This document provides a summary of the device configuration for a 7UT633 8T.C1C+R1 protection relay. It lists various protection functions and their settings, including differential protection, thermal overload protection, and over/undervoltage protection mostly being disabled. It also includes power system data like transformer ratings and CT/VT assignments. Settings for differential element characteristics, harmonic restraint, and pole slip detection are also summarized.

Uploaded by

Balaji
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
806 views7 pages

Power System Device Configuration Guide

This document provides a summary of the device configuration for a 7UT633 8T.C1C+R1 protection relay. It lists various protection functions and their settings, including differential protection, thermal overload protection, and over/undervoltage protection mostly being disabled. It also includes power system data like transformer ratings and CT/VT assignments. Settings for differential element characteristics, harmonic restraint, and pole slip detection are also summarized.

Uploaded by

Balaji
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

7UT633 8T_C1C+R1_prn_11_23_29

Device Configuration
Airport Project / Folder / 380kV / SGT /
SIMATIC 7UT633 8T.C1C+R1/7UT633 06.09.18 11:23:29

1 Device Configuration

No. Function Scope

0103 Setting Group Change Option Disabled


0105 Protection Object Autotransformer current node
0112 Differential Protection Enabled
0113 Restricted earth fault protection Disabled
0114 Restricted earth fault protection 2 Disabled
0117 Cold Load Pickup Disabled
0120 DMT / IDMT Phase Disabled
0130 DMT / IDMT Phase 2 Disabled
0132 DMT / IDMT Phase 3 Disabled
0122 DMT / IDMT 3I0 Disabled
0134 DMT / IDMT 3I0 2 Disabled
0136 DMT / IDMT 3I0 3 Disabled
0124 DMT / IDMT Earth Disabled
0138 DMT / IDMT Earth 2 Disabled
0127 DMT 1Phase Disabled
0140 Unbalance Load (Negative Sequence) Disabled
0142 Thermal Overload Protection Disabled
0144 Thermal Overload Protection 2 Disabled
0143 Overexcitation Protection (U/f) Disabled
0150 Reverse Power Protection Disabled
0151 Forward Power Supervision Disabled
0152 Undervoltage Protection Disabled
0153 Overvoltage Protection Disabled
0156 Over / Underfrequency Protection Disabled
0170 Breaker Failure Protection Disabled
0171 Breaker Failure Protection 2 Disabled
0180 Disconnect measurment location Disabled
0181 Measured Values Supervision Disabled
0182 Trip Circuit Supervision Disabled
0186 External Trip Function 1 Disabled
0187 External Trip Function 2 Disabled
Flexible Function
additional Measured Value

Page 1 of 7
7UT633 8T_C1C+R1_prn_11_23_29
Power System Data 1
Airport Project / Folder / 380kV / SGT /
SIMATIC 7UT633 8T.C1C+R1/7UT633 06.09.18 11:23:29

2 Power System Data 1

2.1 Group Power System Data 1; Group CT-Numbers

Group Power System Data 1; Group CT-Numbers


No. Settings Value Group

0211 Number of connected Measuring Locations 3 All


0212 Number of assigned Measuring Locations 3 All
0213 Number of Sides 3 All

2.2 Group Power System Data 1; Group CT-Assign

Group Power System Data 1; Group CT-Assign


No. Settings Value Group

0222 Assignment at 3 assig.Meas.Loc./ 3 Sides S1:M1, S2:M2, S3:M3 All


0241 Side 1 is assigned to auto-connected All
0242 Side 2 is assigned to auto-connected All
0243 Side 3 is assigned to earthing electrode All
0251 Auxiliary CT IX1 is used as not connected All
0252 Auxiliary CT IX2 is used as not connected All
0253 Auxiliary CT IX3 is used as not connected All
0255 Type of auxiliary CT IX3 1A/5A current input All

2.3 Group Power System Data 1; Group VT-Assign

Group Power System Data 1; Group VT-Assign


No. Settings Value Group

0261 VT set UL1, UL2, UL3 is assigned not connected All


0262 VT U4 is assigned not connected All
0263 VT U4 is used as Udelta transformer All

Page 2 of 7
7UT633 8T_C1C+R1_prn_11_23_29
Group Power System Data 1; Group Power System
Airport Project / Folder / 380kV / SGT /
SIMATIC 7UT633 8T.C1C+R1/7UT633 06.09.18 11:23:29

2.4 Group Power System Data 1; Group Power System

Group Power System Data 1; Group Power System


No. Settings Value Group

0270 Rated Frequency 60 Hz All


0271 Phase Sequence L1 L2 L3 All
0276 Unit of temperature measurement Degree Celsius All

2.5 Group Power System Data 1; Group Transf.

Group Power System Data 1; Group Transf.


No. Settings Value Group

0311 Rated Primary Voltage Side 1 380.0 kV All


0312 Rated Apparent Power of Transf. Side 1 502.00 MVA All
0321 Rated Primary Voltage Side 2 132.0 kV All
0322 Rated Apparent Power of Transf. Side 2 502.00 MVA All

2.6 Group Power System Data 1; Group CT's

Group Power System Data 1; Group CT's


No. Settings Value Group

0511 CT-Strpnt. Meas. Loc.1 in Dir. of Object YES All


0512 CT Rated Primary Current Meas. Loc. 1 3000 A All
0513 CT Rated Secondary Current Meas. Loc. 1 1A All
0521 CT-Strpnt. Meas. Loc.2 in Dir. of Object YES All
0522 CT Rated Primary Current Meas. Loc. 2 3000 A All
0523 CT Rated Secondary Current Meas. Loc. 2 1A All
0531 CT-Strpnt. Meas. Loc.3 in Dir. of Object YES All
0532 CT Rated Primary Current Meas. Loc. 3 800 A All
0533 CT Rated Secondary Current Meas. Loc. 3 1A All

Page 3 of 7
7UT633 8T_C1C+R1_prn_11_23_29
Group Power System Data 1; Group CB
Airport Project / Folder / 380kV / SGT /
SIMATIC 7UT633 8T.C1C+R1/7UT633 06.09.18 11:23:29

2.7 Group Power System Data 1; Group CB

Group Power System Data 1; Group CB


No. Settings Value Group

0831 Switchgear / CBaux at Side 1 Q0 All


0832 Switchgear / CBaux at Side 2 <none> All
0833 Switchgear / CBaux at Side 3 <none> All
0836 Switchgear / CBaux at Measuring Loc. M1 <none> All
0837 Switchgear / CBaux at Measuring Loc. M2 <none> All
0838 Switchgear / CBaux at Measuring Loc. M3 <none> All
0851A Minimum TRIP Command Duration 0.15 sec All

Page 4 of 7
7UT633 8T_C1C+R1_prn_11_23_29
Settings groups
Airport Project / Folder / 380kV / SGT /
SIMATIC 7UT633 8T.C1C+R1/7UT633 06.09.18 11:23:29

3 Settings groups

3.1 Group Power System Data 2; Group PoleOpen Detect

Group Power System Data 2; Group PoleOpen Detect


No. Settings Value Group

1111 Pole Open Current Threshold Side 1 0.20 I/InS A


1112 Pole Open Current Threshold Side 2 0.15 I/InS A
1113 Pole Open Current Threshold Side 3 0.20 I/InS A
1121 Pole Open Current Threshold Meas.Loc. M1 0.15 A A
1122 Pole Open Current Threshold Meas.Loc. M2 0.10 A A
1123 Pole Open Current Threshold Meas.Loc. M3 0.04 A A

3.2 Group Differential Protection; Group General

Group Differential Protection; Group General


No. Settings Value Group

1201 Differential Protection ON A


1205 Increase of Trip Char. During Start OFF A
1206 Inrush with 2. Harmonic Restraint ON A
1207 n-th Harmonic Restraint OFF A

3.3 Group Differential Protection; Group I-Diff

Group Differential Protection; Group I-Diff


No. Settings Value Group

1221 Pickup Value of Differential Curr. 0.40 I/InO A


1226A T I-DIFF> Time Delay 0.00 sec A
1231 Pickup Value of High Set Trip 10.0 I/InO A
1236A T I-DIFF>> Time Delay 0.00 sec A

Page 5 of 7
7UT633 8T_C1C+R1_prn_11_23_29
Group Differential Protection; Group Characteristic
Airport Project / Folder / 380kV / SGT /
SIMATIC 7UT633 8T.C1C+R1/7UT633 06.09.18 11:23:29

3.4 Group Differential Protection; Group Characteristic

Group Differential Protection; Group Characteristic


No. Settings Value Group

1241A Slope 1 of Tripping Characteristic 0.30 A


1242A Base Point for Slope 1 of Charac. 1.00 I/InO A
1243A Slope 2 of Tripping Characteristic 0.80 A
1244A Base Point for Slope 2 of Charac. 2.50 I/InO A
1251A I-RESTRAINT for Start Detection 0.10 I/InO A
1252A Factor for Increasing of Char. at Start 1.0 A
1253 Maximum Permissible Starting Time 5.0 sec A
1261A Pickup for Add-on Stabilization 4.00 I/InO A
1262A Duration of Add-on Stabilization 15 Cycle A
1263A Time for Cross-blocking Add-on Stabiliz. 15 Cycle A

3.5 Group Differential Protection; Group Inrush 2.HM

Group Differential Protection; Group Inrush 2.HM


No. Settings Value Group

1271 2nd Harmonic Content in I-DIFF 15 % A


1272A Time for Cross-blocking 2nd Harm. 10 Cycle A

3.6 Group Differential Protection; Group Restr. n.HM

Group Differential Protection; Group Restr. n.HM


No. Settings Value Group

1276 n-th Harmonic Content in I-DIFF 25 % A


1277A Time for Cross-blocking n-th Harm. 0 Cycle A
1278A Limit IDIFFmax of n-th Harm.Restraint 1.5 I/InO A

Page 6 of 7
7UT633 8T_C1C+R1_prn_11_23_29
Group Supervision; Group General
Airport Project / Folder / 380kV / SGT /
SIMATIC 7UT633 8T.C1C+R1/7UT633 06.09.18 11:23:29

3.7 Group Supervision; Group General

Group Supervision; Group General


No. Settings Value Group

8401 Fast broken current-wire supervision OFF A


8414 Delay time for BWD supervision 1.0 sec A
8415 min differential current for BWD 1.00 I/InO A