01 Electrical Systems
01 Electrical Systems
Electrical Systems
V. Open Neutral
AC C LOAD AC D LOAD
AC D LOAD E LOAD
AC
xo ↑
Circuit E is much better than circuit D because of the provision of additional safety means
(e.g. earth at load side, the addition of mechanical protection, access barrier, etc.) and the
provision of protective devices (e.g. fuse, circuit breaker, etc.).
&
ELEC4146 Building Services Electrical Installations Electrical Systems-6
Safety in Utilization of Electrical Energy (cont’d)
E LOAD AC
F LOAD
AC
2-pole breaker
Circuit F offers additional protection due to the use of the 2-pole breaker to disconnect
both live and neutral. Such a breaker must be designed as a “common trip” breaker.
trip at the
same time
ELEC4146 Building Services Electrical Installations Electrical Systems-7
Transmission System of CLP
E
back up
power station
[Link]
• In practice, we use high voltage (HV) for transmission and low voltage (LV) for distribution to the main
switchboard in a building. Step-down transformers at individual floors are therefore unnecessary.
• Prevention of electric shock may also be achieved by ELV (extra-low-voltage). ELV is mainly used for
small power applications.
outlet
Building. -> socket
⑳
8
HW -
↓ home, appartment
feeder
&
A2
1-
• Both radial and ring arrangements are common in HV distribution. In Hong Kong, radial arrangement
is more common in buildings, except for socket outlet circuits.
• Basically, most of the circuits in building services are in&
radial form. In Hong Kong, ring is recommended
for socket outlets only.
• In engineering, it is common to use a single line to represent a circuit. Such a diagram is called a Single-
Line Schematic Wiring Diagram. One copy of the schematic wiring diagram must be placed at an obvious
location (usually beside the entrance) inside the main switch room.
ELV (Extra Low Voltage) means a voltage normally not exceeding 50 V (RMS) alternating current (AC) -or-
120 V direct current (DC), between conductors or between a conductor and earth.
LV (Low Voltage) means a voltage normally exceeding ELV but normally not exceeding:
(a) Between conductors: 1000 V RMS AC -or- 1500 V (1.5 kV) DC; DC (V)
ACCRMS) (v)
(b) Between a conductor and earth: 600 V RMS AC -or- 900 V DC.
ELV 158 (120
1500
LV between
HV >600 >908
120° 120°
Three-phase Three-phase
Generator P2 Load
P3
N
• Constant power output (vector sum of three phases), compared to (sine-wave) pulsating power
in single phase.
W Wye(Y) Connection Delta( ) Connection
L1 L3
-
L2 220 V
0° N
220 V L1
220 V 120°
0° N 220 V
220 V 220 V
240° 120°
240°
L3 L2
• Increased robustness: Suppose you lose one phase for some reason.
=
380
In a 3-wire system, the entire system fails. However, in a 4 wire ·
system, the remaining two phases continue to operate except
now there is a larger current in the neutral conductor.
=> Easy fault detection and phase balance.
Neutral N.A. 0 0 0
hor
Phase 3 Lero
x+
Phase 2
120° 120°
120° L 120°
0° Phase 1 0° Phase 1
clockwise clockwise
240° 240°
120
6
Phase 3 2-120
-
Phase 2 S
Phase 1 -> Phase 2 -> Phase 3 Phase 1 -> Phase 3 -> Phase 2
Typically, Phase 1 serves as the reference for the other two phases (i.e., it has a phase angle of zero).
-220/esf2a) -jsint:
=20030+ jsino)
V2 (240
+
22021) 220) = j)
Question: Show that V12 3 V1n for a balanced 3-phase 4-wire system
= +
-
Note: V12 is the line-to-line voltage between Phase 1 and Phase 2. =220(1 j2) +
+
V1n is the line-to-neutral voltage (or phase voltage) for Phase 1. =220(2 j) +
(0)
53 (Vin) 53120 381,0530
=
=
=
38).
V12 = V1n V2 n V23 = V2n V3n V31= V3n V1n
V3n -V2n Let 12 be the phase angle of V12
V12
By using phasor representation, we can write
12
V1n V12 =V1n 0 V2 n 120
2n
&*
V12 = 220 cos(0 ) j sin(0 ) 220 cos( 120 ) j sin( 120 )
V2n
Emolet = 330 + j190.5256 V
=220) 1a
- - -
V12 = 381.051
=381,052-90
Hence, V12 = 3 V1n , where V1n 220 (assuming balanced load).
20(smo-jsinia)
1
tan 30
-
12
330
=
jz) 220(1)
=220(
+
-
2150
381.05
Exercise: Derive the magnitude and phase angle of V23 and V31.
=
E855 Gumcalfest
By using phasor representation, we can write
V23=V2n 120 V3n 120 ->
= 220 cos( 120 )
-
23 90
V23 381 90 V
V31 = 381.051
31 150
A V12
--
3V 30
bottom sign for negative sequence
top sign for positive sequence
V23 3V 90
bottom sign for negative sequence
top sign for positive sequence
V31 3V 150
bottom sign for negative sequence
(1) Linc
V2 n 220 60 vo:
Van
-90
5
=
(Ven(120)
V23 3V 90 (2) V2z
[30:
=53Ven
Finally, by plugging in the value of V2n from (1) into (4), we have
V23 3 220 60 30 381.05 90 V
Since V2 n 220 60 ,
&-
Ise V23 3 220 60 30 381.05 90 V
Fundamental currents of P2
the three phases are Neutral current contains no fundamental component,
balanced => sum to zero but the third harmonic is 300% of the phase current.
Third harmonic N
current
But, third harmonic currents of
the three phases coincide P3
Third harmonic current
[Link]
• Be aware of the fact that some of the older installations are still using the old colour code.
For the safety of yourself and others, we must be conversant with both the new and old
colour codes.
*An
• Even though it is called a 3-phase 4-wire system, we actually have a total
of 5 conductors, including the protective conductor.
• For safety and identification purposes, electrical
circuits and equipment must be clearly labeled
with sequence and warning. Refer to Code 4D
in the CoP for more details.
• Despite the earth has zero potential, yet electrical
currents in neutral. Hence, both neutral and phase
conductors are live conductors whenever the
control switch of the circuit is ON.
Compared with a low-voltage system serving the same kVA electrical load, a high-voltage system
carries the following advantages:
I
Power loss: F
Recall: P = V I
⑦• Smaller current to deliver the same amount of power => allowing the use of smaller conductors which
reduces cost and weight.
a
⑳ • Smaller IR (voltage) drop across transmission lines (important for energy delivery and utilization).
③ • Reduced power losses across transmission lines => higher conducting efficiency.
The first letter denotes the earthing arrangement at the source of energy (supply side).
T = direct connection of one or more points to earth
I = all live parts isolated from earth or one point connected to earth through an impedance
The second letter denotes the relationship of the exposed conductive parts of the installation to
earth (load side).
T = direct electrical connection of the exposed conductive parts to earth, independently of the
earthing of any point of the source of energy (independent earth)
N = direct electrical connection of the exposed conductive parts to the earthed point of the
source of energy. For AC, it is usually the neutral point (dependent earth)
Sometimes, a third and/or fourth letter are/is designated to each TN system to identify the
relationship of the electrical earth connection with neutral and protective conductors.
Examples: TN S
TN C
TN C S
= E
TT System
1 I
Evs
·
II
• Both HEC and CLP recommend the use of TT system for their low voltage supply.
In addition, C.O.P. also recommends the use of TN-S system under certain condition.
• In principle, the loads will draw the same current regardless of the types of systems.
However, the behavior of these systems under an earth fault can be significantly different.
TN-S TN-C IT
-No
-
-
I
,
...
IEF
IEF
- -
Zsource Zline
V phase
I EF
Z loop
O
• The complete path is called the earth fault loop. Thus,
the impedance of the path is called the earth fault loop
impedance (Zloop).
earth source Zprotective
• Note that Zs in CoP is equivalent to Zloop. impedance
-
i are ene
-
• Supply is earthed at the neutral point
2018-
Where the supply is taken directly from the electricity supplier’s transformer(s) within the premises in
which the installation is situated, the main earthing terminal of the installation should be bonded by a
conductor or through a common conductor to a bonding terminal provided by the electricity supplier at
the point of supply, for example, near the transit block or the main cable terminations on the incoming
circuit breakers.
ne
cable termination at the point of supply, the main earthing terminal of the installation should be bonded to
these exposed conductive parts via bonding terminal(s) provided by the electricity supplier.
trogen
sonductor
↑
#
EtFN-2
I
1
Fi
! -
*8
I -
*bonding
terminal.
By including the bonding conductor, the T-T system essentially acts like a T-N-S System.
(Ironically, some people still call it a T-T System).
suppliers
metering
suppliers
neintral -> cut out
Simply put, for generator used for temporary supply, only a single Earth is used for both supply and load.
Iphrase Ame
-
Z
loop
&
• The connection between the -
bonding conductor.
exposed
- -
conductive part and the supply earth is called
• Under normal operation, there is no current flowing across the bonding conductor, but
there could be unbalanced current on the neutral (N) wire (also known as working zero line).
T
between
Difference
and INS
I
TT tant ->
is
there
-> when thr
currant
-> large earth (TT]
(IN-3)
true
currenthe
conductor
->
large bending
IEF
Although the earth fault behavior in a TN-S is similar to that of a TT system, a substantial amount
of current flows through the bonding conductor (instead of through the true earth).
---
&
For TN-S system: Zloop,TN-S = Zsource + Zline + Zprotective
# ⑤
Zloop,TT = ZERS + Zsource + Zline + Zprotective + ZERL Zprotective
smaller
-
Any same
⑧ IEF
Why ERs/ZE
Iphese:
z
loop bigger
V phase TNS
-
bigger no
same
path
I protective alw
In other words, TN-S leads to a larger earth fault current. represent
the fault
me current return,
nord to consider I
&
- >
in close proximity to the switch room of a building.
-
Transformer Switch
Room Room
Bonding conductor is
only a few meters long
20
The protective bonding conductor (as recommended by CoP) between the two earths is short and has a much lower
- O
impedance than an earth resistance. Hence, this bonding conductor in TN-S lowers the overall earth fault loop impedance.
-
time
faster response C... larger
nex
·
the earth
against
perfe
TT System TN-S System
• Contrary to our intuition, a large earth fault current in TN-S is not necessarily a bad thing because a larger
fault current enables faster response of the protective devices (e.g. RCD, earth fault relays).
• The regulations governing the earth fault protection requirements between TT and TN-S are not identical.
In general, TT requirements are tougher (e.g. many RCDs are required). Yet, these additional safety measures
make TT systems safer and more robust against earth leakage protection.
• In short, there are pros and cons of TT and TNS.
0
-
• Earth fault has a higher power factor (closer to one) due to low inductance along the earth fault loop.
-
No long cables and/or bonding conductors are used. cost by
->
free
• Lower cost due to savings in bonding conductor materials. cas
Disadvantages:
tougher, regulation
a
• Earth fault relays and RCDs are frequently required. ->
-
• Separate earth at the load side incurs higher cost for consumers.
>
• TT may create step voltage. Step voltage is the voltage between
-
TT TN-S
• Exposed conductive parts of the load are connected to earth, i.e., a direct connection to the earth (in TT) or
an indirect connection to the direct connection to the earth at the source side (in TN-S).
E4
• In a building, non-electrical metal parts within&two meters are known as extraneous conductive parts
e.g. main water pipes, gas installation pipes, exposed metallic parts of structural framework, etc.
-
• Equipotential bonding is an electrical connection maintaining various exposed
Equipotential bonding
conductive parts and extraneous conductive parts at substantially the same potential.
In IT system, the supply is not earthed (i.e., isolated neutral), capacitive currents are present
in all installations. These capacitive currents are usually insignificant (compared to large
earth fault currents in TT and TN-S) unless the cables are very long.
&
• When earth fault occurs (say at L1), due to the presence of the capacitances, there are capacitive leakage
currents between line (or neutral) and earth.
- &
• Excessive heat and arcing ground may occur, especially in high voltage systems. This can pose serious
&
fire hazards.
-
a
phase
v Iz
(220 120
=
->
(5000)
↓
v I
=
228 15cca
=
1:0,044 A 12
44mA (per phase)
=
220
LI2C
a otE- Eloop:
304j/02,49902
I
Lovor
-
"I
-
I
Wantthelost
onz
.
-
have
rector.
t IEF
=
IEF(50,9902)
4.31 A
=
I
13 V=22020
& ->
V2 220 120
=
I v 3 220(120
↓
=
A Iilie I
t
12 -
Vain: proc
->
source
12 (stje 2 e
V Iz
V Iz
=
a
=
I Uph IEF
=
(6tj)
44-j76.2)
=
55
55
j95,26
=
-
- +
-
=
22
& -> L
UNN =
-j76.2755 +;95.26
1.15
↓ =44.
11-55-595.
12
V 1z
=
Fit
(8,
vi 220 =
L0
U2 220L120 =
1, =
=55 I
US (0-120
=
-22+ j38.11
12 4
=
=
I1 2120
=
-
-
55-95.26
⑦
e
A n e
E
Earth Fault in IT System (cont’d)
A
IT System before earth fault IT System at earth fault
L2
Un
L3
neutral
Line voltage = Phase to earth voltage
carth.
-
ELEC4146 Building Services Electrical Installations Electrical Systems-52
TN-C System
TN-C System before earth fault
-
-
TN-C System at earth fault
7
>
r
W
L C L
Question: Draw the path of the earth fault current in TN-C System.
IEF
Ox
Z1 Z2 Z3
I1 Z1 I2 Z2 I3 Z3
V1 V2 V3
V1 V2 V3 Millman’s Formula
I total I1 I 2 I 3
0
V1 V2 V3
Z1 Z 2 Z3
Z1 Z2 Z3 V1Y1 V2Y2 V3Y3 I1 I 2 I 3
1 Vtotal I total Z total
Z total 1 1 1 Y1 Y2 Y3 Y1 Y2 Y3
1 1 1 Z1 Z2 Z3
Z1 Z 2 Z 3 1
Note: Z , where Y is the admittance.
Y
↑
A ↓
&
• When the neutral is broken, the voltage of the neutral at the load
relative to earth (VN’N) is no longer zero. It is given by the
Millman’s equation.
E
VL1N Y1 VL 2 N Y2 VL 3 N Y3 I L1 I L 2 I L 3
VN ' N
Y1 Y2 Y3 Y1 Y2 Y3
millian
2/23 parallel of
where VL1N 220 0o ,VL 2 N 220 120o ,VL 3 N 220 120 o
- UN
VN ' N VN ' L1 VL1N => VL1N ' VL1N VN ' N
open neutral
VN ' N VN ' L 2 VL 2 N => VL 2 N ' VL 2 N VN ' N New phase voltage
A
Common risks of open neutral include:
1. Higher voltages in some phases increase stress on the cables,
I L3 N ' VL 3 N 'Y3
mean
i
thereby degrading their insulation;
2. Higher currents in those phases overload !
equipment, which may cause overheating and even start a fire; I
↑
-
3. In TN-C and TN-C-S, users can potentially experience an electric shock because it lacks a safe path to earth.
-
!
are unbalanced. A non-zero potential at the neutral point
on the load side is developed, which is given by
VL1N Y1 VL 2 N Y2 VL 3 N Y3 I L1 I L 2 I L 3
O
-safe)
VN ' N
Y1 Y2 Y3 Y1 Y2 Y3
=human
open neutral
body In TN-C system, this voltage (VN’N) may appear at the
safel
exposed conductive part.
Note that this phenomenon does not appear in other systems.
.
S
ELEC4146 Building Services Electrical Installations Electrical Systems-58
A
Example (3) I = 11: 118:
--xe44,98.39-14637'
line place In
24j
poltage voltage 195.56/16587
Question:
↓ -
W 13
8
=
Phase 1, Phase 2, and Phase 3, respectively. If the neutral conductor (NN’) is open circuited, determine
-
(a) Load current in each of the three phases before the open circuit; I 2j ij + +
-
-> total voltage.
(b) Potential of the load start-point relative to the earth;
-
- -
- -
--
- 123. 14-173.49
(c) New voltages across the loads; and
- --
c) Viro:VIN #UnY
-12.095
(d) New load currents in the three phases. Vie-azeL8 =86. (174.42:W
305.71218.437
d)
--
ri:
A 2201-120
200.382837-
=
Usi:-220(120
183,796 83.379 S
= --
*
(a)
Given Z1 = 2, Z2 = 2+j, and Z3 = 1 j.
VL1 = 220 0°; VL2 = 220 120°; VL3 = 220 +120°;
VL1 = 220;
VL2 = 220[cos( 120°)+j sin( 120°)]= 110 j 190.525588;
VL3 = 220[cos(120°)+j sin(120°)]= 110 + j 190.525588;
It is recommended to use more significant figures in the early part
IL1 = VL1/Z1 =220/2 = 110 A of the calculations in order to obtain more accurate results.
(b)
VN’N = (IL1+IL2+IL3)/(Y1+Y2+Y3) => Millman formula
IL1+IL2+IL3 = 110 + ( 82.105 j 54.210) + ( 150.263+j 40.263)
= 122.368 j 13.947
(j)
Y1 = 1/Z1 =1/2
=
(d)
IL1’ = VL1N’ Y1 = 152.8 j 4.2 A
The values of the phase voltages (currents) have changed because of the open neutral.
Advantages: G
me
↓
IT System
u
~Post TT System
• Provides inherent protection against touch voltages (except for AC systems with very high system
leakage capacitances and asymmetric loads). No closed circuit path exists for earth faults.
• Undesirable service interruptions can be avoided. In the event of an earth or insulation fault,
shutdown is not necessary. This is especially important for life-supporting equipment
(e.g. in intensive care units).
Disadvantages:
• In the event of an earth fault, the phase-to-earth voltage could be as high as the line voltage.
mine -
• Arcing ground may result from an earth fault.
-
• Current operated devices are unable to detect (or differentiate) the first occurrence of an earth fault.
for temporary
supply
elea
·I
Parameter TT IT TN-S TN-C TN-C-S
Safety HA Safe Less Safe Safest
e Least Safe Safe
Need earth electrode at installation? Yes Yes No No No
3Cost of protective earth (PE) conductor Low Low Highest Least High
-en
V, 770 L0 220
Is:51905Vi
V Iz
=
=
+190.53
y
=
-110
V2 220(120
=
=
V3 220-120
= =
-110 -j190.52, 11
Z
13
55
=55;95,272:
, Y1
=
t
=
=
-
:
Eess.c
4
Y2 5
=
12 =
↓
Z
Y3 I
1953 2-1538,106
=
64.48(-11)
= -