.6 C for high pressure and 20.6 C for low pressure under normal conditions.
R is the design flow rate in kilograms per minute (kg/min);
V is the volume of piping in cubic metres (m3);
H is the latent heat of vaporization of liquid carbon dioxide in kilojoules per kilogram (kJ/kg)4)
4) Approximately 150.7 kJ/kg for high pressure and approximately 276.3 kJ/kg for low pressure systems.
BSI 07-2001 63
BS 5306-4:2001
Table E.3 Discharge rate of equivalent orifice areaa for low pressure storage (20.7 bar)
Orifice pressure Discharge rate/unit area
bar (kg/min)/mm2
20.7 2.967
20.0 2.039
19.3 1.670
18.6 1.441
17.9 1.283
17.2 1.164
16.5 1.072
15.9 0.991 3
15.2 0.917 5
14.5 0.850 7
13.8 0.791 0
13.1 0.736 8
12.4 0.686 9
11.7 0.641 2
11.0 0.599 0
10.3 0.558 9
9.65 0.521 0
8.96 0.484 4
8.27 0.448 6
7.58 0.414 1
6.89 0.381 1
a Based upon a standard single orifice having a rounded entry with a coefficient of 0.98.
m in m m m m m
10 0.18 0.40 0.24 0.82 0.09
15 0.24 0.52 0.30 1.0 0.12
20 0.30 0.67 0.43 1.4 0.15
25 1 0.40 0.85 0.55 1.7 0.18
32 1 0.52 1.1 0.70 2.3 0.24
40 1 0.61 1.3 0.82 2.7 0.27
50 2 0.79 1.7 1.1 3.41 0.37
65 2 0.94 2.0 1.2 4.08 0.43
80 3 1.2 2.5 1.6 5.06 0.55
100 4 1.5 3.26 2.0 6.64 0.73
125 5 1.9 4.08 2.6 8.35 0.91
150 6 2.3 4.94 3.08 10.0 1.1
64 BSI 07-2001
BS 5306-4:2001
BSI 07-2001 65
BS 5306-4:2001
Table E.8 Discharge rate of equivalent orifice areaa for high pressure storage (51.7 bar)
Orifice pressure Discharge rate/unit area
bar (kg/min)/mm2
51.7 3.255
50.0 2.703
48.3 2.401
46.5 2.172
44.8 1.993
43.1 1.839
41.4 1.705
39.6 1.589
37.9 1.487
36.2 1.396
34.5 1.308
32.8 1.223
31.0 1.139
29.3 1.062
27.6 0.984 3
25.9 0.907 0
24.1 0.829 6
22.4 0.759 3
20.7 0.689 0
17.2 0.548 4
13.8 0.418 3
a Based upon a standard single orifice having a rounded entry with a coefficient of 0.98.
66 BSI 07-2001
BS 5306-4:2001
BSI 07-2001 67
68 blank
BS 5306-4:2001
Bibliography
Standards publications
Other documents
[1] GREAT BRITAIN. Health and Safety at Work etc. Act 1974. London: The Stationery Office.
[2] GREAT BRITAIN. Factories Act 1961, Section 30, London: The Stationery Office.
[3] GREAT BRITAIN. Fire Precautions Act 1971, London: The Stationery Office.
BSI 07-2001 69
BS 5306-4:2001
Revisions
It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using
this British Standard would inform the Secretary of the technical committee
responsible, the identity of which can be found on the inside front cover.
Tel: 020 8996 9000. Fax: 020 8996 7400.
BSI offers members an individual updating service called PLUS which ensures
that subscribers automatically receive the latest editions of standards.
Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel: 020 8996 9001. Fax: 020 8996 7001.
Standards are also available from the BSI website at [Link]
Information on standards
Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the
UK, of the publications of the international standardization bodies. Except as
permitted under the Copyright, Designs and Patents Act 1988 no extract may be
reproduced, stored in a retrieval system or transmitted in any form or by any
means electronic, photocopying, recording or otherwise without prior written
permission from BSI.
This does not preclude the free use, in the course of implementing the standard,
of necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
written permission of BSI must be obtained.









