42 CJR 024723
42 CJR 024723
SVM-05010-2
SERVICE MANUAL
AIR CONDITIONER
SPLIT WALL TYPE
42CJR024-723 / 38CJR024-723
42CJR018-723 / 38CJR018-723
42TAR024X-723 / 38TAR024X-723
42TAR018-723 / 38TAR018-723
42HNR024-713 / 38HNR024-713
42HNR018-713 / 38HNR018-713
CONTENTS
1. SPECIFICATIONS
2. CONSTRUCTION VIEWS
2-1 Indoor Unit (42CJR024-723, 42TAR024X-723, 42TAR018-723)
2-2 Outdoor Unit (42CJR018-723, 42HNR018-713, 42HNR024-713)
2-3 Outdoor Unit (38CJR024-723, 38TAR024X-723, 38TAR018-723, 38HNR024-713)
2-4 Outdoor Unit (38CJR018-723)
2-5 Outdoor Unit (38HNR018-713)
3. WIRING DIAGRAM
3-1 42CJR024-723 / 38CJR024-723, 42TAR024X-723 / 38TAR024X-723
3-2 42CJR018-723 / 38CJR018-723
3-3 42TAR018-723 / 38TAR018-723
3-4 42HNR018-713 / 38HNR018-713
3-5 42HNR024-713 / 38HNR024-713
4. SPECIFICATION OF ELECTRICAL PARTS
4-1 Indoor Unit (42CJR024-723, 42CJR018-723, 42TAR024X-723, 42TAR018-723)
4-2 Indoor Unit (42HNR024-713, 42HNR018-713)
4-3 Outdoor Unit (38CJR024-723, 38TAR024X-723)
4-4 Outdoor Unit (38CJR018-723)
4-5 Outdoor Unit (38TAR018-723)
4-6 Outdoor Unit (38HNR024-713)
4-7 Outdoor Unit (38HNR018-713)
5. REFRIGERATION CYCLE DIAGRAM
5-1 42CJR024-723 / 38CJR024-723, 42TAR024X-723 / 38TAR024X-723
5-2 42HNR024-713 / 38HNR024-713
5-3 42CJR018-723 / 38CJR018-723
5-4 42TAR018-723 / 38TAR018-723
5-5 42HNR018-713 / 38HNR018-713
6. CONTROL BLOCK DIAGRAM
6.1 42CJR024-723, 42CJR018-723, 42TAR024X-723, 42TAR018-723
6.2 42HNR024-713, 42HNR018-713
7. OPERATION DESCRIPTION
7-1 Outline of Air Conditioner Control
7-2 Description of Operation Circuit
7-3 High-Temperature Limit Control
7-4 Low-Temperature Limit Control
7-5 Defrost Operation
7-6 Auto Restart Function
7-7 Filter Check Lamp
–1–
FILE NO. SVM-05010
8. INSTALLATION PROCEDURE
8-1 Safety Cautions
8-2 Installation Diagram of Indoor and Outdoor Units
8-3 Installation
8-4 Indoor Unit
8-5 Outdoor Unit
8-6 How to Set Remote Control Selector Switch
8-7 Others
9. TROUBLESHOOTING CHART
9-1 Troubleshooting Procedure
9-2 Basic Check Items
9-3 Primary Judgement
9-4 Self-Diagnosis by Remote Control (Check Code)
9-5 How to Diagnose Faulty Parts
9-6 Troubleshooting for Indoor Unit
9-7 Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire)
9-8 Troubleshooting for P.C. Board
9-9 Troubleshooting for Remote Control
10. PART REPLACEMENT
10-1 Indoor Unit
10-2 Outdoor Unit (38CJR024-723, 38TAR024X-723, 38TAR018-723)
10-3 Outdoor Unit (38CJR018-723)
10-4 Outdoor Unit (38HNR024-713)
10-5 Outdoor Unit (38HNR018-713)
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E - Parts Assy)
11-2 Indoor Unit
11-3 Outdoor Unit (38CJR024-723, 38TAR024X-723)
11-4 Outdoor Unit (38TAR018-723)
11-5 Outdoor Unit (38CJR018-723)
11-6 Outdoor Unit (38HNR024-713)
11-7 Outdoor Unit (38HNR018-713)
–2–
FILE NO. SVM-05010
1. SPECIFICATIONS
42CJR024-723 / 38CJR024-723 42TAR024X-723 / 38TAR024X-723
MODEL
ITEM Cooling
Capacity 220V 240V 220V
kW
6.40 6.45 6.40
Phase 1∅
Power source V 220 – 240 220
Hz 50
Power consumption W 2420 2510 2250
Power factor % 98 92 95
220V 240V 220V
R unning current A
0.3/10.9 0.3/11.1 0.3/10.5
Indoor/Outdoor
Starting current A 67
Moisture removal lit/h 2.7
Indoor (H/M/L) dB 45/41/37
Noise
Outdoor (220 – 240V) dB 56-57 56
Name of refrigerant R22
Refrigerant
Rated amount kg 1.70
Refrigerant control Capillary tube
Gas side size mm ∅15.88
Connection type Flare connection
Liquid side size mm ∅6.35
Interconnection Connection type Flare connection
pipe Maximum length 15*1
m
(One way) 25*2
Maximum height
difference m 10
–4–
FILE NO. SVM-05010
42HNR024-713 42HNR018-713
MODEL 38HNR024-713 38HNR018-713
Note : 2
Charge refrigerant according to the table below.
–6–
FILE NO. SVM-05010
2. CONSTRUCTION VIEWS
2-1. Indoor Unit (42CJR024-723, 42TAR024X-723, 42TAR018-723)
Back body
Front panel
998 208
Grille inlet
298
50
75
7
51
8
50
50
75 65
763.5
(For stud bolt ∅6)
450
(For stud bolt ∅8 − ∅10)
to ceiling
20 20
48
29
10
135
48
298
54 16
Wireless remote control
Installation
∅
40
65
65
100 100
∅
Plate outline
–7–
FILE NO. SVM-05010
2-2. Outdoor Unit (42CJR018-723, 42HNR018-713, 42HNR024-713)
Back body
Front panel
998 208
Grille inlet
298
50
75
7
51
8
50
50
75 65
763.5
(For stud bolt ∅6)
450
(For stud bolt ∅8 − ∅10)
to ceiling
20 20
48
29
10
135
48
298
54 16
Wireless remote control
Installation
∅
40
65
65
100 100
∅
Plate outline
–8–
Installation dimension
A ∅25 Drain outlet 600
120
A Detail Drawing 100 or 600 or
600 more more
50
68 52
63.8
Air inlet
340
340
27
100 or 600 or
340
∅12x18 hole Air outlet 4-∅12x18
more more
for ∅8 − ∅10
600 140 anchor bolt
4-∅12x18 holes 23 310
(for ∅8 − ∅10 anchor bolt)
Electric
Parts cover
Handle
690
Liquid side
(Flare ∅6.35)
–9–
Gas side
(Flare ∅15.88)
88
Service Port
880 74 12 340 (pitch) 12
364
Handle
2-3. Outdoor Unit (38CJR024-723, 38TAR024X-723, 38TAR018-723,38HNR024-713)
FILE NO. SVM-05010
FILE NO. SVM-05010
2-4. Outdoor Unit (38CJR018-723)
310
36
102
302
∅6 Hole R15
310
302 ∅6 Hole
302
36
310
B
∅30 Drain outlet
2-∅11x14 Hole
(For ∅8-∅10 anchor bolt)
COVER PV
Z
530
265
270
600 90 310
780 62 330
Electrical
part cover
Liquid side
(Flare ∅6.35)
Gas side
(Flare ∅12.7)
120
13 Series
75
54
Z View
Service port
Installation dimension
600
100 or more Air inlet
600 or more
325
−10 −
A 120 Installation dimension
A Detail Drawing
600 600
100 or more
50 Air inlet
R10 600 or more
35
Air inlet
325
52
23
325
∅ 6 hole 600 or
100 or more more 4x∅11x14
∅ 11x14 hole Air for ∅8 − ∅10
outlet anchor bolt
8-∅6 holes
(for fixing outdoor unit)
Fan guard ∅ 25 Drain outlet
6-∅11x14 holes
Handle (for ∅8 − ∅10 anchor bolt)
2-5. Outdoor Unit (38HNR018-713)
Electric
Parts cover
Liquid side
538
Service Port (Flare ∅ 6.35)
– 11 –
Gas side
91 54 (Flare ∅ 12.7)
90 600 90 50
300 830 60 344
FILE NO. SVM-05010
FILE NO. SVM-05010-1
3. WIRING DIA GRAM
3-1. 42CJR024-723 / 38CJR024-723, 42TAR024X-723 / 38TAR024X-723
COLOR IDENTIFICATION
BRW : BROWN
RED : RED
WHI : WHITE Louver
YEL : YELLOW motor
BLU : BLUE Infrared rays receive
and Indication parts
BLK : BLACK
GRY : GRAY 1 2 3 4 5 6 7 8 9 10
PNK : PINK 1 2 3 4 5 6 7 8 9 10 CN25
ORN : ORANGE
GRN : GREEN
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
WHI
BRW
ORN
RED
PNK
BLU
YEL
GRN&YEL : GREEN & YELLOW
6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 10
6 5 4 3 2 1 CN07 1 2 3 4 5 6 7 8 9 10 CN13
BLK P04
DSA Varistor
F01
6.3A 250V Power supply
Varistor
circuit
Control
Fan motor
CN30
circuit
CN31
CN27
BRW
GRY
GRN&YEL
BLK
BLK
BLK
BLK
YEL
1 2 3 4 5 6 Thermo. Heat exchanger
1 2 3 4 5 6 sensor sensor
(TA) (TC)
TEMP FUSE
145 C
Indoor
terminal 1 3 INDOOR
block 2
UNIT
OUTDOOR
TERMINAL L N i 1 2 3
BLOCK GRN&YEL
BLK
RED i
BLK
CHASSIS
RED
SPARK KILLER
A2 52C A1
RED
RED WHI
CAPACITOR RED BLK
RED
1/L1 2/T1
COMPRESSOR
5/L3 6/T3
COMPRESSOR TERMINAL
MAGNETIC CONTACTOR
− 12 −
3-2. 42CJR018-723 / 38CJR018-723 FILE NO. SVM-05010-1
COLOR IDENTIFICATION
BRW : BROWN
RED : RED
WHI : WHITE Louver
motor
YEL : YELLOW Infrared rays receive
BLU : BLUE and Indication parts
BLK : BLACK
1 2 3 4 5 6 7 8 9 10
GRY : GRAY 1 2 3 4 5 6 7 8 9 10 CN25
PNK : PINK
ORN : ORANGE
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
WHI
BRW
ORN
RED
GRN : GREEN
PNK
BLU
YEL
GRN&YEL : GREEN & YELLOW
6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 10
6 5 4 3 2 1 CN07 1 2 3 4 5 6 7 8 9 10 CN13
BLK P04
DSA Varistor
F01
6.3A 250V Power supply
Varistor
circuit
Control
Fan motor
CN30
circuit
CN31
CN27
BRW
GRY
GRN&YEL
BLK
BLK
BLK
BLK
YEL
1 2 3 4 5 6 Thermo. Heat exchanger
1 2 3 4 5 6 sensor sensor
(TA) (TC)
TEMP FUSE
145 C
Indoor
terminal 1 2 3
block
INDOOR
UNIT
OUTDOOR
UNIT
POWER SUPPLY
220 − 240 V ~ 50 Hz
OUTDOOR
TERMINAL L N i 1 2 3
BLOCK GRN&YEL
BLK
BLK
RED
BLK
GRN&YEL
i
BLK RED RED
CHASSIS
SPARK KILLER
GRY
R S T
A1 (or A)
MAGNETIC
CONTACTOR
A2 (or B)
U V W
CAPACITOR CAPACITOR
RED RED
S WHI
WHI C RED BLK
PNK BLK
R
FAN MOTOR
COMPRESSOR
C
S R
COMPRESSOR TERMINAL
– 13 –
FILE NO. SVM-05010-1
3-3. 42TAR018-723 / 38TAR018-723
COLOR IDENTIFICATION
BRW : BROWN
RED : RED
WHI : WHITE Louver
motor
YEL : YELLOW Infrared rays receive
BLU : BLUE and Indication parts
BLK : BLACK
1 2 3 4 5 6 7 8 9 10
GRY : GRAY 1 2 3 4 5 6 7 8 9 10 CN25
PNK : PINK
ORN : ORANGE
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
WHI
BRW
ORN
RED
GRN : GREEN
PNK
BLU
YEL
GRN&YEL : GREEN & YELLOW
6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 10
6 5 4 3 2 1 CN07 1 2 3 4 5 6 7 8 9 10 CN13
BLK P04
DSA Varistor
F01
6.3A 250V Power supply
Varistor
circuit
Control
Fan motor
CN30
circuit
CN31
CN27
BRW
GRY
GRN&YEL
BLK
BLK
BLK
BLK
YEL
1 2 3 4 5 6 Thermo. Heat exchanger
1 2 3 4 5 6 sensor sensor
(TA) (TC)
TEMP FUSE
145 C
Indoor
terminal 1 2 3
block
INDOOR
UNIT
OUTDOOR
TERMINAL L N i 1 2 3
BLOCK GRN&YEL
BLK
RED i
BLK
CHASSIS
RED
SPARK KILLER
A1 52C A2
RED
RED WHI
CAPACITOR RED BLK
RED
R U
COMPRESSOR
T W
COMPRESSOR TERMINAL
MAGNETIC CONTACTOR
− 14 −
FILE NO. SVM-05010-1
COLOR IDENTIFICATION
BRW : BROWN
RED : RED
WHI : WHITE
YEL : YELLOW Louver
motor
BLU : BLUE Infrared rays receive
BLK : BLACK and Indication parts
GRY : GRAY 1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 CN25
PNK : PINK
ORN : ORANGE
WHI
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BRW
ORN
RED
PNK
GRN : GREEN
BLU
YEL
GRN&YEL : GREEN & YELLOW 6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 10
6 5 4 3 2 1 CN07 1 2 3 4 5 6 7 8 9 10 CN13
BLK P04
DSA Varistor
F01
6.3A 250V +12 VDC
+5 VDC
WP-003
Serial Signal
BRW
GRY
YEL
CN23 circuit
1 2 3 4 5 6
1 2 3 4 5 6
TEMP FUSE
145 C
1 2 3
RY07
MAGNETIC
CONTACTOR BLU 1 1
CN11
R S T 3 3
(1/L1) (3/L2) (5/L3)
A1 YEL
CR11 RY05
52C
(2/T1) (4/T2) (6/T3) BLU
1 1
A2
CN02
U V W 3 3
BLU CR12
COIL FOR
4 WAY VALVE
CR13 RY06
CAPACITOR CAPACITOR
RED RED
CN03
C 1 3
1
S R S
WHI WHI
C
PNK BLK RED BLK BLK
R
COMPRESSOR TERMINAL
C OMP R E S S OR F AN MOT OR
−15 −
FILE NO. SVM-05010-1
3-5. 42HNR024-713 / 38HNR024-713
COLOR IDENTIFICATION
BRW : BROWN
RED : RED
WHI : WHITE
YEL : YELLOW
Louver
BLU : BLUE motor
BLK : BLACK Infrared rays receive
and Indication parts
GRY : GRAY
1 2 3 4 5 6 7 8 9 10
PNK : PINK 1 2 3 4 5 6 7 8 9 10 CN25
ORN : ORANGE
GRN : GREEN
WHI
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BRW
ORN
RED
PNK
BLU
YEL
GRN&YEL : GREEN & YELLOW
6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 10
6 5 4 3 2 1 CN07 1 2 3 4 5 6 7 8 9 10 CN13
BLK P04
DSA Varistor
F01
6.3A 250V +12 VDC
+5 VDC
WP-003
Serial Signal
BRW
GRY
YEL
CN23 circuit
1 2 3 4 5 6
1 2 3 4 5 6
TEMP FUSE
145 C
1 2 3
RY07
MAGNETIC
CONTACTOR BLU 1 1
CN11
R S T 3 3
(1/L1) (3/L2) (5/L3)
A1 YEL
CR11 RY05
52C
(2/T1) (4/T2) (6/T3) BLU
1 1
A2
CN02
U V W 3 3
BLU CR12
COIL FOR
4 WAY VALVE
CR13 RY06
CAPACITOR CAPACITOR
RED RED
CN03
C
1 3
1
S R
S
WHI WHI
C
PNK BLK RED BLK BLK
R
COMPRESSOR TERMINAL
COMPRESSOR FAN MOTOR
−16 −
FILE NO. SVM-05010
– 17 –
FILE NO. SVM-05010
– 18 –
FILE NO. SVM-05010
– 19 –
FILE NO. SVM-05010
− 20 −
FILE NO. SVM-05010
5. REFRIGERATION CYCLE DIAGRAM
5-1. 42CJR024-723 / 38CJR024-723, 42TAR024X-723 / 38TAR024X-723
T
Indoor unit
Evaporator
Cooling
0.39 m 0.49 m
(Connecting pipe) (Connecting pipe)
∅15.88 ∅6.35
Cross flow fan
O.D.:15.88 mm P O.D.:6.35 mm
Cooling
Condenser Dryer
Refrigerant
Propeller fan R22 1.70 kg
Cooling Outdoor unit Mark ( ) means check points of Gas Leak
Ambient temp.
Standard Surface temp. of heat conditions DB/WB
Fan speed
50 Hz pressure P exchanger interchanging (°C)
(indoor)
(MPaG) pipe T (°C)
Indoor Outdoor
Standard 0.4 11.0 High 27/19 35/24
Cooling High temperature 0.5 12.0 High 32/23 43/26*
Low temperature 0.3 1.0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
– 21 –
FILE NO. SVM-05010
T
Indoor unit
Evaporator
Cooling
O.D.:15.88 mm P O.D.:6.35 mm
Capillary tube
∅1.0 x 700 s
Heating Cooling Compressor
2JS386D5BB02
Refrigerant
Propeller fan R22 1.75 kg
Cooling Outdoor unit Mark ( ) means check points of Gas Leak
Heating
Ambient temp.
Standard Surface temp. of heat conditions DB/WB
Fan speed
50 Hz pressure P exchanger interchanging (°C)
(indoor)
(MPaG) pipe T (°C)
Indoor Outdoor
Standard 1.7 43.0 High 20/– 7/6
Heating High temperature 2.3 ~ 2.4 52.0 ~ 59.0 Low 27/– 24/18
Low temperature*1 1.2 36.0 High 20/– –10/–10
Standard 0.4 11.0 High 27/19 35/24
Cooling High temperature 0.6 12.0 High 32/23 43/26
Low temperature 0.3 1.0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
– 22 –
FILE NO. SVM-05010
5-3. 42CJR018-723 / 38CJR018-723
T
Indoor unit
Evaporator
0.39 m 0.49 m
(Connecting pipe) (Connecting pipe)
∅12.7 ∅6.35
Cross flow fan
O.D.:12.7 mm P O.D.:6.35 mm
Compressor PH340X3C-4KT1
Condenser
Refrigerant
Propeller fan R22 1.17 kg
Ambient temp.
Standard Surface temp. of heat conditions DB/WB
Fan speed
50 Hz pressure P exchanger interchanging (°C)
(indoor)
(MPaG) pipe T (°C)
Indoor Outdoor
Standard 0.4 11.0 High 27/19 35/24
Cooling High temperature 0.5 13.0 High 32/23 43/26
Low temperature 0.3 2.0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
– 23 –
FILE NO. SVM-05010
5-4. 42TAR018-723 / 38TAR018-723
T
Indoor unit
Evaporator
0.39 m 0.49 m
(Connecting pipe) (Connecting pipe)
∅15.88 ∅6.35
Cross flow fan
O.D.:15.88 mm P O.D.:6.35 mm
Compressor PH290X2C-4FT1
Condenser
Refrigerant
Propeller fan R22 1.47 kg
Ambient temp.
Standard Surface temp. of heat conditions DB/WB
Fan speed
50 Hz pressure P exchanger interchanging (°C)
(indoor)
(MPaG) pipe T (°C)
Indoor Outdoor
Standard 0.5 10.0 High 27/19 35/24
Cooling High temperature 0.6 12.0 High 32/23 43/26
Low temperature 0.3 2.0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
– 24 –
FILE NO. SVM-05010
5-5. 42HNR018-713 / 38HNR018-713
T
Indoor unit
Evaporator
Cooling
O.D.:12.7 mm P O.D.:6.35 mm
Capillary tube
∅0.8 x 400 s
Heating Cooling Compressor
2JS350D5A02
Capillary tube
∅2.0 x 600 s
Accumulator
Condenser
Dryer
Refrigerant
Propeller fan R22 1.17 kg
Cooling Outdoor unit Mark ( ) means check points of Gas Leak
Heating
Ambient temp.
Standard Surface temp. of heat conditions DB/WB
Fan speed
50 Hz pressure P exchanger interchanging (°C)
(indoor)
(MPaG) pipe T (°C)
Indoor Outdoor
Standard 1.7 45.0 High 20/– 7/6
Heating High temperature*1 2.1 ~ 2.3 49.0 ~ 58.0 Low 27/– 24/18
Low temperature 1.2 34.0 High 20/– –10/–10
Standard 0.4 10.0 High 27/19 35/24
Cooling High temperature 0.5 15.0 High 32/23 43/26
Low temperature 0.3 1.0 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
– 25–
FILE NO. SVM-05010
6. CONTROL BLOCK DIAGRAM
6.1 42CJR024-723, 42CJR018-723, 42TAR024X-723, 42TAR018-723
Indoor Unit Control Panel
M.C.U.
Functions Operation
Heat Exchanger Sensor Display
• Louver Control
Timer
Temperature Sensor • 3-minute Delay at Restart for Compressor
Display
Filter Sign
Infrared Rays Signal Receiver • Motor Revolution Control
Display
AUTO FAN
Initiallizing Circuit • Processing
Sign Display
Infrared (Temperature Processing)
Rays
Clock Frequency
Oscillator Circuit • Timer
Indoor
Fan Motor
Power Supply
Circuit Outdoor unit Louver ON/OFF Signal
Remote ON/OFF Signal
Control
Relay RY04
REMOTE CONTROL
Infrared Rays
Remote Control
Operation (START/STOP)
Temperature Setting
ON TIMER Setting
ECO
– 26–
FILE NO. SVM-05010
Timer
Temperature Sensor • 3-minute Delay at Restart for Compressor
Display
Filter Sign
Infrared Rays Signal Receiver • Motor Revolution Control
Display
PRE DEF
Initiallizing Circuit • Processing
Sign Display
Infrared (Temperature Processing)
Rays
Clock Frequency
Oscillator Circuit • Timer
Indoor
Fan Motor
Power Supply
Circuit Outdoor unit Louver ON/OFF Signal
Remote ON/OFF Signal
Control
Relay RY04
REMOTE CONTROL
Infrared Rays
Remote Control
Operation (START/STOP)
Temperature Setting
ON TIMER Setting
ECO
– 27 –
FILE NO. SVM-05010
7. OPERATION DESCRIPTION
7-1. Outline of Air Conditioner Control • Turning off the compressor and outdoor fan
when the outdoor unit receives the shutdown
This is a fixed capacity type air conditioner, which uses command
a AC motor for an indoor fan. The AC motor drive • Defrost control in heating operation
circuit is mounted in the indoor unit. And electrical (Temperature measurement by the outdoor heat
parts which operate the compressor and the outdoor exchanger and control for the four-way valve
fan motor, are mounted in the outdoor unit. and the outdoor fan motor) *Heat pump Model
The air conditioner is mainly controlled by the indoor only
unit controller. The controller operates the indoor fan
motor based upon commands transmitted by the 7-1-1. Louver control
remote control and transfers the operation commands (1) Vertical air flow louver
to the outdoor unit controller. Position of veritcal air flow louver is automatically
The outdoor unit controller receives operation controlled according to the operation mode.
commands from the indoor unit, and operates the Besides, position of vertical air flow louver can be
outdoor fan motor and the compressor. arbitrarily set by pressing [FIX] button.
(1) Role of indoor unit controller The louver position which is set by [FIX] button is
The indoor unit controller receives the operation stored in the microcomputer, and the louver is
commands from the remote control and executes automatically set at the stored position for the next
them. operation.
• Temperature measurement at the air inlet of the (2) Swing
indoor heat exchanger by the indoor If [SWING] button is pressed when the indoor unit
temperature sensor is in operation, the vertical air flow louver starts
• Temperature setting of the indoor heat swinging. When [FIX] button is pressed, it stops
exchanger by the heat exchanger sensor swinging.
• Louver motor control
• Indoor fan motor operation control 7-1-2. Indoor fan control (AC Fan motor)
• LED display control
• Transferring of operation commands to the (1) The indoor fan is operated by the stepless speed
outdoor unit change AC motor.
• Receiving of information of the operation status (2) For air flow level, speed of the indoor fan motor is
and judging of the information or indication of controlled in five steps (LOW, LOW+, MED, MED+
error and HIGH). If AUTO mode is selected, the fan
(2) Role of outdoor unit controller motor speed is automatically controlled by the
The outdoor unit controller receives the operation difference between the preset temperature and
commands from the indoor controller and the room temperature.
executes them.
• Compressor operation LOW+ = LOW+MED
Operations according 2
control
to the commands
• Operation control of MED+ = MED+HIGH
from the indoor unit
outdoor fan motor 2
Table 7-1-1
FAN TAP
Cooling UH H M+ M L+ L L- UL SUL/SL-
OPERATION Heat UH H M L+ L L- UL SUL/SL-
MODE Fan only H M+ M L+ L L-
Dry M+ M L+ L L- UL SUL
rpm 1300 1250 1200 1150 1050 1000 900 800 700 600
42HNR024-713
Air flow volume (m3/h) 873 830 790 750 667 625 543 461 380 300
rpm 1200 1150 1100 1050 950 900 800 700 600 500
42HNR018-713
Air flow volume (m3/h) 790 750 708 667 584 543 461 380 300 220
Model
42CJR024-723 rpm − 1300 1250 − 1150 − 1050 1000 900 800 700 −
42TAR024X-723 Air flow volume (m3/h) − 873 830 − 750 − 667 625 543 461 380 −
rpm − 1150 1100 − 1050 − 950 900 800 700 600 −
42CJR018-723
Air flow volume (m3/h) − 750 708 − 667 − 584 543 461 380 300 −
rpm − 1300 1250 − 1050 − 950 900 800 700 600 −
42TAR018-723
Air flow volume (m3/h) − 873 830 − 667 − 584 543 461 380 300 −
− 28 −
FILE NO. SVM-05010
7-2. Description of Operation Circuit 7-2-2. Cooling operation
([MODE] button on the remote control is set
(1) When turning on the breaker, the operation lamp to the cooling operation.)
blinks. This means that the power is on (or the
power supply is cut off.) (1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in
(2) When pressing [ ] button on the
Fig. 7-2-2.
remote control, receiving beep sounds from the
indoor unit, and the next operation is performed
(Preset temp.)
together with opening the vertical air flow louver. °C
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation ON ON
0.5
can be effected thereafter simply by pressing
(Room temp.)
[ ] button.
OFF OFF OFF ON
7-2-1. Fan only operation
([MODE] button on the remote control is set
to the fan only operation.) Preset 0
temp.
OPERATION
display lamp
Compressor
4-way valve
Outdoor fan
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C Fig. 7-2-2
(Room temp.) − (Preset temp.)
+1
+3
+0.5
M+
+2.5
Preset 0
*1
temp. +2
*1
+1.5
(Preset temp.: 24°C) *1
+1
+0.5
NOTE :
Preset 0
*1: The values marked with *1 are calculated and temp.
controlled by the difference in motor speed -0.5
between M+ and L–.
NOTE :
(2) The Hi POWER, ECO and COMFORT SLEEP
*1: The values marked with *1 are calculated and
operation cannot be set.
controlled by the difference in motor speed
Fig. 7-2-1 Setting of air flow [FAN:AUTO] between M+ and L–.
− 29 −
FILE NO. SVM-05010
7-2-3. Dry operation 7-2-4. Heating operation *Heat pump model only
([MODE] button on the remote control is set ([MODE] button on the remote control is set
to the dry operation.) to the heating operation.)
(1) The compressor, 4-way valve, outdoor fan and (1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in operation display lamp are controlled as shown in
Fig. 7-2-4. Fig. 7-2-6.
OFF:5min. OFF:4min.
OFF:5min. OFF:4min.
(Preset temp.)
ON:5min. ON:6min.
ON:5min. ON:6min.
°C
°C
+3 Preset 0
temp.
(Preset temp.)
OFF ON
(Room temp.)
+2
OFF ON OFF ON
+1
OFF OFF 0.5
Preset 0 ON ON
(Room temp.)
OPERATION
display lamp
temp.
Compressor
4-way valve
Outdoor fan
OPERATION
display lamp
Compressor
4-way valve
Outdoor fan
Fig. 7-2-4 Fig. 7-2-6
(2) The microprocessor turns the compressor on and (2) When [FAN] button is set to AUTO, the indoor fan
off at the regular intervals (4 to 6 minutes). While motor operates as shown in Fig. 7-2-7. When
the compressor is turning off, the indoor fan motor [FAN] button is set to LOW, LOW+, MED, MED+ or
operates in the SUPER LOW position. HIGH, the motor operates with a constant air flow.
The pattern of operation depending on the relation
between room temperature and preset °C
temperatures is shown in Fig. 7-2-5. Preset 0 L
temp. -0.5
-1
(Room temp.) − (Preset temp.)
R oom temp. *1
-1.5 *2
-2
Preset temp.+1
Preset temp. M+
-5.0
ON ON ON ON -5.5
Compressor H
[FAN AUTO]
Outdoor fan
OFF OFF OFF
– 30 –
FILE NO. SVM-05010
(3) The indoor heat exchanger restricts revolving 7-2-5. Automatic operation
speed of the fan motor to prevent a cold draft. The ([MODE] button on the remote control is set
upper limit of the revolving speed is shown in to the automatic operation.)
Fig. 7-2-8 and Table 7-2-1.
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the
Manual preset temperature and the room temperature at
(One of
46 34 AUTO 5 speed) which the automatic operation has started, as
45 33 shown in Fig. 7-2-9. The Fan only operation
continues until the room temperature reaches a
*4
L-H level at which another mode is selected.
33 21
32 20 (Up to
setting (2) Temporary Auto
SUL*3 speed) When the TEMPORARY button on the indoor unit
*2 A+4 A+4 is pushed, the preset temperature is fixed at 24°C
SUL*1
A-8 A-8
Stop
and the indoor unit is controlled as shown in
Fig. 7-2-9.
*6 *5
°C
Cooling operation
NOTES : The louver moves to the position same
*1: The fan stops for 2 minutes after thermostat-OFF. as Hi POWER operation.
+4
(Room temp.) − (Preset temp.)
*2: A is 24°C when the preset temperature is 24°C or
more and A is the preset temperature when it is Cooling operation
under 24°C.
0
*3: SUL means Super Ultra Low.
*4: Calculated from difference in motor speed Fan only operation
between SUL and HIGH. -1
*5 and *6:
42HNR024-713 42CJR024-713, 42TAR024X-723
42HNR018-713 42CJR018-713, 42TAR018-723
Table 7-2-1
– 31 −
FILE NO. SVM-05010
7-3. High-Temperature Limit Control 7-5-1. Defrost starting condition
*Heat pump model only A-Zone : If -10°C > Teo ≥ − 18°C, defrost will
The microcontroller detects the indoor heat exchanger start when.
temperature to prevent pressure of a refrigerating cycle Teo - Te ≥ 2.5°C at teat 20 sec or
from increasing excessively. ~ 30 min after operation.
The compressor and outdoor fan motor are controlled B-Zone : If Te ≤ −18°C, defrost start instantaneously
as shown in Fig. 7-4-1. (Suddenly) 00 ~ 25 min ofter operation
C-Zone : If -2ºC ≥ Teo ≥ −10°C defrost will start when
Compressor Outdoor fan Heat exchanger Teo - Te ≤ −3°C at least 20 sec or ~ 60 min
temp. after operation.
(°C)
OFF OFF
60
ON OFF
55
ON ON 52
Fig. 7-3-1
- 32 -
FILE NO. SVM-05010
7-6. Auto Restart Function 7-6-1. How to set auto restart function
The indoor unit is equipped with an automatic To set the auto restart function, proceed as follows:
restarting function which allows the unit to restart The power supply to the unit must be on; the function
operating with the set operating conditions in the event will not set if the power is off.
of power supply being accidentally shut down. The Push the [TEMPORARY] button located in the center
operation will resume without warning three minutes of the front panel continuously for three seconds.
after power is restored. The unit receives the signal and beeps three times.
This function is not set to work when shipped from the The unit then restarts operating automatically in the
factory. Therefore it is necessary to set it to work. event of power supply being accidentally shut down.
→
The unit starts to operate. The green lamp is on.
→
After approx. three seconds,
0
3S
The unit beeps three times The lamp changes from
and continues to operate. green to orange.
TEMPORARY button
If the unit is not required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it off.
TEMPORARY button
If the unit is required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it on.
• While this function is being set, if the unit is in • While the filter check lamp is on, the
operation, the orange lamp is on. [TEMPORARY] button has the function of filter
• This function can not be set if the timer operation reset button.
has been selected.
• When the unit is turned on by this function, the
louver will not swing even though it was swinging
automatically before shutting down.
– 33 –
FILE NO. SVM-05010
7-6-2. How to cancel auto restart function
To cancel auto restart function, proceed as follows:
Repeat the setting prodedure: the unit receives the
signal and beeps three times.
The unit will be required to be turned on with the
remote control after the main power supply is turned
off.
→
The unit starts to operate. The orange lamp is on.
→
After approx. three seconds,
0
3S
The unit beeps three times The lamp changes from
and continues to operate. orange to green.
TEMPORARY button
If the unit is not required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it off.
TEMPORARY button
If the unit is required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it on.
• While this function is being set, if the unit is in 7-7. Filter Check Lamp
operation, the orange lamp is on.
When the elapsed time reaches 1000 hours, the filter
7-6-3. Power failure during timer operation check lamp indicates. After cleaning the filters, turn off
the filter check lamp.
When the unit is in Timer operation, if it is turned off
because of power failure, the timer operation is 7-7-1. How to turn off filter check lamp
cancelled. Therefore, set the timer operation again.
Press [FILTER] button on the remote control.
OR push [TEMPORARY] button on the indoor unit.
Note:
If [TEMPORARY] button is pushed while the filter
check lamp is not indicating, the indoor unit will start
the Automatic Operation.
– 34 –
FILE NO. SVM-05010
8. INSTALLATION PROCEDURE
8-1. Safety Cautions
For general public use
Power supply cord of Outdoor unit shall be more than 4 mm2 (H07RN-F or 245 IEC66 : polychloroprene
sheathed flexible cord) or 3.5 mm2 (AWG-12).
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
• CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED
WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT
WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATORS,
FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY
CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R22) WITH ANY OTHER GASEOUS BODY
INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT,
THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT
RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE
INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS
IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
• Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock
switches.
• Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
• Before doing the electrical work, attach an approved plug to the power supply cord.
Also, make sure the equipment is properly earthed.
• Appliance shall be installed in accordance with national wiring regulations.
If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately.
CAUTION
• Exposure of unit to water or other moisture before installation could result in electric shock.
Do not store it in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Please read this installation manual carefully before installing the unit. It contains further important
instructions for proper installation.
– 35–
FILE NO. SVM-05010
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier
before installation. If you experience any problems, or if the installation is not accepted by the supplier, the
service agency will take adequate countermeasures.
– 36 –
FILE NO. SVM-05010
8-2. Installation Diagram of Indoor and Outdoor Units For the rear left and left
For installation of the indoor unit, use the paper pattern piping
on the back of the installation manual.
65 mm or more
Wall
Hook
1 Installation
170
or m mm
ore
plate
Insert the cushion between
the indoor unit and wall, and
lift the indoor unit for better
170
Hoo
k
or m mm
ore
operation.
Rear
Rear left
Bottom Left
3 Batteries
Saddle
Extension
600 mm or more
drain hose
(Not available, me drain hose polyethylene foam
me 0 mor
0 mo r provided by 10 r m (Not available,
10 r m o
o installer) provided by
100 installer)
100 m mo
mm
or m
Electric rm
o re o re
parts cover Electric
parts cover
o re o re
rm rm
m mo 600
mm
600
mm m mo 600
or m or m 600 mm
600 o re o re
or m
o re
– 37 –
FILE NO. SVM-05010
8-3. Installation
8-3-1. Optional installation parts
600 mm
Air inlet
120 mm
325 mm
52 mm
Air outlet
Fig. 8-3-1
600 mm
102 mm
73 mm
310 mm
64 mm
340 mm
7 mm
Air outlet
90 mm
600 mm
Drain outlet
Air outlet
Fig. 8-3-3
Fig. 8-3-2
• Secure the outdoor unit with the fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
• Use ∅8 mm or ∅10 mm anchor bolts and nuts.
– 38–
FILE NO. SVM-05010
8-3-2. Accessory and installation parts
Part Part Part
Part name (Q'ty) Part name (Q'ty) Par t name (Q'ty)
No. No. No.
1 4 7
2 5 8
Pan head wood screw
Wireless remote control x 1 Nano silver filter x 2 ∅ 3.1 x 16 l x 2
3 6
Others Name
Owner’s manual
Installation manual
– 39 –
FILE NO. SVM-05010
8-4. Indoor Unit 8-4-2. Cutting a hole and mounting installation
plate
8-4-1. Installation place
<Cutting a hole>
• A place which provides the spaces around the
indoor unit as shown in the above diagram. When installing the refrigerant pipes from the rear.
• A place where there is no obstacle near the air inlet
and outlet.
• A place that allows easy installation of the piping to
the outdoor unit.
• A place which allows the front panel to be opened.
CAUTION
• Direct sunlight to the indoor unit's wireless Pipe hole
m
5
Indoor unit 5
m
7m 65
55
Hook
*7m
45° 45 °
°
75
170
Remote Reception
Reception control range Remote control
120
range
* : Axial distance
1
Hook Installation
Fig. 8-4-1 Hook plate
Pipe hole Pipe hole
Thread
7 Mounting screw
Indoor unit Weight
Fig. 8-4-3
– 40 –
FILE NO. SVM-05010
<When the installation plate is directly mounted on 8-4-3. Electrical work
the wall>
1. The supply voltage must be the same as the rated
1. Securely fit the installation plate onto the wall by voltage of the air conditioner.
screwing it in the upper and lower parts to hook up 2. Prepare the power source for exclusive use with the
the indoor unit. air conditioner.
2. To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as NOTE:
illustrated in the above figure. • Wire type : More than 1.5 mm2 (H07RN-F or 245
3. Install the installation plate horizontally in the wall. IEC66) or 1.3 mm2 (AWG-16)
CAUTION CAUTION
When installing the installation plate with a • This appliance can be connected to the mains in
mounting screw, do not use the anchor bolt hole. the following way.
Otherwise the unit may fall down and result in Connection to fixed wiring :
personal injury and property damage. A switch or circuit breaker which disconnects all
poles and has a contact separation of at least
Installation plate 3 mm must be incorporate in the fixed wiring. An
<Keep horizontal direction>
approved circuit breaker or switches must used.
Anchor
bolt NOTE:
• Perform wiring works so as to allow a generous
Projection
wiring capacity.
5 mm dia. hole 15 mm or less
7 Mounting
screw
∅4 x 25s
s
Clip anchor
(local parts)
Fig. 8-4-4
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit falls.
NOTE:
• Secure four corners and lower parts of the
installation plate with 6 to 8 mounting screws to
install it.
– 41–
FILE NO. SVM-05010
8-4-4. Wiring connection
CAUTION
Air Inlet grille
• Be sure to refer to the wiring system diagram
labeled inside the front panel.
• Check local electrical cords and also any specific
Front panel
wiring instructions or limitations.
2
1
Connecting cable
abo
ut 1
5 cm
Terminal block
Fig. 8-4-6
Cord clamp
Earth
<Stripping length of the connecting cable>
line
Screw
Terminal
10
cover
10
50
40
Screw
Earth line
Connecting cable
Fig. 8-4-7
Fig. 8-4-5
NOTE:
<How to connect the connecting cable> Use stranded wire only.
• Wire type: More than 1.5 mm2 (H07RN-F or
Wiring of the connecting cable can be carried out 245 IEC66) or 1.3 mm2 (AWG-16)
without removing the front panel.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward
you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local
cords) into the pipe hole on the wall.
4. Take out the connecting cable through the cable
slot on the rear panel so that it protrudes about
15 cm from the front.
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws. Fig. 8-4-8
6. Tightening torque : 1.2 N·m (0.12 kgf·m).
7. Secure the connecting cable with the cord clamp. NOTE:
8. Fix the terminal cover, rear plate bushing and air Connect the earth line to the metallic part (i mark)
inlet grille on the indoor unit.
located at the side of 3P terminal.
Fig. 8-4-9
– 42 –
FILE NO. SVM-05010
8-4-5. Piping and drain hose installation To connect the pipe after installation of the unit (figure)
<In case of rightward piping> (To the forefront of flare)
43 mm
R 30 mm (Use polisin (polyethylene)
core or the like for bending pipe.)
Fig. 8-4-12
Fig. 8-4-10
NOTE:
<In case of downward piping>
If the pipe is bent incorrectly, the indoor unit may
• After scribing slits of the body-right by a knife or a unstably be set on the wall.
making-off pin, cut them by a pair of nippers or the After passing the connecting pipe through the pipe
like. hole, connect the connecting pipe to the auxiliary pipes
and wrap the facing tape around them.
CAUTION
• Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly. In case of leftward
piping and rear-leftward piping, bind the auxiliary
pipes (two) only with facing tape.
Slit (Body-right)
Indoor unit
Auxiliary pipes
Fig. 8-4-11 Connecting cable
Drain hose
<Left-hand connection with piping> Installation plate
– 43 –
FILE NO. SVM-05010
8-4-6. Indoor unit fixing 8-4-7. Drainage
1. Pass the pipe through the hole in the wall, and hook 1. Run the drain hose sloped downwards.
the indoor unit on the installation plate at the upper
hooks. NOTE:
2. Swing the indoor unit to right and left to confirm that • Hole should be made at a slight downward slant on
it is firmly hooked up on the installation plate. the outdoor side.
3. While pressing the indoor unit onto the wall, hook it
Do not form the
at the lower part on the installation plate. Pull the Do not rise the drain hose into
indoor unit toward you to confirm that it is firmly drain hose. a wavy shape.
Fig. 8-4-16
Push Push
Wall
Drain guide
Fig. 8-4-17
– 44 –
FILE NO. SVM-05010
8-5. Outdoor Unit 8-5-2. Refrigerant piping connection
1. Install the outdoor unit without anything blocking 15.88 1.0 to 1.5 2.0 to 2.5
the air discharging.
2. When the outdoor unit is installed in a place <Tightening connection>
exposed always exposed to strong wind like a Align the centers of the connecting pipes and tighten
coast or on a high storey of a building, secure the flare nut as far as possible with your fingers. Then
the normal fan operation using a duct or a wind tighten the nut with a spanner and torque wrench as
shield. shown in the figure.
3. In particularly windy areas, install the unit such
as to avoid admission of wind.
4. Installation in the following places may result in CAUTION
trouble. • Do not apply excess torque.
Do not install the unit in such places. • Otherwise, the nut may crack depending on the
• A place full of machine oil. conditions.
• A saline-place such as the coast.
• A place full of sulfide gas.
• A place where high-frequency waves are likely
to be generated as from audio equipment,
welders, and medical equipment.
Strong
wind
Fig. 8-5-1
– 45 –
FILE NO. SVM-05010
(Unit : N·m) 8-5-3. Evacuating
Outer dia. After the piping has been connected to the indoor unit,
Tightening torque
of copper pipe you can perform the air purge together at once.
∅6.35 mm 16 to 18 (1.6 to 1.8 kgf·m)
∅12.70 mm 50 to 62 (5.0 to 6.2 kgf·m) AIR PURGE
Evacuate the air in the connecting pipes and in the
∅15.88 mm 65 to 80 (6.5 to 8.0 kgf·m) indoor unit using a vacuum pump. Do not use the
refrigerant in the outdoor unit. For details, see the
• Tightening torque of flare pipe connections manual of the vacuum pump.
Flare at indoor unit side
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow
prevention function so that inside oil of the pump does
not flow backward into pipes of the air conditioner
when the pump stops.
1. Connect the charge hose from the manifold valve to
the service port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum
Flare at outdoor unit side
pump.
Fig. 8-5-4
3. Open fully the low pressure side handle of the
gauge manifold valve.
Half union Flare nut
4. Operate the vacuum pump to start evacuating.
Perform evacuating for about 15 minutes if the
Externally Internally piping length is 20 meters. (15 minutes for
threaded side threaded side 20 meters) (assuming a pump capacity of 27 liters
per minute.) Then confirm that the compound
Use a wrench to secure. Use a torque wrench to tighten. pressure gauge reading is –101 kPa (–76 cmHg).
5. Close the low pressure side valve handle of gauge
Fig. 8-5-5 manifold.
6. Open fully the valve stem of the packed valves
(both side of Gas and Liquid).
CAUTION
7. Remove the charging hose from the service port.
• KEEP IMPORTANT 4 POINTS FOR PIPING 8. Securely tighten the caps on the packed valves.
WORK
Compound pressure gauge Pressure gauge
(1) Take away dust and moisture (Inside of the
connecting pipes.)
-101 kPa (-76 cmHg)
(2) Tight connection (between pipes and unit)
Manifold valve
(3) Evacuate the air in the connecting pipes using
VACUUM PUMP. Handle Lo Handle Hi
(Keep full closed)
(4) Check gas leak (connected points)
Charge hose
Charge hose
Connecting pipe
Vacuum pump
adapter for
counter-flow
prevention
Vacuum
pump
Service port
(Valve core (Setting pin))
Packed valve at liquid side
Fig. 8-5-7
– 46 –
FILE NO. SVM-05010
TO CHARGE REFRIGERANT <Stripping length of connection cable>
No need to charge
15 m or less 15 m or less
refrigerant L N 1 2 3
L N 12 3
Gas side Tightening torque A
10
10
Gas side 65 to 80 N·m 5 mm
10
10
(∅15.88 mm) (6.5 to 8.0 kgf·m) 70 80
60 70
Gas side 50 to 62 N·m 4 mm
(∅12.70 mm) (5.0 to 6.2 kgf·m)
Earth line
Liquid side 16 to 18 N·m Same as
(∅6.35 mm) (1.6 to 1.8 kgf·m) Gas side
Power supply cord Connecting cable
9 to 10 N·m
Service port
(0.9 to 1.0 kgf·m) Fig. 8-5-8
– 47 –
FILE NO. SVM-05010
8-6. How to Set Remote Control Selector 2. Set the remote control selector switch with the
remote control
Switch
When two indoor units as installed in seperated rooms,
[B] is indicated on the liquid crystal display when
there is no need to change the selector switch.
setting remote control selector switch to B. [A] is
not indicated on the display even if the selector
<Remote control selector switch>
switch is set to A.
• When two indoor units are installed in the same
room or the adjacent two rooms, they may be 1) Load the remote control with the batteries.
controlled simultaneously with a single remote 2) Press the [CHECK] button using something with
control. To prevent this, set either unit and its sharp point. (The preset temperature on the remote
remote control to B setting. (Both units are set to A control changes to [00].)
setting before shipment.)
• The remote control signal is not recived when the 3) Press the [MODE] button while pressing the
indoor unit setting is different from the remote [CHECK] button, [B] is indicted at the right of the
control one. present temperature display.
1. Set the remote control selectors witch with the • To reset the switch to the [A] setting, press the
indoor unit. [MODE] button again while pressing the [CHECK]
button.
1) Turn the circuit breaker of the main power switch off
before setting the selector switch.
2) Remove the Air inlet grille and Front panel. (Refer to
Chapter 10-1, procedure 1 )
3) Open the Electrical part cover (Refer to chapter MODE TEMP. FAN
10-1, procedure 2 ), then cut the jumper (J90) AUTO AUTO B
COOL QUIET
with only the nippers. DRY
AUTO FAN
CAUTION TEMP.
Do not use any other sharp tools (such
as cutters, pliers, or the like). Such tools START/STOP
may cause breakage or damage. [MODE] button
TIMER
Fig. 8-6-2
– 48 –
FILE NO. SVM-05010
8-7. Others 8-7-3. Auto restart setting
8-7-1. Gas leak test This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
Electric parts cover
C
as before the power failure.
D
Information
Flare nut connections The product was shipped with Auto Restart function
(Indoor unit)
in the off position. Turn it on as required.
Valve stem cap
connection
Flare nut connections
A
<How to set the auto restart>
(Outdoor unit)
• Press and hold down the TEMPORARY button for
about 3 seconds. After 3 seconds, the electronic
B Service cap connection beeper makes three short beeps to tell you the Auto
Valve stem cap connection Restart has been selected.
• To cancel the Auto Restart, follow the steps
Fig. 8-7-1 described in the section Auto Restart Function of
the Owner’s Manual.
• Check the flare nut connections, valve stem cap
connections and service port cap connections for
gas leak with a leak detector or soap water.
TEMPORARY button
Fig. 8-7-2
– 49 –
FILE NO. SVM-05010
9. TROUBLESHOOTING CHART
9-1. Troubleshooting Procedure : 9-2-2. Incorrect cable connection between Indoor
and outdoor units
Follow the details of 9-2. Basic Check Items.
If there is no trouble corresponding to 9-2, check The indoor unit is connected to the outdoor unit with
whether or not there are faulty parts following 4 cables. Check that the indoor and outdoor units have
9-4. Self-Diagnosis by Remote Control. been properly connected with terminals assigned the
same numbers. If the connectors are not properly
connected, the outdoor unit will not operate normally,
9-2. Basic Check Items or OPERATION lamp and TIMER lamp will blink (5 Hz).
9-2.1 Power supply voltage
9-2-3. Program control
The line voltage must be AC 220 – 240 V. If it is not
within this range, the air conditioner may not operate The microcontroller operates as shown in Table 9-2-1
normally. to control the air conditioner. If there are any opera-
tional problems, check whether or not the problems
correspond to Table 9-2-1. If they correspond to the
Table, they are not problems with the air conditioner,
but they are indispensable operations to control and
maintain the air conditioner properly.
Table 9-2-1
No. Operation of air conditioner Descriptions
1 When the main power supply is turned The OPERATION lamp blinks to indicate that power is turned on. If the
on, the OPERATION lamp on the [START/STOP] button is pressed, the lamp stops blinking.
indoor unit blinks.
2 The indoor fan motor speed does not The indoor fan motor speed is automatically controlled in the Dry
change in the Dry operation. operation.
3 The compressor is not turned off even The compressor has a function that it is not turned off for 3 minutes
though the room temperature is in the after it is turned on even though the room temperature is in the range
range that the compressor is turned off. that the compressor is turned off.
4 The compressor is not turned on and In the Dry operation, the compressor is turned on and off automatically
off even though the thermo control is at the regular intervals, independent of the thermo control.
operated in the Dry operation.
*5 The PRE-DEF. lamp is indicated when The PRE-DEF. lamp is indicated during the Defrosting operation or if
the Heating operation starts. the indoor heat exchanger temperature is low when the Heating
operation starts. At this time, the indoor fan motor stops to prevent
cold air from blowing in the room.
*6 The outdoor fan motor stops in the When the indoor heat exchanger temperature is high, the outdoor fan
Heating operation. motor is stopped by the high-temperature limit control operation.
7 The compressor is not turned on even The compressor is not turned on in the restart delay timer (3-minutes
though the room temperature is in the timer) operation. It is also not turned on after the power supply is
range that the compressor is turned on. turned on because of this timer operation.
8 The operation mode changes in the In Automatic operation, the room temperature is detected all time
Automatic operation. for control fan speed and the operation mode is changed every
15 minutes according to difference between the room temperature
and the preset temperature.
9 The Auto Fan operation continues in the When the room temperature is in the range
Automatic operation. (Preset temperature ± 1°C), the Auto Fan operation is selected.
10 The ECO operation These operations do not work when the unit is in the Dry
operation does not work. operation or Auto Fan operation.
– 50 –
FILE NO. SVM-05010
9-3. Primary Judgement 9-3-2. Failure diagnosis
9-3-1. Role of indoor unit controller The indoor unit diagnoses the operation condition and
indicates the information of the self-diagnosis with the
The indoor unit controller receives the operation lamps on the display panel of the indoor unit.
commands from the remote control and executes
them.
• Temperature measurement at the air outlet of the
indoor heat exchanger by the indoor temperature
sensor
• Temperature setting of the indoor heat exchanger by
the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the outdoor
unit
Table 9-3-1
Lamps Self-diagnosis
A OPERATION lamp is blinking. (1Hz) Power failure (when the power supply is turning on)
B OPERATION lamp is blinking. (5Hz) Thermo sensor (TA) short or break
C OPERATION lamp is blinking. (5Hz) Heat exchanger sensor (TC) short or break
D OPERATION lamp is blinking. (5Hz) Indoor fan motor lock or failure
E OPERATION lamp is blinking. (5Hz) Indoor P.C. board failure
F OPERATION and TIMER lamps are blinking. Wrong wiring of connecting cable
(5Hz)
G OPERATION, TIMER and AUTO FAN lamps • Gas shortage or other refrigerant cycle trouble
are blinking. • Heat exchanger sensor open, break or short
• Overload relay or thermostat trouble of compressor
H OPERATION, TIMER and AUTO FAN lamps Cycle failure
are blinking.
– 51 –
FILE NO. SVM-05010
9-4. Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to H in Table
9-3-1, execute the self-diagnosis by the remote
control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the opera-
tion condition and indicate the information of the
self-diagnosis on the display of the remote control
with the check codes. If a fault is detected, all
lamps on the indoor unit will blink at 5Hz and it will
beep for 10 seconds (Pi, Pi, Pi....). The timer lamp
usually blinks (5Hz) during the self-diagnosis.
START/STOP
(2) Press [TEMP. 8] button.
SWING FIX FAN If there is no fault with a code, the indoor unit will
beep once (Pi) and the display of the remote
MODE RST CHK ECO
control will change as follows:
TIMER 00 01 02 1d 1E 22
ON OFF SET CLR
• Check the unit with all 35 check codes (00 to 22).
as shown in Table 9-4-1.
• Press [TEMP. 9] button to change the check
code backwards.
– 52–
FILE NO. SVM-05010
Table 9-4-1
Block level Diagnosis function
Check Check Unit Judgement and action
Block Symptom Condition
code code status
Indoor The indoor thermo sensor (TA) is Operation The lamp on the 1. Check the indoor thermo sensor (TA).
P.C. board defective. continues. indoor unit blinks 2. Check the indoor P.C. board.
Disconnection or short-circuit when error is
defected.
The indoor heat exchanger Operation The lamp on the 1. Check the indoor heat exchanger
sensor (TC) is defective. continues. indoor unit blinks sensor (TC).
Disconnection or short-circuit when error is 2. Check the indoor P.C. board.
defected.
The indoor fan motor or its circuit All off The lamp on the 1. Check the connector circuit of the
is defective. indoor unit blinks indoor fan motor (CN10).
when error is 2. Check the indoor fan motor.
defected. 3. Check the indoor P.C. board.
The part other than the above Operation The lamp on the 1. Check the indoor P.C. board.
parts on the indoor P.C. board is continues. indoor unit blinks (EEPROM and peripheral circuits)
defective. when error is
EEPROM access error defected.
IOL operation All off The lamp on the Overload operation of refrigerating cycle
indoor unit blinks
when error is
defected.
Cable The serial signals can not be Operation The lamp on the 1. In the case of the outdoor unit not
connection transmitted and received between continues. indoor unit blinks operating at all;
indoor and outdoor units. when error is • Check the crossover cable and
• The crossover wire is defected. connect it properly.
connected wrongly. • Check the outdoor P.C. board.
• The serial signal transmitting 2. In the case of the outdoor unit operating
circuit on the outdoor P.C. board normally;
is defective. • Check whether or not both of serial
• The serial signal receiving LED (Green) and serial LED (Orange)
circuit on the indoor P.C. board is blinking.
is defective. If the serial LED (Green) is not
blinking, check the outdoor P.C. board.
If the serial LED (Orange) is not
blinking, check the indoor P.C. board.
The operation command signals Operation The lamp on the If the operation command signals continue
are not transmitted from the continues. indoor unit blinks to be transmitted between 2 and 3 of the
indoor unit to the outdoor unit. when error is indoor terminal block, replace the outdoor
defected. And it P.C. board.
returns to the
normal condition
when recovering
from errors.
Outdoor The outdoor thermo sensor (TE) All off The lamp on the 1. Check the outdoor thermo sensor (TE).
P.C. board is defective. indoor unit blinks 2. Check the outdoor P.C. board.
Disconnection or short-circuit when error is
defected.
The outdoor heat exchanger (TD) All off The lamp on the 1. Check the outdoor heat exchanger
sensor is defective. indoor unit blinks sensor (TD).
Disconnection or short-circuit when error is 2. Check the outdoor P.C. board.
defected.
Other parts The reply serial signal has been Operation The lamp on the 1. Repeatedly turn the indoor unit on and
(including transmitted when starting the continues. indoor unit blinks off with the interval of approx. 10 to 40
compressor) unit, but stops being transmitted when error is minutes. (The check code is not
shortly after. defected. And it indicated during operation.) And supply
1. Compressor thermo operation returns to the gas. (Check gas leak.)
• Gas shortage normal condition 2. The indoor unit operates normally
• Gas leak when recovering during the check.
2. Instantaneous power failure from errors. If the reply serial signal continues to be
transmitted between 2 and 3 of the
indoor terminal block, replace the
outdoor P.C. board.
If the signal stops between them,
replace the indoor P.C. board.
The discharge temperature is All off The lamp on the 1. Check the heat exchanger sensor (TD).
over 120°C. indoor unit blinks 2. Gas purging
when error is
defected.
The IOL operation is defective. All off The lamp on the When turning on the unit, the normal
indoor unit blinks phase (RST) is detected but T-R waveform
when error is has not been detected for 120 seconds or
detected. more.
− 53 −
FILE NO. SVM-05010
9-5. How To Diagnose Faulty Parts
Operation
Check item
Item by symptoms
Does outdoor NO
unit operate?
YES
Are 1, 2 and 3 crossover NO Connect crossover
wires connected properly? wires properly.
YES
Are circuit NO
Circuit check/modification
wires normal?
YES
Replace TC sensor.
– 54–
FILE NO. SVM-05010
[09 Other cycle error] (1) (Heat pump model)
NO
Does compressor operate?
YES
Does inner
YES YES Check charged amount of refrigerant.
Is compressor overload relay Check defective overload.
turned off shortly? (in compressor) Check compressor.
operate?
NO
NO
Is TC sensor Failure Replace
NO
resistance value compressor.
(10 kΩ at 25°C) normal?
YES
Is circuit wiring NO
Replace TC Wiring check/modification
sensor. normal?
YES
YES Is TC sensor
Is outdoor P.C. NO Outdoor P.C. board Replace
disconnected from
board normal? is defective. P.C. board.
the sensing element?
NO YES
NO Does indoor
fan operate?
YES
NO Is connector YES
connected properly? Are filters clogged? Clean filters.
YES NO
Connect
connector
properly. Is TC sensor
NO Replace
resistance value
(10 kΩ at 25°C) normal? TC sensor.
NO
Is condenser normal? YES
YES
Replace
Is charged amount NO
condenser. Anti-freezing operation
of refrigerant normal?
– 55 –
FILE NO. SVM-05010
[0C Indoor TA sensor error]
YES
– 56 –
FILE NO. SVM-05010
[19 outdoor TD sensor error] (Heat pump model)
YES
Is protective NO NO
Are wires connected Connect wires to
controller such as discharge
to connector properly? connector properly.
thermostat normal?
YES
YES
Is overload relay normal? Unit operates normally.
NO
– 57 –
FILE NO. SVM-05010
9-6. Troubleshooting for Indoor Unit
Operation
9-6-1. Power can not be turned on. (The unit does not operate at all.)
Check item
<Primary check>
Conceivable principle
(1) Is the supply voltage normal? cause
(2) Is the connection to the AC output OK?
(3) Is the fuse (F01) blown? Measure
Item by symptoms
Turn off power
supply once, and 5
second later, turn it
on again.
NO Is OPERATION
lamp blinking?
YES
Does
Is it possible to transmission
turn on power mark on
supply by NO remote NO Remote control is
pressing control flash
defective.
[START/STOP] normally, and
button on remote is its signal
control? transmitted
properly?
YES Refer to 9-9
YES
ÒTroubleshooting for
Remote Control.Ó
Parts (R21,
Unit operates
Is fuse (F01) R22, SG01, Does the fan
YES normally.
of indoor C01, DB01, motor
YES
control board C02, connector
blown? M01 and IC04) between 1
NO are defective. and 2 short-
circuit?
Is voltage (DC NO
12V or 5V)
NO indicated on YES Replace main P.C.
Microcomputer is
rear of indoor board.
defective.
control board
normal?
Is DC 310 -
340V across NO
C63?
YES
YES YES
Replace motor.
– 58−
FILE NO. SVM-05010
9-6-2. Only the indoor fan does not operate
<Primary check>
(1) Is it possible to detect the power supply voltage (200 −240V) between 1 and 2 on the terminal block?
(2) Does the indoor fan motor operate in cooling operation?
Replace connecting
Replace the control the cable (or power cord),
Normal P.C. board. thermal fuse and
terminal block.
− 59 −
FILE NO. SVM-05010
9-6-3. Compressor does not operate.
<Primary check>
(1) Is the preset temperature higher than the room temperature in cooling operation?
(2) Is the crossover cable connected properly?
<Inspection procedure>
-Cooling only model-
– 60 –
FILE NO. SVM-05010
<Inspection procedure>
YES
NO Connect crossover
Is crossover cable normal?
cable properly.
YES
NO Rewire or replace
Are all of compressor cords normal?
defective cords.
YES
NO
Is capacitor for compressor normal? Capacitor is defective. Replace compressor.
YES
NO
Is overload relay normal? Overload relay is defective. Replace overload relay.
YES
NO
Does compressor start? Compressor is defective. Replace compressor.
YES
YES
Compressor is defective.
YES
− 61 −
FILE NO. SVM-05010
<Inspection pr ocedure>
- Heating model
AC 70-100V
Replace transformer
outdoor
P.C. board.
− 62 −
FILE NO. SVM-05010
YES
NO Rewire or replace
Are all of compressor cords normal?
defective cords.
YES
NO
Is capacitor for compressor normal? Capacitor is defective. Replace capacitor.
YES
NO
Is overload relay normal? Overload relay is defective. Replace overload relay.
YES
NO
Does compressor start? Compressor is defective. Replace compressor.
YES
Compressor is defective.
YES
Replace compressor.
– 63 –
FILE NO. SVM-05010
9-7. Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire)
9-7-1. Outdoor unit does not operate.
<Inspection procedure>
(1) Is the voltage between 1 and 2 of the indoor terminal block varied?
(2) Are signals from the indoor unit to the outdoor unit transmitted correctly based upon the following diagram?
NOTE:
Measure the voltage for 2 minutes and 30 seconds after starting the unit.
Heatpump model
Terminal block on indoor side
Red 3
White 2
Tester
1 Terminal block
White 2
Tester
1 Terminal block
Fig. 9-7-1
Normal condition : After start operated about 2 minutes and 30 seconds. Voltage between 2 and 3 of the
of the indoor's Terminal block should be equal AC 220 ~ 240V
Abnormal condition : Don't found voltage AC 220 ~ 240V from terminal block (0V)
<Confirmation procedure> Select one of 3 cases below and follow the procedure.
(1) The outdoor unit stops between 10 and 20 minutes passed after starting and it takes 10 minutes or more to
restart the unit.
(2) The outdoor unit stops once, it would not operate until the power is turned on again.
(3) The outdoor unit stops between 10 minutes to 1 hour after starting and a check code is indicated on the
remote control. (Check code 03-1E : Refer to Table 9-4-1.)
− 64−
FILE NO. SVM-05010
9-8. Troubleshooting for P.C. Board <Inspection procedure>
(1) If the P.C. board is detective, check for
9-8-1. How to check indoor P.C. board disconnection, burn or discoloration of the copper
foil pattern of the P.C. board.
<Cautions for handling P.C. board> (2) The P.C. board consists of the following 2 parts:
(1) When removing the front panel and the P.C. board, a. Main P.C. board parts:
be sure to turn off the power supply. Power relay, indoor fan motor drive circuit and
(2) When removing the P.C. board, hold the edge of control circuit, C.P.U. and peripheral circuits, buzzer
the P.C. board and do not apply force to the parts. drive circuit and buzzer.
(3) When connecting or disconnecting the connectors b. Infrared rays parts:
on the P.C. board, hold the housing. Do not pull at Infrared rays receiving circuit
lead wires.
Check the defects of the P.C. board with Table 9-8-1.
3 Press [START/STOP] button once to Check power supply voltage; 1. The wire of the relay coil (RY03)
start the unit. (Do not set the mode to 1. Between connector of Q25 and GND comes down or the relay drive
Fan Only or On-Timer operation.) (for relay coil (DC12V)) (Q25) is defective.
2. Between 1 and 2 of terminal block 2. CN27 or RY03 is connected
for connecting cable wrongly.
4 Shorten the line of the restart delay Check whether or not all lamps The lamps are defective or the
timer and start unit. (OPERATION, TIMER, FAN ONLY, ECO housing assembly (CN13) is defective.
and AUTO) are indicated for 3 seconds
and
– 65 –
FILE NO. SVM-05010
(1) Set the operation mode, temperature, and air flow MODE TEMP. FAN
AUTO AUTO
rate to be applied with the timer short mode. COOL QUIET
(2) Push the [CLR] button while keeping [CHK] button DRY
Hr.ON OFF
AUTO FAN
pushed. in this case, the check mode is released,
and the timer short mode is waited. TEMP.
(The status is kept even if [CHK] and [CLR] buttons
are released.) START/STOP
(3) Pushing [START/STOP] buttons sends operation
code + timer short code. SWING FIX FAN
(4) The timer short mode is released by only a trans-
MODE RST CHK ECO
mission. Therefore, repeat steps from (2) to
perform the timer short mode again. TIMER [CHK] button
– 66 −
FILE NO. SVM-05010
9-9. Troubleshooting for Remote Control
Is transmission NO
mark indicated?
YES
Press START/STOP
button.
YES
Batteries are
exhausted.
YES
Does radio sound
is affected by
remote control when NO
a signal is transmitted
at distance of 5 cm
from radio?
YES
Remote control
is defective.
P.C. board is
defective.
– 67 –
FILE NO. SVM-05010
10. PART REPLACEMENT
10-1. Indoor Unit
(4)
2 Electrical part 1) Remove the front panel with the procedure 1. (3) Drain guide
assembly 2) Remove the screw fixing the electrical part box. (5) screws
3) Remove the drain guide.
4) Remove the connector (5P) for the fan motor and 5P
the connector (6P) for the louver motor from the
6P
microcomputer assembly.
5) Remove the screw for the earth, and pull the
electrical part base toward you to remove it from
the main unit.
6) Pull out the TC sensor from the sensor holder.
(2) screws
(6) TC sensor
– 68 –
FILE NO. SVM-05010
No. Part name Procedures Remarks
3 Horizontal grille 1) Remove center 2 shafts of the horizontal grille from (1) Center shafts
the back body.
2) Remove left shaft of the horizontal grille from the
back body.
3) Remove the horizontal grille from the back body. (2) Left shafts
(4) 2 screws
5 Cross flow fan 1) Remove the front panel, electrical parts assembly, (3) Screws
horizontal grille and the heat exchanger with
procedure 4.
2) Loosen the set screw of the cross flow fan.
3) Remove 2 screws fixing the bearing base and the
back body.
4) Pull the cross flow fan toward you. (2) Set screw
– 69 –
FILE NO. SVM-05010
10-2. Outdoor Unit (38CJR024-723, 38TAR024X-723, 38TAR018-723)
4 screws ∅4 x 22L
– 70 –
FILE NO. SVM-05010
10-3 Outdoor Unit (38CJR018-723)
Upper
cabinet
Front
cabinet
Running capacitor
5 Spark killer 1) Perform the common procedure 1 for fan motor
2) Remove the fixing screw. (1 screw ∅ 4 x 10L)
3) Disconnect the lead wires from the terminal.
− 71 −
FILE NO. SVM-05010
10-4. Outdoor Unit (38HNR024-713)
4 screws ∅4 x 22L
– 72 –
FILE NO. SVM-05010
10-5 Outdoor Unit (38HNR018-713)
− 73−
FILE NO. SVM-05010-2
11. EXPLODED VIEWS AND PARTS LIST
11-1. Indoor Unit (E-Parts Assy)
402 43T60002 Terminal Block, 3P 411 43T69442 P.C. Board ASSY (42TAR024X,CJR024)
403 43T50004 Sensor, Heat Exchanger 10 kΩ 25°C 411 43T69443 P.C. Board ASSY (42CJR018-723)
404 43T69005 Sensor, Thermostat 10 kΩ 25°C 411 43T69445 P.C. Board ASSY (42TAR018-723)
405 43T69066 P.C. Board ASSY, WRS-LED 411 43T69448 P.C. Board ASSY (42HNR024-713)
MCC-819 411 43T69449 P.C. Board ASSY (42HNR018-713)
407 43T62003 Cord Clamp
– 74 −
FILE NO. SVM-05010-2
− 75−
FILE NO. SVM-05010
11-3. Outdoor Unit (38CJR024-723, 38TAR024X-723)
− 76 −
FILE NO. SVM-05010
11-4. Outdoor Unit (38TAR018-723)
− 77 −
FILE NO. SVM-05010
11-5. Outdoor Unit (38CJR018-723)
− 78 −
FILE NO. SVM-05010
11-6. Outdoor Unit (38HNR024-713)
− 79 −
FILE NO. SVM-05010
11-7. Outdoor Unit (38HNR018-713)
– 64 –