Residential Occupancy Checklist

This document appears to be a report from the Naguilian Fire Station summarizing an inspection of a residential occupancy. It includes sections providing general information about the building and owner, details of the building construction, classification of occupancy, exit details including the number and location of exits, means of egress, vertical exits like stairs, horizontal exits, ramps if present, and any areas of safe refuge. The inspector checked boxes and provided brief descriptions to document compliance with various fire and building codes regarding the number and specifications of exits, travel distances, doors, stairs, signs, and other life safety features.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
475 views5 pages

Residential Occupancy Checklist

This document appears to be a report from the Naguilian Fire Station summarizing an inspection of a residential occupancy. It includes sections providing general information about the building and owner, details of the building construction, classification of occupancy, exit details including the number and location of exits, means of egress, vertical exits like stairs, horizontal exits, ramps if present, and any areas of safe refuge. The inspector checked boxes and provided brief descriptions to document compliance with various fire and building codes regarding the number and specifications of exits, travel distances, doors, stairs, signs, and other life safety features.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
  • Inspection Details
  • Residential Occupancy Checklist
  • Building Classification and Exit Details
  • Additional Exit and Safety Measures
  • Fire Safety Equipment and Walls
  • Operating Features and Recommendations

Republic of the Philippines

Department of the Interior and Local Government


BUREAU OF FIRE PROTECTION
Region 1
Naguilian Fire Station
(STATION)
Brgy. Ortiz, Naguilian, La Union
(Station Address)

Date: ________________

SUBJECT : Inspection of___________________________________________________________

FOR : CITY/MUNICIPAL FIRE MARSHAL


ATTN: CHIEF, FIRE SAFETY ENFORCEMENT SECTION

REFERENCE: INSPECTION ORDER NO.___________________ DATE ISSUED: __________________

DATE OF INSPECTION: __________________

NATURE OF INSPECTION CONDUCTED: [Check Appropriate Box]


[ ] Building Under Construction [ ] Periodic Inspection of Occupancy
[ ] Application for Occupancy Permit [ ] Verification Inspection of Compliance to NTCV
[ ] Application for Business Permit [ ] Verification Inspection of Complaint Received
[ ] Others (Specify) ________________________________________

RESIDENTIAL OCCUPANCY CHECKLIST

I. GENERAL INFORMATION

Name of Building ___________________________________________________________________________________


Business Name _____________________________________________________________________________________
Address ___________________________________________________________________________________________
Name of Owner/Occupant_______________________________________________ Contact No.___________________
Name of Representative _________________________________________________Contact No. ___________________
No. of Storey ________________ Height of Bldg.___________ m Portion Occupied_____________________________
Area per Flr. _______________________________ sqm Total Flr. Area ____________________________sqm
Building Permit No.____________ Date Issued_________ Occupancy Permit No. ___________ Date Issued__________
Latest FSIC Issued Control No.____________________ Date Issued __________________ FC Fee _________________
Certificate of Fire Drill __________________________Date Issued ___________________FC Fee__________________
Latest Notice to Correct Violations Control No. __________________________ Date Issued ______________________
Name of Fire Insurance Co/Co-Insurer_________________________ Policy No.__________ Date Issued ____________
Latest Mayors/Bus. Permit _____ Date Issued ________ Municipal License No. __________Date Issued ________
Latest Certificate of Electrical Inspection No. _____________________________Date Issued ______________________
Other Information ___________________________________________________________________________________

II. BUILDING CONSTRUCTION

Beams _________________________ Columns______________________ Flooring _____________________________


Exterior Walls ___________________Corridor Walls _________________ Room Partitions_______________________
Main Stair ______________________Windows_____________________ Ceiling _______________________________
Main Door _____________________Trusses________________________ Roof ________________________________

III. SECTIONAL OCCUPANCY (Note: Indicate specific usage of each floor, section or rooms)
__________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
________________________________________________________________________________________
___________________________________________________________________________________
IV. CLASSIFICATION

Occupancy Classification: [ ] Hotel [ ] Apartment [ ] Others______________________________________________


Occupant Load: _______________________ (Requirement: 18.6 square meter per person)
Any renovation: [ ] Yes [ ] No Underground: [ ] Yes [ ] No Windowless: [ ] Yes [ ] No

V. EXIT DETAILS
Capacity of Horizontal Exit (Corridor/Hallway):_____ ( Requirement:100 persons per unit of exit width per min)
Capacity of Exit Stair:__________________________ (Requirement: 75 persons per unit of exit width per min)
No. of Exits ____________________ Remote? [ ] Yes [ ] No
Minimum Requirement: No. of Exits: Two (2) units per floor
Location of Exits _______________________________________________________________________________
Maximum Travel Distance Requirement from Farthest Room: 30 m without AFSS & 46m with AFSS
Any Enclosure Provided? [ ] Yes[ ]No Min of 2-hr fire rating- 4-storey or more, Min of 1 hr fire rating- less than 4-
storey

MEANS OF EGRESS
Readily accessible? [ ] Yes [ ] No Obstructed? [ ] Yes [ ] No
Travel distance within limits? [ ] Yes [ ] No Dead-ends within limits ? [ ] Yes [ ] No
Adequate illumination [ ] Yes [ ] No Proper rating of illumination? [ ] Yes [ ] No
Panic hardware operational? [ ] Yes [ ] No Door swing in the direction of exit? [ ] Yes [ ] No
Doors open easily? [ ] Yes [ ] No Self-closure operational? [ ] Yes [ ] No
Bldg w/ Mezzanine? [ ] Yes [ ] No Mezzanine with proper exits? [ ] Yes [ ] No
Corridors & aisles of sufficient size? [ ] Yes [ ] No

A. VERTICAL EXITS

1. Main stairway: Width ______________Construction _________________________


Are there railings provided? [ ] Yes [ ] No Made of_____________________________________________
Any enclosure provided? [ ] Yes [ ] No Enclosure construction ________________Any opening? [ ] Yes [ ] No
Fire door construction_________________________________ Door equipped w/ Self-closing device? [ ] Yes [ ] No
Door proper rating: [ ] Yes [ ] No Door provided w/ vision panel: [ ] Yes [ ] No If Yes, made of _________________
Door swing in the direction of exit travel (when required)? [ ] Yes [ ] No
Stairways Pressurized? [ ] Yes [ ] No [ ] N/A If pressurized, what type or method? __________________________
Date Last Tested ____________________________________________________________________________________

2. Secondary Stair/Fire Escape: Number______________ Width ______________________


Construction_________________ Are there railings provided? [ ] Yes [ ] No Made of ______________________
Location: [ ] Interior [ ] Exterior Exits accessible? [ ] Yes [ ] No
Any obstruction? [ ] Yes [ ] No Termination/Discharge of Exits __________________________
Any enclosure provided? [ ] Yes [ ] No Enclosure construction ________________________________
Any opening?[ ] Yes [ ] No Opening protected? [ ] Yes [ ] No
Are fire door provided? [ ] Yes [ ] No Width ____________Fire door construction ________________
Door provided with vision panel? [ ] Yes [ ] No If Yes, made of ______________________________________
Door equipped w/ Self-closing device? [ ] Yes [ ] No Doors & enclosure proper rating? [ ] Yes [ ] No
Doors open easily? [ ] Yes [ ] No Self-closing device operable? [ ] Yes [ ] No
Door equipped w/ panic hardware? [ ] Yes [ ] No Operable? [ ] Yes [ ] No
Door swing in the direction of exit travel? [ ] Yes [ ] No Enclosure properly protected? [ ] Yes [ ] No
Fire escape pressurized? [ ] Yes [ ] No [ ] N/A If pressurized, what type or method? __________________________
Date Last Tested ___________________________________________________________________________________

C. HORIZONTAL EXITS
Width of door/s ______________________ Construction________________________ With vision panel [ ] Yes [ ] No
Door swing in the direction of egress travel? [ ] Yes [ ] No With Self-closing device? [ ] Yes [ ] No
Width of corridors or hallways _______________________________Construction _______________________________
Corridor walls extended from slab to slab? [ ] Yes [ ] No Properly illuminated? [ ] Yes [ ] No
Exit readily visible? [ ] Yes [ ] No Clear and unobstructed? [ ] Yes [ ] No
Properly marked w/ illuminated exit sign? [ ] Yes [ ] No With illuminated directional sign? [ ] Yes [ ] No
Properly located? [ ] Yes [ ] No

D. RAMPS
Provided? [ ] Yes [ ] No Type: [ ] Interior [ ] Exterior Width _______________ Class _______________
Railings provided? [ ] Yes [ ] No Height from the floor ______________(Requirement: 91 cm)
Any enclosure provided? [ ] Yes [ ] No Construction________________________________________________
Are fire doors provided? [ ] Yes [ ] No Width ____________________ Fire door construction______________
Door equipped w/ Self-closing device? [ ] Yes [ ] No Door with proper rating? [ ] Yes [ ] No
Door provided w/ vision panel? [ ] Yes [ ] No If Yes, made of _____________________________________________
Door swing in the direction of exit travel (when required)? [ ] Yes [ ] No
Any obstruction? ________________________________ Termination/Discharge of exit _________________________

E. AREA OF SAFE REFUGE


Provided? [ ] Yes [ ] No Type: [ ] Interior [ ] Exterior Location ___________________________________
Any enclosure provided ? [ ] Yes [ ] No Construction________________________________________________

Are fire door provided? [ ] Yes [ ] No Width _______________ Fire door construction___________________
Door equipped w/ self-closing device? [ ] Yes [ ] No Door with proper rating? [ ] Yes [ ] No
Door provided w/ vision panel? [ ] Yes [ ] No If Yes, made of ________________________________
Door swing in the direction of exit travel? [ ] Yes [ ] No

VI. LIGHTINGS & SIGNS


A. EMERGENCY LIGHTS
Automatic Emergency Lights Provided? [ ] Yes [ ] No Source of Power [ ] AC/DC [ ] Others _________________
No. of Units per Floor________________ Located at: Hallways _______________ Stairway Landings _______________
Operational: [ ] Yes [ ] No Exit path properly illuminated? [ ] Yes [ ] No
Tested Monthly: [ ] Yes [ ] No Minimum AEL Power Duration : at least one (1) hour

B. EXIT SIGNS
Exit Signs Illuminated? [ ] Yes [ ] No Location _________________________________________________
Source of Power [ ] AC/DC { } Others____________________________________ Readily visible? [ ] Yes [ ] No
Minimum Letter Size _______________________ Min. Requirement: Height of 11.5 cm & width of 19.0 mm
Exit Route Plan posted on: Lobby/Hallways? [ ] Yes [ ] No Rooms? [ ] Yes [ ] No
Directional Exit Signs? [ ] Yes [ ] No Location_____________________________________________________

C. WARNING/SAFETY SIGNS
[ ] No Smoking [ ] Dead-end [ ] Elevator Sign [ ] Keep Door Closed
Others, specify _____________________________________________________________________________________

VII. FEATURES OF FIRE PROTECTION


A. PROTECTION OF VERTICAL OPENINGS
Properly protected? [ ] Yes [ ] No Atrium? [ ] Yes [ ] No Fire Doors good condition? [ ] Yes [ ] No
Elevator opening protected? [ ] Yes [ ] No Pipe Chase opening protected? [ ] Yes [ ] No
Aircon Ducts system with damper? [ ] Yes [ ] No Dumb Waiter opening protected? [ ] Yes [ ] No
Garbage Chute opening protected? [ ] Yes [ ] No Between Floor & Glass Curtain opening protected? [ ] Yes [ ]
No
Date Last Tested____________________________________________________________________________________

B. ALARM SYSTEM
Fire Alarm Provided? [ ] Yes [ ] No Type: [ ] Manual [ ] Automatic Centralized? [ ] Yes [ ] No
Location of Central Control __________________________________________________________________________
No. of Bells per Floor __________ Location__________________________________________________________
Coverage: [ ] Building [ ] Air Handling Unit [ ] Portion, specify__________ Monitored? [ ] Yes [ ] No
Type of Initiation Device? [ ] Smoke [ ] Heat [ ] Manual [ ] Water Flow [ ] Others ____________________________
No. of Pull Stations per Floor______Max.. Horizontal Distance Bet. Pull Stations: 61.0 m
Smoke Detectors? [ ] Yes [ ] No No. of Units per Room _______________ Integrated? [ ] Yes [ ] No
Heat Detectors? [ ] Yes [ ] No No. of Units per Room _______________ Integrated? [ ] Yes [ ] No
Power Source of Detectors [ ] AC/DC [ ] Others___________ Total Detectors per Floor ________________________
Date Last Tested ____________________________________________________________________________________

C. STANDPIPE SYSTEM
Type: [ ] Wet [ ] Dry Tank Capacity ____________________Location _______________________________
Siamese Intake Provided? [ ] Yes [ ] No Location _________________________________________________
Size ________________ No. of Units ___________________________ Accessible? [ ] Yes [ ] No
Fire Hose Cabinets Provided? [ ] Yes [ ] No With Complete accessories [ ] Yes [ ] No
Location ___________________________________________
No. of Units per Floor ____________ Size of Hose ___________________ Length of Hose _______________________
(Note: Min Required Size of Riser & Distribution Pipe: 2 inch and 1 inch in diameter, respectively
Type of Nozzle ________________________________Date Last Tested ______________________________________
Fire Lane Provided: [ ] Yes [ ] No Location of nearest Fire Hydrant ______________________________

D. FIRST AID FIRE PROTECTION EQUIPMENT (PORTABLE FIRE EXTINGUISHERS)


Type _________________________ Capacity ____________________ No. of Units _____________________________
With PS Mark? [ ] Yes [ ] No With ISO Mark? [ ] Yes [ ]No
Properly Maintained? [ ] Yes [ ] No Conspicuously Located? [ ] Yes [ ] No Accessible? [ ] Yes [ ] No
Other Types Provided, if any __________________________________________________________________________

E. AUTOMATIC FIRE SUPPRESSION SYSTEM (SPRINKLER SYSTEM)


Type of Extinguishing Agent Used __________________Jockey Pump Capacity ____________hp ________GPM

Fire Pump Capacity: ____________hp _____________GPM Tank Capacity?__________________________ gallons


Maintaining Line Pressure ________________________Farthest Sprinkler Head Pressure _________________________

Riser Size _______Type of Heads Installed ______________________________________________________________


No. of Heads per Floor ___________Total___________________ Spacing of Heads _____________________________
Location of Fire Department Connection ________________________________________________________________
Date Last Tested ___________________________ Conducted By?___________________________________________
Plan Submitted? _________________________ Certificate of Installation? ____________________________________
BFP AFSS Certificate payment under Section 13 B(5) and Fund Code No. D2531-151.

F. FIRE WALL
Building required with fire walls? [ ] Yes [ ] No Provided? [ ] Yes [ ] No
Any opening?[ ] Yes [ ] No

VIII. BUILDING SERVICE EQUIPMENT


A. Boiler Provided? [ ] Yes [ ] No No. of Units provided_________________________________________
Fuel: [ ] Diesel [ ] Kerosene [ ] Coal [ ] Bunker [ ] LPG Capacity ______________________________________
Container: [ ] Above-ground [ ] Underground Location ____________________________________________
LPG Installation Covered with Permit? [ ] Yes [ ] No Fuel with Storage Permit? [ ] Yes [ ] No

B. Generator Set Provided? [ ] Yes [ ] No [ ] Automatic [ ] Manual Fuel:[ ] Diesel [ ] Gasoline


Capacity _______________________ Location ______________________ Dikes/Bundwall Provided [ ] Yes [ ] No
Container: [ ] Above-ground [ ] Underground Dispensing System? [ ] By pump [ ] By gravity
Output Capacity __________________kva Mechanical Permit ______________________Date Issued________________
Fuel with Storage Permit? [ ] Yes [ ] No Others (specify) _____________________________________________
Automatic Transfer Switch Provided? [ ] Yes [ ] No Time interval ______sec (Requirement- max 10
seconds)

C. Refuse (Garbage) Handling Facility: Provided? [ ] Yes [ ] No


Enclosure provided? [ ] Yes [ ] No Fire resistive? [ ] Yes [ ] No
Fire protection provided? [ ] Yes [ ] No Type ______________________________________________________
Frequency of collection/disposal______________________________ How collected?__________________________

D. Electrical System
Is there any electrical hazard? [ ] Yes [ ] No Specify location_______________________________________

E. Mechanical System
Is there any mechanical hazard? [ ] Yes [ ] No Specify location ______________________________________
No. of elevators provided __________
Firemans elevator provided? [ ] Yes [ ] No Firemans key/switch provided? [ ] Yes [ ]No

F. Other Building Service Systems


[ ] Water Treatment Facility [ ] Waste Water/Sewage Treatment Facility

IX. HAZARDOUS AREAS


[ ] Kitchen [ ] Laundry [ ] Windowless Basement [ ] Storage Room Others____________________
Separation Fire Rated? [ ] Yes [ ] No Type of Fire Protection provided_______________________________________
No. of Units ____________________________ Capacity __________________________Accessible? [ ] Yes [ ] No
Fuel Used _____________ Where Stored _____________________ Covered by BFP Permit _______________________
Chimney: Made of ___________________ Spark Arrester __________________Smoke Hood _____________________
Presence of hazardous materials? [ ] Yes [ ] No Properly stored and handled? [ ] Yes [ ] No
Kinds Container Volume Location
1. ___________________________ __________________ __________ ________________________________
2. ___________________________ __________________ __________ ________________________________

3. ___________________________ __________________ __________ ________________________________

Storage Permit for Flammables/Combustibles Covered by BFP Permit? _______________________________________


Clearance of Stocks From Ceiling _____________________________________________________________________
Minimum Ceiling Clearance: 1.0m for Flammable Liquids and 0.5m for Combustible Materials

X. OPERATING FEATURES
Fire Safety Program (Under the supervision of the Chief Local Fire Service)
Fire Brigade Organization? [ ] Yes [ ] No
Fire Safety Seminar [ ] Yes [ ] No
Employees trained in emergency procedures? [ ] Yes [ ] No
Fire/Evacuation Drill [ ] Yes [ ] No
1st ________________ 2nd _________________ 3rd ___________________ 4th ____________________

XI. DEFECTS / DEFICIENCIES NOTED DURING INSPECTION ( Attached pictures, sketches and others)
___________________________________________________________________________________________
__________________________________________________________________________________________________
__________________________________________________________________________________________________
__________________________________________________________________________________________________
__________________________________________________________________________________________________
___________________________________________________

XII. RECOMMENDATIONS
___________________________________________________________________________________________
__________________________________________________________________________________________________
__________________________________________________________________________________________________
__________________________________________________________________________________________________
___________________________________________________________

ACKNOWLEDGED BY:

____________________________________________ ____________________________________________
Signature Over Printed Name of Owner/Representative Fire Safety Inspector/s
Date & Time______________________

__________________________________________
Team Leader

RECOMMEND ISSUANCE OF FSIC/NTC/NTCV:

__________________________________________
CHIEF, FIRE SAFETY ENFORCEMENT SECTION

APPROVED/DISAPPROVED:

Original (BFP copy) ____________________________________


Duplicate (BO or BPLO, as the case maybe) City Fire Marshal
Triplicate (Applicant/Owners Copy)