General contents
Closer to you 6
Chain of values 8
General overview 11
Cubicle description 12
Instrument transformers 23
Applications 26
5
: 1 to 17.5 kV
Closer to you
offers you
Pre-engineered & adaptable solutions tailored to your specific requirements:
■ significantly reduced maintenance,
■ local support centres.
6
: 1 to 17.5 kV
Quality assurance and environment
Type test
The certification process of Schneider Electric guarantees that the product:
■ has been subjected to type testing according to standardised procedures
(EN 4500) in approved laboratories by independent organisations,
■ is in conformity with recognised international standards.
… a major asset
Certified quality ISO 9001
In each of its units, Schneider Electric integrates a functional organization
whose main role is to check quality and monitor compliance with standards.
This procedure is:
■ uniform throughout all departments,
■ recognized by many customers and approved organizations.
But above all, its strict application has allowed us to obtain the recognition
of an independent organization: the French Quality Assurance Association
(AFAQ).
The quality system for the design and manufacture of is
certified to be in conformity with the requirements of ISO 9001 and
ISO 9002 quality assurance standards.
… protected environment
Certified quality ISO 14001
As part of the company environmental policy, has been designed
with environmental protection in mind:
■ the materials used, insulators and conductors are identified easily,
separable and recyclable,
■ production sites are certified ISO 14001.
7
: 1 to 17.5 kV
Chain of values
… reliability
■ type tested cubicles,
■ 40 years of experience in the field of MV distribution,
■ wide base of installed MV switchgears all over the world,
■ existence in more than 130 countries,
■ the user benefits from the service expertise developed by Schneider
Electric in terms of:
Specifying Implementing
We help you to define your We oversee the completion and
solutions: selection guide, commissioning of your installation:
technical assistance, advice… design, cost optimization, guaranteed
performances and dependability,
commissioning tests, etc.
Modernizing Operating
We can bring the performance of We help run your daily operations in
your installation up to date: real time: maintenance contract,
installation audit, switchgear technical assistance, supply of
diagnosis, adaptation and replacement parts, corrective and
modification, end of life recycling, preventive maintenance, operation
etc. and maintenance training, etc.
… comprehensive solution
■ different types of CB technologies (vacuum and SF6),
■ wide range of performance / applications,
■ wide range of sensors and protection devices.
… simplicity
■ a user interface which is easily understood by everybody,
■ sepam-type protection units enabling on-site information retrieval
without any additional devices,
■ maintenance limited to simple, routine operating checks and cleaning,
■ easy installation due to identical civil engineering for all cubicles,
■ roll-on-floor CB type which enables simple operation and handling
without need for extra tools.
8
: 1 to 17.5 kV
Chain of values
… safety
Very comprehensive set of mechanical interlocks
prevents operator errors.
■ enhanced safety for your staff and operations,
■ operations are all performed from the front,
■ the earthing switch with making capacity.
… proximity
■ international quality level available locally,
■ targets to offer:
❐ fast response to requests for quotes and
tenders,
❐ optimal solutions with advanced features,
■ is based on a modular structure
for cubicle, designed to meet:
❐ local requirements,
❐ local standards.
… durability
structure is designed to:
■ withstand transportation conditions,
■ withstand operating under different
environmental conditions.
9
: 1 to 17.5 kV
In conformity to the latest IEC
10
: 1 to 17.5 kV
General overview
Busbar compartment
VT compartment
Control compartment
Cable compartment
C.B. compartment
Construction
■ all the metal surfaces are produced with anti-corrosion protected sheet
steel in accordance to ISO 5002,
■ paint: epoxy powder polymerized at high temperature,
■ non metallic components are self-extinguishing,
■ supports: cast resign with high electrical and mechanical performance,
■ has different degrees of protection (up to IP5X) in accordance
with IEC 60529.
11
: 1 to 17.5 kV
Cubicle description
Interlocking
The cubicle incorporates different interlockings to prevent incorrect
operation. secures operation to:
■ operate the circuit breaker,
■ rack in and out,
■ operate the earthing switch,
■ access to the VTs and fuses,
■ connection and disconnection the LV plug,
■ operation of the earthing truck.
12
: 1 to 17.5 kV
Cubicle description
Busbar compartment
With flat copper bars and no fragile parts, this compartment requires no special
maintenance under normal operating conditions.
■ partitioning between each cubicle,
Options:
■ insulated busbars and junctions.
Pressure relief
■ general structure is designed so that the expanding gas developed in
case of a short circuit shall be directed in a safe direction through special
flaps to ensure personal safety,
■ this provision (flaps) is provided for each compartment,
■ the used (flaps) are designed to maintain the cubicle protection degree IP.
13
: 1 to 17.5 kV
IF incomer and feeder
630 A, 1250 A and 2500 A
(1) Optional.
(2) On request, the cubicles can be delivered with double set of CTs.
(3) On request, the cubicles can be delivered for higher temperature up to 55 °C.
14
: 1 to 17.5 kV
C coupler - R riser
1250 A and 2500 A
D W
D W
■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■
■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■
< 50 < 50 < 50 < 50 < 50 < 50
< 60 < 60 < 60 < 60 < 60 < 60
< 65 < 65 < 65 < 65 < 65 < 65
IP 3X - IP 4X - IP 5X IP 3X - IP 4X - IP 5X IP 3X - IP 4X - IP 5X IP 3X - IP 4X - IP 5X
40 (3) 40 (3) 40 (3) 40 (3) 40 (3) 40 (3) 40 (3) 40 (3) 40 (3) 40 (3) 40 (3) 40 (3)
15
: 1 to 17.5 kV
MT metering and busbar earthing
630 A, 1250 A and 2500 A
Metering MT11
D W
Functions
■ Low voltage compartment
■ Voltage transformers
❐ withdrawable
■ Busbar earthing
❐ with earthing switch
(1)
■ Surge arrestors
(1)
■ Voltage presence indication system
(1) Optional.
(2) On request, the cubicles can be delivered for higher temperature up to 55 °C.
16
: 1 to 17.5 kV
LS load break switch
630 A
Dimensions:
■ Height (H) = 2120 mm D W
■ Depth (D) = 1273 mm
Switch-disconnector ■ Safety
❐ the switch may be in one of three positions: “closed”, “open” or “earthed”,
giving a natural interlocking system that prevents operator error. Moving
contact rotation is driven by a fast-acting mechanism that is independent of
the operator.
❐ the device combines the breaking and disconnecting functions.
❐ the SF6 enclosed earthing switch has a short-circuit making capacity
in compliance with standards.
■ Breaking principle
Contacts closed Contacts open Contacts earthed
❐ the outstanding qualities of SF6 gas are used to extinguish the electrical
arc. To increase the cooling of the arc, a relative movement is created
between the arc and the gas.
❐ the arc strikes when the fixed and moving contacts separate. The
F
combination of the current and a magnetic field created by a permanent
magnet causes the arc to rotate around the fixed contact, extending and
F cooling it until it is extinguished at current zero point.
F ❐ the distance between the fixed and moving contacts is then sufficient to
F S withstand the recovery voltage.
This system is both simple and dependable, and it provides improved
electrical endurance due to very low wear of contacts.
F
17
: 1 to 17.5 kV
Merlin Gerin products inside
Fig. 3 Fig. 4
18
: 1 to 17.5 kV
Merlin Gerin products inside
For the first time, a low voltage device control mechanism has been
integrated in a medium voltage circuit breaker. The Masterpact control
mechanism used on Evolis provides the benefits of a system that has
proven itself for over 10 years on hundreds of thousands of installations.
19
: 1 to 17.5 kV
Merlin Gerin products inside
Sepam series 20
Sepam series 80 The same sensors measure phase currents from 100 A to 1250 A.
20
: 1 to 17.5 kV
Merlin Gerin products inside
Sepam advantages
Sepam, a digital multi-functional protection unit, provides you with the
following advantages:
■ simple to use for better daily efficiency: user-machine interface (UMI)
which is ergonomic and which provides comprehensive & clear information
to operators.
■ simple to incorporate: flexibility and user friendliness of parameter setting
software and simplified tests.
■ money saving:
❐ integrating all functions required in one single, ready to use product,
❐ upgradeable solution, to spread the cost of investment over time.
21
: 1 to 17.5 kV
Schneider Electric products inside
Application flexibility
■ separate meter and display modules,
■ direct-connect up to 600 V: higher voltages with PTs.
Earthing Switch
An earthing switch is used to earth and short-circuit the cable ends before
work is performed on the cable. The switch incorporates the following:
■ designed for making capacity,
■ a fast-acting closing mechanism independent of the operator,
■ a locking device which will not allow it to be operated until the circuit
breaker has been opened and withdrawn,
■ 3 voltage capacitive dividers incorporated into the insulators which
support the terminal plates, and connected to three “neon” indicators
mounted on the front plate, to indicate whether the cables are live or dead.
Voltage Presence Indicating Systems are in compliance to IEC 61958.
22
: 1 to 17.5 kV
Instrument transformers
Voltage transformers
These voltage transformers are used to supply power to:
■ measuring, metering and monitoring devices,
■ relays or protective devices,
■ auxiliary LV sources for various types of switchgear, all these devices are
protected and insulated from the MV section.
The voltage transformers are withdrawable type and the energized part
is entirely encapsulated in an epoxy resin, which provides both electrical
insulation and mechanical strength.
The voltage transformers are with one insulated MV terminal, for connection
between neutral and phase conductors in three-phase systems.
Both the VT and the fuse are withdrawable from both sides.
Technical characteristics
■ primary voltage 3/3 up to 15/3 kV,
■ 1st secondary voltage available in different ratios with burden up to 50 VA
and accuracy class 0.5 (1),
■ 2 nd secondary voltage available with burden up to 50 VA and accuracy
class 0.5 or protection class 3P.
(1) For different burdens and accuracy classes, please consult us.
23
: 1 to 17.5 kV
Instrument transformers
Technical characteristics
■ single or double primary with rated current up to 2500 A,
■ the secondary current for measuring and protection can be of 1 A or 5 A,
■ class 0.2, 0.5 or 1 for measuring and 5P10, 5P15 or 5P20 for protection,
■ short time withstand current up to 40 kA / 3 sec,
■ winding burden up to 30 VA.
Technical characteristics
■ rated current 1250 A,
■ power-frequency withstand voltage test 38 kV / 1 min,
■ Impulse with stand test 95 kV,
■ rated voltage 17.5 kV,
■ short time withstand current 25 - 31.5 kA /3 sec.
LV ring CT
■ secondary current for measurement and protection can be of 1A or 5A
with different classes and burdens for measurement and protection.
24
: 1 to 17.5 kV
Instrument transformers
Technical characteristics
■ standard IEC 60044-8 (FDIS),
■ rated nominal primary current 100 A,
■ rated extended primary current 1250 A,
■ rated nominal secondary output 22.5 mV,
■ accuracy class for measuring 0.5,
■ accuracy class for protection 5P,
■ accuracy limit factor 500,
■ rated short time thermal current 50 kA x 1 sec - 40 kA x 3 sec,
■ highest voltage 17.5 kV,
■ rated power-frequency withstand voltage 42 kV,
■ rated lightning impulse withstand voltage 95 kV,
■ secondary plug RJ45 - 8 pts.
25
: 1 to 17.5 kV
Applications
Energy
optimizing the production, distribution and sale of
electricity
■ Our solutions, products and services cover:
❐ power generation and distribution
❐ energy metering and quality
❐ protection, supervision and monitoring
❐ management of electrical power
Infrastructure
optimizing availability, safety, and operating costs
■ Our solutions, products and services cover:
❐ water transmission and treatment
❐ passenger and freight transportation
❐ telecommunication infrastructure
❐ gas and oil infrastructure
❐ multi-site remote management
Industry
optimizing productivity, flexibility, safety & traceability
■ Our products and services solutions cover:
❐ machine control
❐ process automation
❐ electrical supply and distribution
❐ single or multi-site production data management
Buildings
optimizing comfort, safety, communication & operating
costs
■ Our products and services solutions cover:
❐ electrical supply and distribution
❐ utilities management: lighting, air conditioning, elevators, access control
❐ data exchange: Voice-Data-Image, power line carrier technology, radio
❐ multi-site remote management for office buildings, shopping malls and
stores, industrial buildings, ships, hotels, hospitals and schools, etc.
26
27
Schneider Electric NE Africa & Egypt Head Office Customer Support Center (CSC) As standard specifications
68, Tayaran st., Nasr City, Tel: (202) 40 10 899 Fax: (202) 26 20 473 and designs change from
Cairo, Egypt. [Link]@[Link] time to time, please ask for
P.O. Box 2658 El Horreya. confirmation of the
Tel : +202 40 10 119 information given in this
Fax: +202 26 18 908 Design & production: Communication - SEE publication.
[Link] Printing: Trust Advertising co.
SEE 62045 / E
28