100% found this document useful (2 votes)
467 views70 pages

Sec Engineers Manual

A2 - A1 a1 - a2 C B c 19 > Transformer Protection Dy 11 4. Draw B Phase Windings A a b

Uploaded by

Prathap Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
467 views70 pages

Sec Engineers Manual

A2 - A1 a1 - a2 C B c 19 > Transformer Protection Dy 11 4. Draw B Phase Windings A a b

Uploaded by

Prathap Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

DOCUMENT TITLE :

Power System Protection Training Manual for SEC


Engineers & Technicians

VOLUME-2
CONTRACTOR CONSULTANT

Saudi Engineering Group International DAR Engineering


Saihati Building, King Abdulaziz St. Alfanar Building, Salman Al-faresi
P.O. Box 5289 St.
Dammam 31422 PO Box 13103, Dammam 31493

28/11/2012 0 Issued for approval Kailash.S Johnson.T Yogesh.K


DATE
REV REVISION DESCRIPTION PREPARED BY REVIEWED BY AUTHORIZED BY
DD/MM/YY
DOCUMENT NO: DG-294 / SEC / EL / 2476 (b)
JOB NO:DG-294
INDEX

CHAPTER No. DESCRIPTION

7 TRANSFORMER PROTECTION

8 GENERATOR PROTECTION

9 DIAGNOSTIC PROTECTION PROBLEMS

10 TESTING AND COMISSIONING OF PROTECTION SYSTEM


CHAPTER-7

Engineers and Designers ‫مھندسون ومصممون‬


Engineers and Designers ‫مھندسون ومصممون‬
1 > Transformer Protection
Transformer Fault Categories

 Winding and terminal faults


 Core faults
 Tank and transformer accessory faults
 On–load tap changer faults
 Abnormal operating conditions
 Sustained or uncleared external faults

2 > Transformer Protection


Transformer Faults

3 > Transformer Protection


Transformer Faults

1. Earth fault on H.V. external connections.


2. Phase to phase fault on H. V. external connections.
3. Internal earth fault on H.V. windings.
4. Internal phase to phase fault on H.V. windings.
5. Short circuit between turns H.V. windings.
6. Earth fault on L.V. external connections.
7. Phase to phase fault on L.V. external connections.

4 > Transformer Protection


Transformer Faults

8. Internal earth fault on L. V. windings.


9. Internal phase to phase fault on L.V. windings.
10. Short circuit between turns L.V. windings.
11. Earth fault on tertiary winding.
12. Short circuit between turns tertiary winding.
13. Auxiliary transformer internal fault.
14. Earth or phase to phase fault on L. V. connection of
auxiliary transformer.
15. Sustained system earth-fault.
16. Sustained system phase to phase fault.

5 > Transformer Protection


Sources of abnormal stress in a transformer

 overload
 system faults

 overvoltage
 Transient surge voltages
 Power frequency overvoltage
 Reduced system frequency

6 > Transformer Protection


Important Points to be considered for
Transformer Protection
 Line currents present on either side of star-delta transformers
will differ in phase and magnitude.
 Any sudden change in the energisation of the transformer will
produce an inrush magnetizing current into or out of one
winding. The inrush current arises because the core saturates
when temporary over fluxing occurs.
 Delta connected windings do not provide a zero sequence path
for the flow of earth fault current when an earth fault occurs on
the delta side.
 Tap changers used for voltage regulation purposes cause the
turns ratio to vary and hence the voltage and current
magnitudes to vary.
 The transformer inductance can form a resonant circuit with
the capacitance from a connected length of underground
power cable or overhead line producing a condition called
Ferro-resonance.

7 > Transformer Protection


Problems and possible form of protection

8 > Transformer Protection


Transformer Connections

9 > Transformer Protection


Transformer Protection (3)

I A2 Ø

V EP

A1

10 > Transformer Protection


Transformer Protection (4)

I A2 a2

V EP ES

A1 a1

11 > Transformer Protection


Transformer Protection (5)

IP A2 a2 IS

V EP ES

A1 a1

12 > Transformer Protection


Transformer Connections

A a a2
C1 A2
a1
c1 b
A1 b1 b2
C2
C B1 B c2
B2
c

“Clock face” numbers refer to


A a position of low voltage phase -
A2 A1 a1 a2 neutral vector with respect to high
voltage phase - neutral vector.
B b
B2 B1 b1 b2 Line connections made to highest
numbered winding terminal available.

C c Line phase designation is same as


C2 C1 c1 c2 winding.

13 > Transformer Protection


Transformer Vector Groups

Group 1 Yy0
Dd0
0 Phase displacement Zd0
Group 2 Yy6
Dd6
180 Phase displacement Dz6

Group 3 Yd1
Dy1
30 Lag phase displacement Yz1

Group 4 Yd11
Dy11
30 Lead phase displacement Yz11

14 > Transformer Protection


Transformer Connections

 “Clock Face” numbers refer to position of low voltage phase-


neutral vector with respect to high voltage phase neutral vector
 Line connections made to highest numbered winding terminal
available
 Line phase designation is same as winding

Example 1 : Dy 11 Transformer

High Low Voltage


Voltage Windings
Windings
A Phase
Windings
A2 A1 a1 a2
B Phase
Windings
B2 B1 b1 b2
C Phase
Windings
C2 C1 c1 c2

Question : How to connect windings ?


15 > Transformer Protection
Dy 11

12

11

30°

16 > Transformer Protection


Dy 11

1. Draw Phase-Neutral Voltage Vectors

 Line Designation 
A a

30°

C B
c

17 > Transformer Protection


Dy 11

2. Draw Delta Connection

A
a

C B c

18 > Transformer Protection


Dy 11

3. Draw A Phase Windings

A
a
a2
A2

a1
b

A1

C B c

19 > Transformer Protection


Dy 11

4. Complete Connections (a)

A
a
a2

C1 A2
a1
c1 b
b1 b2
C2 A1

c2
B1 B2
C B
c

20 > Transformer Protection


Dy 11

4. Complete Connections (b)

A a
A2 A1 a1 a2

B b
B2 B1 b1 b2

C c
C2 C1 c1 c2

21 > Transformer Protection


Traditional Small Transformer
Protection Package
3.3kV

51 50
200/5 51 50 N N

1MVA
1500/5
3.3/0.44kV

51
N

64 1500/5

22 > Transformer Protection


Traditional Medium Transformer
Protection Package
11kV

51 50

64

1000/5 5MVA
11/3.3kV
51
N

64 1000/5

3.3kV
23 > Transformer Protection
Traditional Large Transformer
Protection Package
33KV

51 50
200/5

10MVA
33/11KV 51
N 87
600/5

64

600/5
5/5A

24 > Transformer Protection


CT Requirements

25 > Transformer Protection


CT requirements

 Proper CT stability during external fault and sensitivity


during internal faults for Transformer differential
protection.
 IEC class CT’s (PX & TPS) and ANSI CT’s (‘c’class) can
be used for differential protection.
 IEC class CT’s (TPS & PX) are used for high impedance
Differential restricted earth fault protection.
 Different relay manufacturer recommend CT requirement
for their protection relay and hence the CT’s are to be
sized as per the manufacture recommendation.

It is to be noted that when the through fault current


does not pass through the transformer the CTs are to
be sized accordingly.

26 > Transformer Protection


Phase Corrections

 Correct operation of transformer differential protection


requires that the transformer primary and secondary
currents, as measured by the relay, are in phase.

 If the transformer is connected delta/star, as shown in above


figure, balanced three phase through current suffers a phase
change of 30° which may lead to unbalance fault current.
Thus phase correction is recommended.
It is to be noted that in the present day scenario
Numerical relay are equipped with inbuilt phase
correction mechanism

27 > Transformer Protection


Phase comparison and zero sequence filtering
requirement

28 > Transformer Protection


Differential Protection

29 > Transformer Protection


Differential Protection

 Overall differential protection may be justified for larger


transformers (generally > 5MVA).
 Provides fast operation on any winding
 Measuring principle :
 Based on the same circulating current principle as the
restricted earth fault protection
 However, it employs the biasing technique, to maintain
stability for heavy through fault current
 Biasing allows mismatch between CT outputs.
 It is essential for transformers with tap changing facility.
 Another important requirement of transformer differential
protection is immunity to magnetising in rush current.

30 > Transformer Protection


Basic Considerations for Differential Protection

 Correction for possible phase shift across the


transformer windings (phase correction)
 Eeffects of the variety of earthing and winding
arrangements (filtering of zero sequence currents)
 Correction for possible unbalance of signals from current
transformers on either side of the windings (ratio
correction)
 Effect of magnetising inrush during initial energisation
 Possible occurrence of overfluxing

31 > Transformer Protection


Biased Differential Scheme

Differential
Current

I1 - I2
BIAS BIAS I OPERATE
I1 2

I1 - I2
RESTRAIN
OPERATE

I1 + I2 Mean Through
2 Current

32 > Transformer Protection


Differential Protection

PROTECTED ZONE
HV LV

Correct application of differential protection requires CT ratio and


winding connections to match those of transformer.
CT secondary circuit should be a “replica” of primary system.
Consider :
(1) Difference in current magnitude
(2) Phase shift
(3) Zero sequence currents
33 > Transformer Protection
Differential Connections

P1 P2 A2 A1 a1 a2 P2 P1

A B C

34 > Transformer Protection


Use of Interposing CT

P1 P2 A2 A1 a1 a2 P2 P1

S1 S2 S2 S1

S2 S1 P1 P2

R
R
R

Interposing CT provides :
 Vector correction
 Ratio correction
 Zero sequence compensation
35 > Transformer Protection
Integral Vectorial and Ratio
Compensation

Power transformer

Ratio
Numeric correction
Relay

Vectorial
correction
Differential
Virtual interposing CT element
Virtual interposing CT

36 > Transformer Protection


Differential Protection
15MVA
150/5 66kV / 11kV 800/5
P1 P2 A2 A1 a1 a2 P2 P1

S1 S2 S2 S1

Dy1

Given above: Need to consider -


(1) Winding full load current (2) Effect of tap changer (if any)
(3) C.T. polarities
Assuming no tap changer
Full load currents:- 66kV: 131 Amp = 4.37 Amps secondary
11kV: 787 Amp = 4.92 Amps secondary
However, require 11kV C.T.’s to be connected in ∆
Thus, secondary current = √3 x 4.92 = 8.52A
∴ RATIO CORRECTION IS REQUIRED
37 > Transformer Protection
Differential Protection
150/5 800/5
P1 P2 A2 A1 a1 a2 P2 P1

S1 S2 S2 S1

4.37A 4.92A
S1 S2 P1 P2

R (2.56) (5)
R
R

It is usual to connect 11kV C.T.’s in and utilise a / interposing C.T. (this


method reduces lead VA burden on the line C.T.’s)
Current from 66kV side = 4.37 Amp
Thus, current required from winding of I.C.T. = 4.37 Amp
Current input to winding of int. C.T. = 4.92 Amp
∴Required I.C.T. ratio = 4.92 / 4.37 = 4.92 / 2.52
√3
May also be expressed as : 5 / 2.56

38 > Transformer Protection


Effect of Tap Changer

e.g. Assume 66kV +5%, -15%


Interposing C.T. ratio should be based on mid tap position
Mid Tap (-5%) = 62.7 kV
Primary current (15 MVA) = 138 Amp
Secondary current = 4.6 Amp
∴ Interposing C.T. ratio required = 4.92 / 4.6
√3
( / )
= 4.92 / 2.66
May also be expressed as : 5 / 2.7
Compared with 5 / 2.56 based on nominal voltage

39 > Transformer Protection


Connections Check
Arbitrary Current Distribution

P1 P2 A2 A1 a1 a2 P2 P1

S1 S2 S2 S1

S2 S1 P1 P2

R
R
R

40 > Transformer Protection


Connections Check
Add Delta Winding Current

P1 P2 A2 A1 a1 a2 P2 P1

S1 S2 S2 S1

S2 S1 P1 P2

R
R
R

41 > Transformer Protection


Connections Check
Complete Primary Distribution

P1 P2 A2 A1 a1 a2 P2 P1

S1 S2 S2 S1

S2 S1 P1 P2

R
R
R

42 > Transformer Protection


Connections Check
Complete Secondary Distribution

P1 P2 A2 A1 a1 a2 P2 P1

S1 S2 S2 S1

S2 S1 P1 P2

R
R
R

43 > Transformer Protection


In-Zone Earthing Transformer
a1 a2
P1 P2 A1 A2 P2 P1

S2 S1

S2 S1 T2 T1 P1 P2

44 > Transformer Protection


In-Zone Earthing Transformer
a2
Alternative (1)
a1
P1 P2 A1 A2 P2 P1

S2 S1

S2 S1 P1 P2

45 > Transformer Protection


In-Zone Earthing Transformer
Alternative (2)

300/1

EARTHING
TRANSF.

900/1

TO DIFFERENTIAL
RELAY
46 > Transformer Protection
In-Zone Earthing Transformer
Alternative (3)

300/1

EARTHING
TXR

300/1

1/0.33

TO DIFFERENTIAL
RELAY
47 > Transformer Protection
Combined Differential and
Restricted Earth Fault Protection

A2 A1 a1 a2 P1 P2
S1 S2

P1
S1 P2
REF
S2 P1
P2
S1

S2
To differential relay

48 > Transformer Protection


Combined Differential and
Earth Fault Protection

 Using Summation Auxiliary Current Transformer

Restricted earth
fault relay
64
Bias windings

Differential relay
87 87 87
operating windings

49 > Transformer Protection


Z T1 X
PHASE a

PHASE b A

PHASE c A

N B
G G G

T1 BEF
T2
F

T3

J J J

T4
Rb
2 H H H
Rb
2
Rb
2

Ro Ro Ro

OVERALL DIFFERENTIAL
RELAY
50 > Transformer Protection
Three Winding Transformer

63MVA 25MVA
132KV 11KV
300/5 1600/5

50MV
A
33KV

1000/5

4.59 5.51 10.33


2.88 5 2.88
5

All interposing C.T. ratio’s refer to


common MVA base (63MVA)
51 > Transformer Protection
Traditional Use of Interposing CT
Dy1(-30°)

Yd11(+30°)

R
R
R

Interposing CT provides :
Vector correction
 Ratio correction
 Zero sequence compensation

52 > Transformer Protection


Protection of Auto-Transformer by
High Impedance Differential Relays

 (a) Earth Fault Scheme

87 High impedance
relay

53 > Transformer Protection


Protection of Auto-Transformer by
High Impedance Differential Relays

 (b) Phase and Earth Fault Scheme

a
b
c

87 87 87

54 > Transformer Protection


Specific problems for transformer
protection

55 > Transformer Protection


Transformer Magnetising
Characteristic

Twice
Normal
Flux

Normal
Flux

Normal
No Load
Current
No Load Current
at Twice Normal
Flux
56 > Transformer Protection
Magnetising Inrush Current
Steady State

+ Φm V
Φ
Im

- Φm

57 > Transformer Protection


Magnetising Inrush Current
Switch on at Voltage Zero - No residual flux

Im

m

Φ
V

58 > Transformer Protection


Factors affecting the magnitude and duration of the
magnetizing inrush current

 Residual flux – worst-case conditions result in the flux


peak value attaining 280% of normal value
 Point on wave switching
 Number of banked transformers
 Transformer design and rating
 System fault level

59 > Transformer Protection


Transformer Differential Protection
Effects of Magnetising Current

 Appears on one side of transformer only

 Seen as fault by differential relay

 Normal steady state magnetising current is less than


relay setting

 Transient magnetising inrush could cause relay to


operate

60 > Transformer Protection


Transformer Differential Protection
Effect of Magnetising Inrush

 SOLUTION 1 : TIME DELAY


 Allows magnetising current to die away before relay can
operate

 Slow operation for genuine transformer faults

61 > Transformer Protection


Transformer Differential Protection
Effect of Magnetising Inrush

 SOLUTION 2 : 2ND (and 5TH) HARMONIC RESTRAINT


 Makes relay immune to magnetising inrush
 Slower operation may result for genuine transformer faults
if CT saturation occurs

 Used in Most of the Numerical Relays

62 > Transformer Protection


Transformer Differential Protection
Effect of Magnetising Inrush

 SOLUTION 3 : GAP MEASUREMENT TECHNIQUE

 Inhibits relay operation during magnetising inrush


 Operate speed for genuine transformer faults unaffected by
significant CT saturation

63 > Transformer Protection


Typical Magnetising Inrush
Waveforms

A
B
C

64 > Transformer Protection


Detection of Typical
Magnetising Inrush (60Hz)

Bias
Differential Differential
comparator
Threshold

T1 = 3.33ms T2 = 16.66ms
Trip

65 > Transformer Protection


Restraint for Transformer
Magnetising Inrush

Bias Trip
Differential Differential
T1 = 3.33ms T2 = 16.66ms
comparator
Threshold

Differential input

Comparator output

T1

Trip
T2
Reset

66 > Transformer Protection


Operation for Transformer Faults

Bias Trip
Differential Differential
T1 = 3.33ms T2 = 16.66ms
comparator
Threshold

Differential input

Comparator output

T1

Trip
T2
Reset

67 > Transformer Protection

You might also like