Voltage Drop-Calculation

The document contains voltage drop calculations for various sizes of PVC insulated aluminum and copper cables. It includes the current rating, supply system voltage, power factor, load, length, calculated voltage drop, and percentage voltage drop for each cable type and size. The calculations show that larger cable sizes have lower voltage drops for a given load and length.

Uploaded by

vjtheee
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
183 views4 pages

Voltage Drop-Calculation

The document contains voltage drop calculations for various sizes of PVC insulated aluminum and copper cables. It includes the current rating, supply system voltage, power factor, load, length, calculated voltage drop, and percentage voltage drop for each cable type and size. The calculations show that larger cable sizes have lower voltage drops for a given load and length.

Uploaded by

vjtheee
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

Voltage Drop for 2 Core PVC Insulated armoured & Unarmoured Cable -Al

Current Supply Power Load in


SL NO Description Voltage
rating system factor (KW)

1 2*2.5 sq mm AYFY 21 1 240 0.9 0.6


2 2*4sq mm AYFY 28 1 240 0.9 0.75
3 2*6 sq mm AYFY 35 1 240 0.9 0.75
4 2*10sq mm AYFY 46 1 240 0.9 1.05
5 2*16sq mm AYFY 60 1 240 0.9 0.9
6 2*25sq mm AYFY 76 1 240 0.9 5
7 2*35sq mm AYFY 92 1 240 0.9 3
8 2*50sq mm AYFY 110 1 240 0.9 5
9
10
11
12
13
14

Voltage Drop for 3 Core PVC Insulated armoured & Unarmoured Cable-Al

Current Supply Power Load in


SL NO Description Voltage
rating system factor (KW)

1 3*2.5 sq mm AYFY 19 3 415 0.9 0.54


2 3*4 sq mm AYFY 25 3 415 0.9 1.08
3 3*6 sq mm AYFY 32 3 415 0.9 2.16
4 3*10 sq mm AYFY 43 3 415 0.9 2.16
5 3*16 sq mm AYFY 60 3 415 0.9 10
6 3*25 sq mm AYFY 76 3 415 0.9 10
7 3*35 sq mm AYFY 92 3 415 0.9 10
8 3*50 sq mm AYFY 110 3 415 0.9 3.06
9
10
11

Voltage Drop for 3 Core PVC Insulated armoured & Unarmoured Cable-Cu

Current Supply Power Load in


SL NO Description Voltage
rating system factor (KW)

1 3*1.5 sq mm AYFY 18 3 415 0.9 3.06


2 3*2.5 sq mm AYFY 24 3 415 0.9 3.06
3 3*4 sq mm AYFY 31 3 415 0.9 2.06
4 3*6 sq mm AYFY 41 3 415 0.9 3.06
5 3*10 sq mm AYFY 56 3 415 0.9
6 3*16 sq mm AYFY 73 3 415 0.9
7
8
9
10
11
12
13
14
15
e -Al

Voltage
Load in Load Length Voltage % Voltage
drop
(Watts) Current (A) (m) drop in L drop
/A /m
600 2.78 200 29 16.11 6.71 -3.71 2.777778
750 3.47 175 18.2 11.06 4.61 -1.61
750 3.47 175 12.1 7.35 3.06 -0.06
1050 4.86 202 7.3 7.17 2.99 0.01
900 4.17 350 4.5 6.56 2.73 0.27
5000 23.15 250 2.9 16.78 6.99 -3.99
3000 13.89 235 2.1 6.85 2.86 0.14
4 0.02 235 1.6 0.01 0.00 3.00

e-Al

Voltage
Load in Load Length Voltage % Voltage
drop
(Watts) Current (A) (m) drop in L drop
/A /m
540 0.84 230 25.1 4.82 1.16 1.84 0.8424
1080 1.67 470 15.8 12.41 2.99 0.01
2160 3.34 600 10.5 21.06 5.07 -2.07
2160 3.34 550 6.3 11.58 2.79 0.21
10000 15.48 470 3.9 28.37 6.84 -3.84 3150
10000 15.48 470 2.5 18.18 4.38 -1.38 5,760.00
10000 15.48 470 1.8 13.09 3.15 -0.15
3060 4.74 5 1.3 0.03 0.01 2.99

e-Cu

Voltage
Load in Load Length Voltage % Voltage
drop
(Watts) Current (A) (m) drop in L drop
/A /m
3060 4.74 350 25 41.44 9.9849219 -6.98
3060 4.74 350 16 26.52 6.39035 -3.39
2060 3.19 350 9.5 10.60 2.5543127 0.45
3060 4.74 350 6.3 10.44 2.5162003 0.48
0 0.00 100 3.8 0.00 0 3.00
0 0.00 100 2.3 0.00 0 3.00