HVAC Load Calculation Sheet

This document contains calculations for heating and cooling load estimates for an unspecified room. It lists outdoor and indoor temperatures, glass and wall areas, heat gain from sunlight, infiltration, transmission, and internal sources. Calculations are shown for sensible and latent heat for both cooling and heating loads. Safety factors are included to determine the final cooling and heating requirements in tons.

Uploaded by

Caps Lock
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
145 views1 page

HVAC Load Calculation Sheet

This document contains calculations for heating and cooling load estimates for an unspecified room. It lists outdoor and indoor temperatures, glass and wall areas, heat gain from sunlight, infiltration, transmission, and internal sources. Calculations are shown for sensible and latent heat for both cooling and heating loads. Safety factors are included to determine the final cooling and heating requirements in tons.

Uploaded by

Caps Lock
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd

Project No.

Room No :

Name :

Room Size. Sq. Ft. x Cu. Ft.

Estimated by : Date :

Checked by : Date :
COOLING LOAD HEATING LOAD

Condition D.B W.B % R.H Gr/lb. Condition D.B W.B % R.H Gr/lb.
Outside 115 82 112 Inside
Inside 75 50% 72 Outside
Difference 40 40 Difference

OUTSIDE AIR : 0 PERSON X 0 0 AIR CHANGES / HR……………….CFM.


Area or Sun gain or Factor
quantity Temp. Diff.
SUNLIGHT GAIN BTU / HR HEAT LOSS BTU / HR.
Glass N 0 Sq. Ft. 15.3 0.56 0 Windows Sq. Ft. 30 x 1.13
Glass S 0 Sq. Ft. 13.06 0.56 0 Walls Sq. Ft. 30 x
Glass W 0 Sq. Ft. 178.8 0.56 0 Partition Sq. Ft. 25 x
Glass E 0 Sq. Ft. 13.08 0.56 0 Ceiling Sq. Ft. 25 x
Wall N 0 Sq. Ft. 37 0.1 0 Floor Sq. Ft. 25 x
Wall S 0 Sq. Ft. 45 0.1 0 Infilt Sq. Ft. 30 x 1.1
Wall W 0 Sq. Ft. 43 0.1 0 SUB TOTAL
Wall E 0 Sq. Ft. 52 0.1 0 SAFETY FACTOR 10%
Roof 0 Sq. Ft. 63 0.1 0
Sky light 0 Sq. Ft. 235 0.52 0
TRANSMISSION GAIN (Except walls & roof) ROOM HEAT LOSS
All Glass 0 Sq. Ft. 40 1.13 0
Infiltration Sq. Ft. 40 1.08 0 O : A Loss CFM x x 1.1
Sh. Wall Sq. Ft. 0
Partition 0 Sq. Ft. 32 .38 0 TOTAL HEAT LOSS
Gl. Part. 0 Sq. Ft. 0 REMARKS
Ceilling Sq. Ft. 20 .38 0
Floor 0 Sq. Ft. 10 .38 0 TOTAL HEAT 0 Btu/hr act. Ton 0
INTERNAL HEAT
People 0 Person 215 0
Appliances Sq. Ft. 1.13 Watt x 3.412 0
Lights 0 Watts/m2 3.412 1.25 0
Room Sensible Heat Subtotal 0
SAFETY FACTOR "A" 10% 0
ROOM SENSIBLE HEAT 0 N. B. :
SAFETY FACTOR "A"
ROOM LATENT HEAT Reheat Supply Duct. Ht. Gain. 5%
People 0 Person * 235 0 Supply Duct Leakage Loss. 2%
Steam 0 x lb/Hr. * 1000 0 Fan H.P. 3%
Room Latent Heat Subtotal 0 Safety Factor. 5%
SAFETY FACTOR "B" 7 % 0 SAFETY FACTOR "B"
ROOM LATENT HEAT 0 Supply Duct Leakage Loss. 2%
ROOM TOTAL HEAT 0 Safety Factor. 5%
OUTSIDE AIR HEAT SAFETY FACTOR "C"
Sens. 0 CFM 40° F x 1.08 0 Return Duct Heat Gain. 2%
Latent 0 CFM x 40 Gr/lb x 0.67 0 Return duct Leakage Gain. 3%
SAFETY FACTOR "C" 5% 0 Pump H. P. 2%
TONS = GRAND TOTAL HEAT 0 Dehum. & Piping Los. 3%

Assume T ( Temp. Diff. Between Rm. Design Temp. and air off Coil D. B. Temp ) = …………F 18° F

Rm S.A.C.F.M = Rm.S.Hi 0 0 cfm


1.08 x T 1.08 * 18