Crompton Greaves Limited
Metal Clad Outdoor Vacuum Circuit Breaker - KIOSK
12kV Roof Bushing KIOSK 12kV Line up KIOSK
Product Overview Salient Features
The KIOSK is specially designed for unmanned substations in the 4
Compact fixed / draw-out type (optional) VCB truck.
Outdoor distribution network. It is a standalone vacuum switchgear 4
SCADA Compatible with rapid autoreclosure duty.
system with built in self driven independent control supply for self 4
Remote metering option with multifunction communicable Tri
tripping & closing of CB. The product is well equipped for metering, Vector Meter.
control, protection & SCADA compatibility.
4
Tested for extended mechanical endurance of M2 class as per
The product is available in two basic designs - IEC 62271 – 100, ensuring 10,000 operating sequences.
Roof bushing type with incoming & outgoing through roof bushings 4
Pedestal mounting to avoid rusting of bottom base & ease of
(Rated Voltage: 12 & 36 kV) control cable wiring.
Line up type with incoming through bottom, rear / side cable entry & 4
Usage of non hygroscopic solid insulations.
outgoing through busbar / cables (Rated Voltage : 12 & 36 kV) 4
Type tested as per IEC: 62271 - 100, 200.
Technical Data
Roof Bushing
Characteristics Units Roof Bushing Line up
& Line up
Rated Voltage kV 12 36
Rated Current Amp Upto 1250 Upto 1250 Upto 1600 Upto 3150 Upto 1250 A
No of poles nos 3
Frequency Hz 50
Symmetrical Breaking Capacity kA upto 26.3 20 26.3 40 26.3
Making Capacity kApk 32.75 50 65.75 100 65.75
Power Frequency Withstand Voltage kV rms 28 70
Impulse Withstand kVpk 75 170
Operating Duty cycles O-0.3sec-CO-3min-CO (Rapid Autoreclosing Duty)
Total Break Time cycles 3 3.5
Make Time cycles 3 3
DC Component % < 50%
Degree of Protection IP 54
Applicable Standard IS 13118, IEC 62271-100 / 200
Outdoor Circuit Breaker Metal Clad Vacuum Circuit Breaker – KIOSK
Roof Bushing Kiosk GA Drawing Line-up Kiosk GA Drawing
OUTGOING
INCOMING
BUSBARS
VCB MECHANISM- MOTORISED
B R
VCB POLE UNIT ASSLY.
Y
CTs SWING INSTRUMENT
FIXED TYPE PANEL
VCB PANEL
WITH TRIP COIL
VTs
H
CT H
VCB
LTCHR
INSTRUMENT
PANEL
CABLE
TERMINATION
GLAND PLATE
PT
FLOOR STAND
D W
SIDE VIEW FRONT VIEW
W D
SIDE VIEW
36kV Roof Bushing KIOSK 36kV Line up KIOSK
Dimensions (mm)
Variants W D H
Line-Up - 12kV
Fault level 20kA & Rated Current 1250 A 707 1840 2030
Fault level 26.3kA & Rated Current 1600 A 857 1840 2030
Fault level 31.5kA & Rated Current 1250 A 707 1960 2424
Fault level 40kA & Rated Current 2000 A 857 1960 2424
Roof Bushing - 36kV
Fault level 26.3kA & Rated Current 1250 A 1300 1780 3020
Roof Bushing - 12kV
Fault level 20kA & Rated Current 800 A 706 954 2850
Fault level 26.3kA & Rated Current 1250 A 706 954 2850
Line Up - 36kV
Fault level 26.3kA & Rated Current 1250 A 1200 3570 2520
Crompton Greaves Ltd.,
Power Systems : M. V. Switchgear Division (S2)
A-3, MIDC, Ambad, Nasik - 422 010. India.
Tel. : +91 253 2382271 to 75
Email : mv.switchgear@cgglobal.com
Registered Office
CG House, 6th Floor, Dr. Annie Besant Road, Worli, Mumbai- 400 030.
www.cgglobal.com