Design calculation sheet

Project name: .Abu Dawood Date: 7/1/2024 Sheet no.: 1 1 Computed by:
Checked by:
Subject: smoke fan calculation Approved by:
Building Floor Smoke Extraction Flow Rate (Air Change Method):
Floor Area A = 5075 m2/floor
Floor Height h = 16 m NO. Air change 2
Q = 162,400 m3/hr a ‫كود البناء السعودى‬
= 95,585 CFM
at 2,300 fpm => f= 0.605 "/100 ft
Duct Length = 0m
Friction Loss through duct: = (Duct Length x 1.25 x 3.28 x f)
Friction Loss = 0.00 "
Total Static Pressure = (PD at Register + Friction Loss + fire Damper)*30%
= 0.20 + 0.00 + 0.2
= 0.52 " 129.48 Pa
Total Fan Static Pressure = 129 Pa = 0.5 IN WG
CONCLUSION
System Discription :
Exhaust Smoke Fans 95585 cfm
Number 8 Nos. Fans
Capacity 11,948 cfm (each)
pressure 0.5 IN WG
power 2.3 kw @μ=67%
Design calculation sheet
Project no: Date: 7/1/2024 Sheet no.: 1 1 Computed by:
Checked by:
Subject: smoke fan calculation OF BASEMENT 2 Approved by:
Building Floor Smoke Extraction Flow Rate (Air Change Method):
Floor Area A = 2375 m2/floor
Floor Height h = 3m NO. Air change 10
Q = 71,250 m /hr
3
a ‫كود البناء السعودى‬
= 41,936 CFM
at 2,300 fpm => f= 0.605 "/100 ft
Duct Length = 40 m
Friction Loss through duct: = (Duct Length x 1.25 x 3.28 x f)
Friction Loss = 0.33 "
Total Static Pressure = (PD at Register + Friction Loss + fire Damper)*30%
= 0.20 + 0.33 + 0.2
= 0.95 " 235.6536 Pa
Total Fan Static Pressure = 236 Pa = 0.9 IN WG
CONCLUSION
System Discription :
Exhaust Smoke Fans 41936 cfm
Number 2 Nos. Fans
Capacity 20,968 cfm (each)
pressure 0.9 IN WG
power 7.4 kw @μ=67%
Design calculation sheet
Project no: Date: 7/1/2024 Sheet no.: 1 1 Computed by:
Checked by:
Subject: Smoke Fan Calculation of Corridore Approved by:
Building Floor Smoke Extraction Flow Rate (Air Change Method):
Floor Area A = 90 m2/floor
Floor Height h = 3m NO. Air change 10
Q = 2,700 m /hr
3
a ‫كود البناء السعودى‬
= 1,589 CFM
at 2,300 fpm => f= 0.605 "/100 ft
Duct Length = 40 m
Friction Loss through duct: = (Duct Length x 1.25 x 3.28 x f)
Friction Loss = 0.33 "
Total Static Pressure = (PD at Register + Friction Loss + fire Damper)*30%
= 0.20 + 0.33 + 0.2
= 0.95 " 235.6536 Pa
Total Fan Static Pressure = 236 Pa = 0.9 IN WG
CONCLUSION
System Discription :
Exhaust Smoke Fans 1589 cfm
Number 1 Nos. Fans
Capacity 1,589 cfm (each)
pressure 0.9 IN WG
power 0.6 kw @μ=67%
Project no: Date: 7/1/2024 Sheet no.: 1 1 Computed by:
Checked by:
Subject: Smoke Fan Calculation of Corridore Approved by:
Building Floor Smoke Extraction Flow Rate (Air Change Method):
Floor Area A = 50 m2/floor
Floor Height h = 3m NO. Air change 10
Q = 1,500 m3/hr a ‫كود البناء السعودى‬
= 883 CFM
at 2,300 fpm => f= 0.605 "/100 ft
Duct Length = 20 m
Friction Loss through duct: = (Duct Length x 1.25 x 3.28 x f)
Friction Loss = 0.16 "
Total Static Pressure = (PD at Register + Friction Loss + fire Damper)*30%
= 0.20 + 0.16 + 0.2
= 0.73 " 182.5668 Pa
Total Fan Static Pressure = 183 Pa = 0.7 IN WG
CONCLUSION
System Discription :
Exhaust Smoke Fans 883 cfm
Number 1 Nos. Fans
Capacity 883 cfm (each)
pressure 0.7 IN WG
power 0.2 kw @μ=67%
Design calculation sheet
Project no: SARI HOTEL Date: 7/1/2024 Sheet no.: 1 1 Computed by:
Checked by:
Subject: smoke fan calculation OF KITCHEN Approved by:
Building Floor Smoke Extraction Flow Rate (Air Change Method):
Floor Area A = 21 m2/floor
Floor Height h = 3m NO. Air change 10
Q = 630 m /hr
3
a ‫كود البناء السعودى‬
= 371 CFM
at 2,300 fpm => f= 0.605 "/100 ft
Duct Length = 0m
Friction Loss through duct: = (Duct Length x 1.25 x 3.28 x f)
Friction Loss = 0.00 "
Total Static Pressure = (PD at Register + Friction Loss + fire Damper)*30%
= 0.20 + 0.00 + 0.2
= 0.52 " 129.48 Pa
Total Fan Static Pressure = 129 Pa = 0.5 IN WG
CONCLUSION
System Discription :
Exhaust Smoke Fans 371 cfm
Number 2 Nos. Fans
Capacity 185 cfm (each)
pressure 0.5 IN WG
power 0.0 kw @μ=67%
Design calculation sheet
Project no: SARI HOTEL Date: 7/1/2024 Sheet no.: 1 1 Computed by:
Checked by:
Subject: smoke fan calculation OF KITCHEN Approved by:
Building Floor Smoke Extraction Flow Rate (Air Change Method):
Floor Area A = 50 m2/floor
Floor Height h = 3m NO. Air change
Q = 1,500 m /hr
3
a ‫كود البناء السعودى‬
= 883 CFM
at 2,300 fpm => f= 0.605 "/100 ft
Duct Length = 0m
Friction Loss through duct: = (Duct Length x 1.25 x 3.28 x f)
Friction Loss = 0.00 "
Total Static Pressure = (PD at Register + Friction Loss + fire Damper)*30%
= 0.20 + 0.00 + 0.2
= 0.52 " 129.48 Pa
Total Fan Static Pressure = 129 Pa = 0.5 IN WG
CONCLUSION
System Discription :
Exhaust Smoke Fans 883 cfm
Number 2 Nos. Fans
Capacity 441 cfm (each)
pressure 0.5 IN WG
power 0.1 kw @μ=67%
NO. Air change 10
‫كود البناء السعودى‬

Damper)*30%
Design calculation sheet
Project no: SARI HOTEL Date: 7/1/2024 Sheet no.: 1 1 Computed by:
Checked by:
Subject: smoke fan calculation OF KITCHEN Approved by:
Building Floor Smoke Extraction Flow Rate (Air Change Method):
Floor Area A = 80 m2/floor
Floor Height h = 3m NO. Air change 4
Q = 960 m /hr
3
a ‫كود البناء السعودى‬
= 565 CFM
at 2,300 fpm => f= 0.605 "/100 ft
Duct Length = 0m
Friction Loss through duct: = (Duct Length x 1.25 x 3.28 x f)
Friction Loss = 0.00 "
Total Static Pressure = (PD at Register + Friction Loss + fire Damper)*30%
= 0.20 + 0.00 + 0.2
= 0.52 " 129.48 Pa
Total Fan Static Pressure = 129 Pa = 0.5 IN WG
CONCLUSION
System Discription :
Exhaust Smoke Fans 565 cfm
Number 2 Nos. Fans
Capacity 283 cfm (each)
pressure 0.5 IN WG
power 0.1 kw @μ=67%