Capacitor Bank Calculation
Project:
ERC1400/D20/C1-DOHA EXPRESS WAY (PKG-1) RE-DESIGN OF AL-RAYAN
INTERCHANGES STORM WATER RESERVOIR &PUMP STATION
Client:
ASHGHAL
Rating as per specification
415V,312.5kVAR
Operating Voltage
415V,50Hz.
De tuning Factor
7%
X eq
(0.415)*(0.415) /0.3125 =0.5511
X eq
XC-XL
XC(1-0.07)
XC
0.5511/0.93 = 0.5925
XL
XC Xeq =(0.5925-0.5511)=0.0414
Voltage raise due to series reactor(VL) =
3*IL*XL
IL
415/(3*0.5511) =434.78A
VL
3*434.78*0.0414= 31.18 V
Capacitor Voltage
31.18+415 =446.18V
Capacitor Bank kVAR per stage
1*12.5kVAR+2*25kVAR+5*50kVAR
Total No. of stages
8 Nos.
Capacitor Bank kVAR
312.5
Capacitor Used
480V,15kVAR-1No.+480V,30kVAR-12Nos.
(375kVAR at 480V)
Remark:The Capacitor selected is hence adequate