Product datasheet

Specifications

PowerLogic HU250: Head Unit


communication gateway with cyber
security management
EMS59000

Main
Range of product PowerLogic T300

Range PowerLogic

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product name PowerLogic T300

Device short name HU250

Complementary
Product or component type Communication gateway

Communication port protocol DNP3 serial and TCP master station/outstation


Modbus serial and TCP client/server
Modbus RTU client/server
IEC 61850-8-1 controlling/controlled station
IEC 60870-5-104 controlling/controlled station
IEC 60870-5-101 controlled station

Communication port support ETHERNET 4 RJ45


RS485/RS232 1 RJ45
3G/4G 1 SMA

Data recording Event logs


4 data logs
1 ms time stamps
500000 events
Sequence of event recording

Memory capacity 16 MB

Time synchronisation protocol NTP


SNTP
GPS

Synchronisation time between 1 ms


inputs
Control type Illuminated push-button status:

Communication service Web server local WiFi:


Web server local Ethernet:
Web server remote WAN:

web services Event log


Alarm
Operating/Status report
Assistance in commissioning and operating the installation
Security/authority verification
Reports and diagrams

Programming language Calculation formula


ST (structured text)
IL (instruction list)
LD (ladder)
FBD (function block diagram)
SFC (sequential function chart)

9 Aug 2024 1
Number of inputs 8 digital multi-purpose conforming to IEC 61131-2 type 3
2 digital remote control
1 analog measure temperature

Number of outputs 2 digital (relay) multi-purpose:

[Us] rated supply voltage 12...48 V DC +/- 20 %

Power consumption in VA 3 VA

Environment
User language Multi-language

Electromagnetic compatibility Electrical fast transient/burst immunity test - test level: level 4 criteria A conforming to
IEC 61000-4-4
Conducted RF disturbances - test level: level 3 criteria A conforming to IEC
61000-4-6
Conducted disturbance emission - test level: level 4 criteria A conforming to IEC
61000-4-16
100 kHz damped oscillating wave - test level: level 3 criteria A conforming to IEC
61000-4-12
Radiated radio-frequency electromagnetic field immunity test - test level: level 4
criteria A conforming to IEC 61000-4-3
Immunity to voltage dips criteria A conforming to IEC 61000-4-29
Electrostatic discharge - test level: level 4 criteria B conforming to IEC 61000-4-2
Surge immunity test - test level: level 3 criteria A conforming to IEC 61000-4-5
Magnetic field at power frequency - test level: level 5 criteria B conforming to IEC
61000-4-8
Conducted and radiated emissions class A conforming to EN 55022

Fixing mode Clip-in (DIN rail)

Type of installation Indoor


Outdoor in cabinet

IP degree of protection IP2X body: conforming to IEC 60529


IP4X front: conforming to IEC 60529

IK degree of protection IK07 conforming to IEC 62262

Relative humidity 5…95 % conforming to IEC 60068-2-30

Mechanical robustness Vibrations 10…2000 Hz 1 gn 10 cycles conforming to IEC 60068-2-6


Bumps 10 gn 16 ms 1000 bumps non energized conforming to IEC 60068-2-29
Shocks 11 ms 3 pulses in operation conforming to IEC 60068-2-27

Ambient air temperature for -40…85 °C


storage
Ambient air temperature for -40…70 °C
operation
Operating altitude 2000 m

Product certifications CE

Standards IEC 60255-27

Height 140 mm

Width 90 mm

Depth 140 mm

Net weight 0.55 kg

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 11.900 cm

Package 1 Width 19.100 cm

Package 1 Length 19.800 cm

2 9 Aug 2024
Package 1 Weight 765.000 g

Unit Type of Package 2 S04

Number of Units in Package 2 9

Package 2 Height 30.000 cm

Package 2 Width 40.000 cm

Package 2 Length 60.000 cm

Package 2 Weight 7.277 kg

9 Aug 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile End of Life Information