Design Report 10KL CWR
Design Report 10KL CWR
CONTRACTOR:
M/S BRCC-KCC(JV)
-
0.30 M
FREE BOARD
LIVE STORAGE
2.05 M
2.50 M
GL = 0.00 M
F.L. -1.2 M
0.10 M DEAD STORAGE
1.0_Inputs for Design of CWR
SALIENT FEATURES:
Capacity of CWR 10.00 KL
Internal Dia of CWR (m) 2.50 m
Height of water column 2.05 m
Free Board 0.30 m
Dead Storage 0.10 m
Depth Below ground Level (m) 1.20 m
Grade of Concrete/Reinforcement/Steel
RCC
Water Retaining structure M35
PCC M15
Reinforcement Fe-415, Confirming to IS: 1786
Density of RCC Concrete 25KN/m3
Density of water 10KN/m3
Thickness of Screed on Roof 75mm
Seismic Parameters
Seismic zone III
Zone Factor (z) 0.16
Importance Factor 1.5
Response Reduction Factor 2.5 as per IS 1893 2014 part -2
Soil Data
Soil Bearing Capacity 7 T/m2 at 1.2 m Depth
Density of soil 17KN/m3
Water table Water table was not encountered up to the depth of
Investigation as per SBC Report.
CODES
Code No. Title
IS: 456-2000
Code of Practice plain & reinforced concrete
SP-16
Code for design Aids for reinforced concrete
IS:875(part2)-2015
Code of practice for design loads
IS: 1893 Part-2:2014 Code for criteria for earthquake resistant design of
structures
IS: 3370 part -2:2021 Code for criteria water retaining wall & floor
IS: 3370 part -4 :2021 Code for Design water retaining wall & floor
72.60
Hoop Tension=
mm2
Diameter of bar = 10 mm
COFFICEN MOMEN ) )
S.NO DISTANC T T
. E
0.0 R 0.000 0.0625 0.0000 300.0 75 10 262 200 OK 0.42 0.00 0.44
0.1 R 0.125 0.0619 0.0073 300.0 75 10 262 250 OK 0.42 0.00 0.44
0.2 R 0.250 0.0600 0.0283 300.0 75 10 262 250 OK 0.42 0.00 0.44
0.3 R 0.375 0.0569 0.0604 300.0 75 10 262 250 OK 0.42 0.15 0.44
0.4 R 0.500 0.0525 0.0991 300.0 75 10 262 250 OK 0.42 0.08 0.44
0.5 R 0.625 0.0469 0.1383 300.0 75 10 262 250 OK 0.42 0.05 0.44
0.6 R 0.750 0.0400 0.1699 300.0 75 10 262 250 OK 0.42 0.03 0.44
0.7 R 0.875 0.0319 0.1844 300.0 75 10 262 250 OK 0.42 0.01 0.44
0.8 R 1.000 0.0225 0.1699 300.0 75 10 262 250 OK 0.42 0.02 0.44
0.9 R 1.125 -0.0119 0.1137 300.0 75 10 262 250 OK 0.42 0.03 0.44
1.0 R 1.250 0.0000 0.0000 300.0 75 10 262 250 OK 0.42 0.04 0.44
DESIGN OF OUTER VERTICAL WALL (CASE-1 - WATER INSIDE AND NO SOIL OUTSIDE)
CONC. MIX M 35
Assuming thickness of wall at base = 15.00 Cm.
H^2/Dt = 12.33
cover = 45 mm
The vertical wall shall be design in accordance to the recommendation given in clause
5.4.b. of IS: 3370 (Part II). The values of the coefficients for moments & Hoop tension
shall be calculated by interpretation from the following tables
Table No.8 IS:3370(part-IV)-2021 for coefficient for bending moment in cylindrical
wall with fixed base free top and subject to triangular load (clause 3.1.1 of IS: 3370
Part IV). IS code have coefficient values for H 2/DT value only up to 16.
CALCULATION FOR BENDING MOMENT
From the above Two tables, values of coefficient for bending moment and Hoop
tension have been interpolated for the corresponding value of H^2/Dt. The value of
bending moment and Hoop tension at different heights in wall have been shown in the
following tables.
Depth Below TWL Coeff. Coeff. Coeff. Bendin Requir Provid Area Area
g ed ed of of
depth depth sreel sreel
rqd rqd
for for
B.M. B.M.
for for for Mome
nt
FRACTIO METER B.M. B.M. B.M. Near Near
N S water outer
Face Face
0.430 180.0 180.0 8.0 279.1 260.0 180.0 8.0 279.1 260.0
0.645 180.0 180.0 8.0 279.1 260.0 180.0 8.0 279.1 260.0
0.860 180.0 180.0 8.0 279.1 260.0 180.0 8.0 279.1 260.0
1.075 180.0 180.0 8.0 279.1 260.0 180.0 8.0 279.1 260.0
1.290 180.0 180.0 8.0 279.1 260.0 180.0 8.0 279.1 260.0
1.505 180.0 180.0 8.0 279.1 260.0 180.0 8.0 279.1 260.0
1.720 180.0 180.0 8.0 279.1 260.0 180.0 8.0 279.1 260.0
1.935 180.0 180.0 8.0 279.1 260.0 180.0 8.0 279.1 260.0
2.150 180.0 180.0 8.0 279.1 260.0 180.0 8.0 279.1 260.0
BOTTOM SECTION OF WALL
Coefficient for design of uncracked section = 3.33
Maximum -ve bending moment at the base of wall = -1.01 KN.M/M
Maximum +ve bending moment = 0.25 KN.M/M
Mi. Overall thickness reqd. for uncracked sec. = 55.07 mm.
(-1.01)/3.33) ^0.5
Overall thickness of wall provided at OK = 150 mm.
base is
Dia. of bar proposed to be used 8 mm + = 8 mm.
Effective depth of section available = 101.00 mm.
base
Area of steel required considering = 77.52 Sq.mm.
B.M.
Spacing of bars required = 648.10 mm.
Spacing of bars provided = 260.00 mm.
Area of steel actually provided = 0.19 Sq.cm.
BASE SHEAR FOR SIESMIC FORCES
base shear for impulsive mode Vi = 39.80 Kn
Base shear for convective mode Vc = 14.03 Kn
Resultant Base shear (Vi = 42.20 Kn
2
+Vc2)
Sectional area of wall = 1.18 sqm
Shear stress due to seismic forces = 0.036 n/mm2
% steel available on water face at the = 0.19 %
base of wall
corresponding allowable stress = 0.339 n/mm2
OK
Parameters can be determined for impulsive and convective mode by h/D ratio; where
"h" is the depth of water in the tank and the "D" is the diameter of the tank
Sa/g
For the impulsive mode 0.786
For the convective mode 1.059
FLOOR SLAB
CONCRETE MIX: M = 35.00
The floor slab is directly supported on the
ground
and is non-structural. As such only temp. steel is
reqd.
Provide thickness of floor slab as = 20.00 Cm.
Temperature steel required = 0.240 %
Area of steel required = 2.400 Sq.c
m.
Diameter of bar chosen = 8.000 mm.
Spacing of bars near both faces required = 20.93 Cm.C
/C
3.14/4*8.00^2/2.40
Spacing of bars provided = 20.00 Cm.C
/C
DESIGN OF OUTER WALL (CASE 2-NO WATER INSIDE AND SOIL OUTSIDE)
COEFF. FOR EARTH PRESSURE = 0.30
Depth of floor below ground level = 1.2 M
THK. OF WALL AT BASE = 15.00 CM
THK AT 1.2 M ABOVE = 15.00 cm
FLOOR
WEGHED THK = 15.00 cm
H2/DT = 3.840
DEPTH BELOW G.L. B.M. B.M. B.M.
COEF COEF COEFF. BM
F. F.
FRACTION METER 1.2 1.6 3.84
0.1H 0.12 0.001 0.001 0.00055 0.485
2 1
0.2H 0.24 0.004 0.004 0.00354 3.120
2 1
0.3H 0.36 0.007 0.007 0.00638 5.623
7 5
0.4H 0.48 0.010 0.010 0.01294 11.404
3 7
0.5H 0.60 0.011 0.012 0.01714 15.105
2 1
0.6H 0.72 0.009 0.011 0.02286 20.146
0 1
0.7H 0.84 0.002 0.005 0.02596 22.878
2 8
0.8H 0.96 - - 0.02682 23.636
0.010 0.005
8 1
0.9H 1.08 - - 0.02104 18.542
0.031 0.023
1 2
1.0H 1.20 - - 0.00382 3.366
0.060 0.050
2 5
COVER = 35.00 mm.
EFFECTIVE DEPTH AVAILABLE AT BASE = 11.10 CM
MAX NEGETIVE B.M. AT BASE = 23.64 KG-
M
AREA OF STEEL REQD. = 0.190 SQC
M
soil face mm
8 = 8.00 mm.
+
Spacing of Bars required = 263.78 cm
Spacing of Bars provided = 20.00 cm
Area of steel actually provided = 5.02 SQC
M
DESIGN OF WALL FOOTING:
CONCRETE MIX M = 35
THICKNESS OF FOUNDATION SLAB ASSUMED THFS = 20.00 CM
DEPTH OF FOOTING BELOW GROUND DOF1 = 1.20 M
UNIT WEIGHT OF SOIL = 1700.00 KG /
Cu.M
SAFE BEARING PRESSURE SBP = 7000.00 KG /
SQ.M
MAX.ALLOW. GROSS LOADING AT FOOTING LEVEL SLF = 7000.00 KG /
SQ.M
ASSUMING WIDTH OF HEEL SLAB HWID = 0.30 M
ASSUMING WIDTH OF TOE SLAB TWID = 0.60 M
WIDTH OF WALL AT BASE = 0.15 M
TOTAL WIDTH OF FOOTING SLAB FWID = 1.05 M
THE FOLLOWING TABLE GIVES CALCULATION OF LOAD AND MOMENTS ON THE FOOTING
LOAD DUE TO LOAD PER DISTANCE FROM
ITEM METER EDGE OF HEEL
KG M KG-M
VERTICAL WALL PART 1 919 0.3 345
75
VERTICAL WALL PART 2 0 0.0 0
00
472 0.3 177
WT. FROM ROOF
75
0.1 92
WT. OF SOIL 612
50
WT. OF BASE SLAB 525 0.5 276
25
NET MOMENT DUE TO SOIL 3
T 2
892
OTAL 528