Download as PDF, TXT or read online on Scribd

RTS Thermostat

Installation instructions
Models
RTS1: Standard heating thermostat
RTS2: Heating thermostat with call for heat LED indicator
RTS3: Indoor frost thermostat
RTS4: *Volt free heating/cooling change over switch
RTS9 & 10: *Volt free heating/cooling changeover switch with call
for heating LED indicator

IMPORTANT NOTE
RTS thermostats are ELECTRONIC with a relay output.
Unless connected to a 230V mains supply the relay will
not operate, no 'click' will be heard and the call for heat
contact will remain open.

Location
Care should be taken to mount the thermostat in a position
which is not subject to direct sunlight or draughts. Preferably
it should be mounted on an inside wall about 1.5m (5ft)
above the floor in a position where it can respond to room
temperature but away from the direct influence of radiators
or other appliances giving off heat.
Note: If the thermostat is to be used as a frost protection
device it should be located in the coldest part of the premises.

Fixing
1. Loosen the securing screws, remove the wall-plate and, if
surface wiring is to be used, snap out the cable entry strip
on the bottom edge of the wall-plate with a pair of pliers.
2. Fix the wall-plate, terminals at the top, either direct onto a
flat wall using wall plugs and No 6 x 1” woodscrews or on a
flush mounting single conduit box using M 3.5 x 14 screws.
3. Complete the wiring to the wall-plate in accordance with
the relevant diagram shown overleaf in accordance with
I.E.T. regulations.
Note: The thermostat is for fixed wiring only and is double
insulated, the earthing continuity (loop) terminal is only
provided for convenience.
4. Plug the thermostat onto the wall-plate and tighten the
securing screws.
5. Before switching on the mains ENSURE THE CIRCUIT
FUSE IS 3A.

WARNING
Disconnect mains supply before fitting or removing from
wall-plate.
A switch having contact separation of at least 3mm in all
poles must be incorporated in the fixed wiring as a means
of providing full disconnection of the mains supply.

Setting
1. Set the desired room temperature on the control knob
against the setting mark.
2. The setting range may be limited or a particular setting
locked through the use of the mechanism to be found
under the control knob.
3. To adjust the limiters firstly set the thermostat to the
desired temperature and then carefully pull off the knob.
4. Lift and rotate the two limiting arms to re-position them in
the required notches.
5. Replace the knob with the previously set temperature
against the setting mark.

Technical data
Electrical supply: 230V ac 50Hz fused 3A
Double insulated (no earth required)
Temp. range: RTS1, 2, 4 & 9 10° to 30°C
RTS3 (Frost) 3° to 10°C
RTS10 14° to 30°C
Switch type: RTS 1, 2 & 3 S.P.S.T 2(1)A 230V ac live
output
RTS4, 9 & 10 S.P.D.T 2(1)A 230V ac volt free
Temp. sensor: Electronic

6490053_F [Link] 1 20/10/2020


Wiring (schematic)
Note: It is essential to make a neutral connection to terminal N.
RTS1, RTS2 and RTS3 RTS4, RTS9 and RTS10

N L 1 2 3 N L 1 2 3

N N Call for
230V AC 50HZ
230V AC 50HZ COM heat
fused 3A
fused 3A Call for Heating satisfied or
L
L call for cooling
heat

Note: Link between terminals L and 1 if mains voltage is


required on the thermostat switch.

Note that the output contacts are voltage-free* so


power needs to be put on to Terminal 1 either by linking
from Terminal L or from a separate supply with a 3A
fuse.
*Not SELV - Fixed wiring only, to comply with currect
IET regulations.

Information
The RTS room thermostat replaces earlier models of both
ACL and Drayton room thermostats subject to a maximum
load of 2(1)A 230V ac. The wiring conversion between
these models is:

ACL ACL Drayton RTS RTS


TS142 TA350 Roomstat 1,2 4, 9,
RT (E) &3 & 10
Live supply 1 – 1 L L
Neutral
4 – 4 N N
(accelerator heater)
Call for heat 2 3 2 3 3
Heating satisfied
– 2 3 – 2
(call for cooling)
Volt free
– 1 – – 1
switch common
Earth connection E 5 – – –

Conforms to the essential requirements of the following


Directives: Energy Class: I = 1%
Relevant EU Directives (According to EU
2014/35/EU Low Voltage Directive 811/2013, 812/2013
2014/30/EU Electromagnetic 813/2013, 814/2013) Schneider Electric
Compatibility Directive 35 Rue Joseph Monier
2011/65/EU RoHS Directive Schneider Electric France-92500
2012/19/EU WEEE Directive 401 Southway Drive Rueil Malmaison
Applied Standards Plymouth
EN60730-1, EN60730-2-9 PL6-6QT [Link]/contact

This product should not be disposed of with household waste.


Please recycle the products where facilities for electronic waste
exist. Check with your local authorities for recycling advice.
Room thermostats
Common

Satisfied
Demand
Neutral
Earth

Live

Make Model
Drayton RTS 1 & 2 N L 3
Drayton RTS 4, 5, 9 & 10 N L 1 3 2
Drayton Digistat 1 1 3 2
ACL Lifestyle PT271/371 N L 1 3 2
ACL Lifestyle TS 142 E 4 1 2
ACL Lifestyle TA 350 5 1 3 2
Drayton Digistat (old version) 4 1 2 3
Drayton RT & RTE 4 1 2 3
Danfoss Randall TP1 E N L 1 2
Danfoss Randall RT1. TP2, 3, 4 & 5 1 3 2
Danfoss Randall RD3, RD3A 4 1 2
Danfoss Randall RTC, RTM, RSR E N 3 1 2
Danfoss Randall R504 N 3 1 2
Honeywell 6060, 6061, 6063 2 1 3 4
Honeywell CT200 A B C
Horstman HRT 1 E 4 1 2
Landis & Gyr RAD 1 E 1 2 3
Potterton PRT 1 N L H
Potterton PRT 2 & 100 ST N TL H
Potterton PRT 100 DT N TL H C
Sunvic TLX 2259 E N L 1 2
Sunvic TLX 2356 E 3 1 2
Sopac TA 350 E 1 3 2
Sopac TA 351 E 4 1 3 2
Switchmaster SRT 2 5 1 3 2
Tower SS E 4 1 2