Load Flow Report for ETAP Project

The document is a load flow report for an electrical distribution system. It provides key information from a load flow analysis, including: - Voltage levels and angles at each bus - Power flows between buses in MW and MVAR - Current flows and power factors for transformers The report lists detailed results for over 90 buses in the system and the power flows between them.

Uploaded by

muhammad ahsan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views2 pages

Load Flow Report for ETAP Project

The document is a load flow report for an electrical distribution system. It provides key information from a load flow analysis, including: - Voltage levels and angles at each bus - Power flows between buses in MW and MVAR - Current flows and power factors for transformers The report lists detailed results for over 90 buses in the system and the power flows between them.

Uploaded by

muhammad ahsan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

ETAP

Project: Page: 1
12.6.0H
Location: Date: 10-06-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: GSK Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR

ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

Bus1 11.000 100.009 0.0 0 0 0 0 Bus2 -0.523 1.647 90.7 -30.3

Bus3 0.523 -1.647 90.7 -30.3

* Bus2 11.000 100.000 0.0 0.524 -1.647 0 0 Bus1 0.524 -1.647 90.7 -30.3

Bus3 11.000 100.010 0.0 0 0 0 0 Bus1 -0.523 1.647 90.7 -30.3

Bus6 0.523 -1.647 90.7 -30.3

Bus5 0.415 98.740 -3.0 0 0 0.000 -0.975 Bus7 0.000 0.000 0.1 96.4

Bus8 0.030 0.010 44.2 95.0

Bus57 0.028 0.009 42.2 95.0

Bus12 0.002 0.001 3.2 95.0

Bus59 0.000 0.000 0.3 95.5

Bus61 0.000 0.000 0.1 95.0

Bus124 0.004 0.001 6.2 95.0

Bus16 0.002 0.001 3.2 95.0

Bus20 0.005 0.002 7.4 95.0

Bus67 0.002 0.001 2.7 95.1

Bus73 0.000 0.000 0.0 99.1

Bus75 0.004 0.001 6.0 95.0

Bus77 0.014 0.005 20.6 95.0

Bus81 0.004 0.001 6.3 95.0

Bus83 0.017 0.006 25.7 95.0

Bus87 0.000 0.000 0.4 95.2

Bus89 0.002 0.001 2.5 95.0

Bus6 -0.472 1.800 2622.5 -25.4

Bus65 0.002 0.001 3.7 95.0

Bus90 0.354 -0.864 1315.9 -37.9

Bus6 0.415 98.048 -2.5 0 0 0 0 Bus5 0.484 -1.784 2622.5 -26.2

Bus3 -0.484 1.784 2622.5 -26.2

Bus7 0.415 98.739 -3.0 0 0 0 0 Bus5 0.000 0.000 0.1 95.0

Bus8 0.415 98.666 -3.0 0 0 0.030 0.010 Bus5 -0.030 -0.010 44.2 95.0

Bus12 0.415 98.737 -3.0 0 0 0.002 0.001 Bus5 -0.002 -0.001 3.2 95.0

Bus16 0.415 98.669 -3.0 0 0 0.002 0.001 Bus5 -0.002 -0.001 3.2 95.0

Bus20 0.415 98.565 -3.0 0 0 0.005 0.002 Bus5 -0.005 -0.002 7.4 95.0

Bus57 0.415 98.712 -3.0 0 0 0.028 0.009 Bus5 -0.028 -0.009 42.2 95.0

Bus59 0.415 98.739 -3.0 0 0 0 0 Bus5 0.000 0.000 0.3 95.0

Bus61 0.415 98.739 -3.0 0 0 0 0 Bus5 0.000 0.000 0.1 95.0

Bus65 0.415 98.659 -3.0 0 0 0.002 0.001 Bus5 -0.002 -0.001 3.7 95.0
ETAP
Project: Page: 2
12.6.0H
Location: Date: 10-06-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: GSK Config.: Normal

Bus Voltage Generation Load Load Flow XFMR

ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

Bus67 0.415 98.290 -2.9 0 0 0.002 0.001 Bus5 -0.002 -0.001 2.7 95.0

Bus73 0.415 98.738 -3.0 0 0 0 0 Bus5 0.000 0.000 0.0 95.0

Bus75 0.415 98.713 -3.0 0 0 0.004 0.001 Bus5 -0.004 -0.001 6.0 95.0

Bus77 0.415 98.645 -3.0 0 0 0.014 0.005 Bus5 -0.014 -0.005 20.6 95.0

Bus81 0.415 98.714 -3.0 0 0 0.004 0.001 Bus5 -0.004 -0.001 6.3 95.0

Bus83 0.415 98.336 -2.9 0 0 0.017 0.006 Bus5 -0.017 -0.006 25.7 95.0

Bus87 0.415 98.728 -3.0 0 0 0 0 Bus5 0.000 0.000 0.4 95.0

Bus89 0.415 98.704 -3.0 0 0 0.002 0.001 Bus5 -0.002 -0.001 2.5 95.0

Bus90 0.415 98.740 -3.0 0 0 0.000 -0.975 Bus92 0.024 0.008 35.5 95.0

Bus94 0.008 0.003 11.9 95.0

Bus96 0.007 0.002 10.1 95.0

Bus98 0.005 0.002 7.4 95.0

Bus101 0.001 0.000 2.1 95.1

Bus103 0.039 0.013 58.4 95.0

Bus106 0.027 0.009 39.9 95.0

Bus109 0.019 0.000 27.5 100.0

Bus111 0.048 0.016 71.0 95.0

Bus113 0.005 0.002 6.9 95.0

Bus115 0.171 0.057 253.4 94.9

Bus117 0.000 0.000 0.0 -93.3

Bus5 -0.354 0.864 1315.9 -37.9

Bus92 0.415 98.648 -3.0 0 0 0.024 0.008 Bus90 -0.024 -0.008 35.5 95.0

Bus94 0.415 98.524 -3.0 0 0 0.008 0.003 Bus90 -0.008 -0.003 11.9 95.0

Bus96 0.415 98.418 -3.0 0 0 0.007 0.002 Bus90 -0.007 -0.002 10.1 95.0

Bus98 0.415 98.636 -3.0 0 0 0.005 0.002 Bus90 -0.005 -0.002 7.4 95.0

Bus101 0.415 98.662 -3.0 0 0 0.001 0.000 Bus90 -0.001 0.000 2.1 95.0

Bus103 0.415 98.689 -3.0 0 0 0.039 0.013 Bus90 -0.039 -0.013 58.4 95.0

Bus106 0.415 98.598 -3.0 0 0 0.027 0.009 Bus90 -0.027 -0.009 39.9 95.0

Bus109 0.415 98.683 -3.0 0 0 0.019 0.000 Bus90 -0.019 0.000 27.5 100.0

Bus111 0.415 98.706 -3.0 0 0 0.048 0.016 Bus90 -0.048 -0.016 71.0 95.0

Bus113 0.415 98.730 -3.0 0 0 0.005 0.002 Bus90 -0.005 -0.002 6.9 95.0

Bus115 0.415 97.946 -3.2 0 0 0.170 0.056 Bus90 -0.170 -0.056 253.4 95.0

Bus117 0.415 98.740 -3.0 0 0 0 0 Bus90 0.000 0.000 0.0 -93.3

Bus124 0.415 98.723 -3.0 0 0 0.004 0.001 Bus5 -0.004 -0.001 6.2 95.0

* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA