Extended technical Data - blueplanet 150 TL3
AC Power
Inverter power nominal 150 kVA
Inverter power maximal 150 kVA
Rated current (In) 131,2 A
Power electronics type IGBT-MLI (self-commutated)
Rated operating voltage 660 V
cos phi nominal ≈1
Grid connection Three-phase
Impedance bei 165 Hz * R165 Hz ≈ 360,0 Ω, X165 Hz ≈ 100,0 Ω
Impedance bei 175 Hz * R175 Hz ≈ 47,0 Ω, X175 Hz ≈ 360,0 Ω
* Scheme in parallel
Operating behaviour in the event of a short circuit at the inverter output
Maximum peak current (Ip) 1,40 x 132,3 A
Maximum peak current (Ik“) 1,02 x 132,3 A
Power quality characteristics
Max. number of switching operations, N10 10
Max. number of switching operations, N120 120
Case of switching operation Cut-in at 10 % of rated power
Grid impedance angle 30° 50° 70° 85°
Flicker step factor 0,05 0,03 0,05 0,05
Voltage change factor 2,05 2,05 2,05 2,05
Maximum incrush current factor 1,00
Maximum incrush current factor (transient only) 0,02
Case of switching operation Cut-in at 100 % of rated power
Grid impedance angle 30° 50° 70° 85°
Flicker step factor 0,33 0,47 0,30 0,29
Voltage change factor 2,05 2,05 2,05 2,05
Maximum incrush current factor 0,51
Maximum incrush current factor (transient only) 0,02
Case of switching operation Service disconnection at rated power
Description of the service disconnection procedere Disconnection by the DC-switch
Grid impedance angle 30° 50° 70° 85°
Flicker step factor 0,80 0,60 0,33 0,12
Voltage change factor 2,05 2,05 2,05 2,05
Maximum incrush current factor 0,08
Maximum incrush current factor (transient only) 0,04
KACO new energy GmbH · Carl-Zeiss-Straße 1 · 74172 Neckarsulm · Germany · Telefon + 49 7132 3818-0 · [email protected]
Worst case over all switching operations 1,00
Worst case over all switching operations (transient only) 0,04
Note: Sk, fic/Sn in the fictitious grid was set to 20
Flicker
Grid impedance angle 30° 50° 70° 85°
Flicker coefficient 0,96 0,94 0,92 0,92
Short-term flicker 0,048 0,047 0,046 0,046
Sk,fic/Sn in the fictitious grid was set to 20
KACO blueplanet
KACO blueplanet 150- TL3
87.0TL3 M1 M1
150.0TL3
RCMU DC link Semicoductor Grid chokes Grid relay Grid relay
capacity bridge
L1
Semicoductor
bridge
Ground fault
monitoring
Semicoductor
bridge
PV generator DC switch L2
EMC filter EMC filter
AC-busbar
(XL-Version) Semicoductor
bridge
Semicoductor
bridge
L3
Semicoductor
bridge
PE
Optional
DC SPD AC SPD
equipment DSP-control &
measurement
Optional interfaces User interface
Slot Slot Inverter 2x Fault Status LEDs
1 2 off Ethernet RS485 USB signal relay
Ethernet RS485
SPD SPD
blueplanet 150 TL3 The limit values acording EN 61000-3-12 are fulfilled
Harmonic
50 Hz 60 Hz
Courant harmonique
[A] [% de In] [A] [% de In]
1 126,717 95,85 127,616 96,46
2 0,088 0,18 0,233 0,18
3 0,143 0,11 0,122 0,09
4 0,038 0,11 0,139 0,11
5 0,356 0,64 0,663 0,69
6 0,043 0,10 0,124 0,10
7 0,374 0,53 0,259 0,54
8 0,062 0,07 0,082 0,07
9 0,035 0,05 0,041 0,04
10 0,059 0,09 0,095 0,08
11 0,244 0,38 0,660 0,50
12 0,074 0,10 0,097 0,10
13 0,272 0,21 0,240 0,23
14 0,058 0,08 0,085 0,07
15 0,031 0,06 0,043 0,05
16 0,058 0,06 0,068 0,06
17 0,258 0,31 0,500 0,38
18 0,090 0,09 0,075 0,10
19 0,230 0,17 0,131 0,18
20 0,070 0,08 0,073 0,07
21 0,031 0,05 0,059 0,05
22 0,066 0,06 0,079 0,06
23 0,228 0,21 0,312 0,24
24 0,102 0,09 0,090 0,09
25 0,224 0,17 0,155 0,13
26 0,082 0,09 0,074 0,07
27 0,035 0,06 0,076 0,06
28 0,067 0,07 0,086 0,06
29 0,183 0,16 0,200 0,15
30 0,106 0,09 0,106 0,08
31 0,187 0,14 0,193 0,15
32 0,082 0,08 0,075 0,06
33 0,029 0,07 0,063 0,05
34 0,062 0,07 0,073 0,05
35 0,161 0,15 0,161 0,12
36 0,098 0,09 0,092 0,07
37 0,159 0,14 0,162 0,12
38 0,075 0,07 0,066 0,05
39 0,030 0,06 0,043 0,03
40 0,055 0,06 0,058 0,04
41 0,119 0,13 0,111 0,08
42 0,085 0,08 0,067 0,05
43 0,116 0,12 0,097 0,07
44 0,065 0,07 0,050 0,04
45 0,019 0,05 0,030 0,02
46 0,045 0,06 0,041 0,03
47 0,089 0,10 0,067 0,05
48 0,071 0,07 0,045 0,03
49 0,083 0,09 0,057 0,04
50 0,054 0,05 0,034 0,03
Power derating blueplanet
Derang 150bp150.0
Kurve: TL3 TL3-M1, UAC 660V, UDC 1000V
175
150
125
Output power[kVA]
100
1000V
960V
75
1300V
50
25
0
25 30 35 40 45 50 55 60 65
Ambient temperature [°C]
Efficiency characteristic curve for blueplanet 150 TL3
% % %
28.11.2019