CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Strength Requirements
Q
Slide No. 1
ENCE 355 Assakkaf
The basic criterion for strength design
may be expressed as
Strength furnished Strength required (1)
All members and all sections of
members must be proportioned to meet
this criterion.
Eq. 1 can be thought of as a supply and
a demand.
Slide No. 2
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Strength Requirements
Q
ENCE 355 Assakkaf
The supply is considered as the
strength furnished, while the demand as
the strength required.
The required strength may be
expressed in the forms of design loads
or their related moments, shears, and
forces.
Design loads may be defined as service
loads multiplied by their appropriate
factors.
Slide No. 3
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Strength Requirements
Q
ENCE 355 Assakkaf
Eq. 1 can be expressed in a more
compact general form as
m
Rn i Lni
(2)
i =1
Where
= strength reduction factor
i = load factor for the ith load component out of n components
Rn = nominal or design strength (stress, moment, force, etc.)
Lni = nominal (or design) value for the ith load component out
of m components
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Strength Requirements
Q
Eq. 2 is the basis for Load and
Resistance Factor Design (LRFD) for
Structural Members.
This equation uses different partial
safety factors for the strength and the
load effects.
The load factors are usually amplifying
factors (>1), while the strength factors
are called reduction factors (<1).
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Strength Requirements
Q
Slide No. 4
ENCE 355 Assakkaf
Slide No. 5
ENCE 355 Assakkaf
Strength Factor
The strength reduction factor provide for
the possibility that small adverse variation
in material strength, workmanship, and
dimensions may combine to result in
undercapacity.
Load Factors
The load factors s attempt to assess the
possibility that prescribed service loads
may be exceeded. Obviously, a live load is
more apt to be exceeded than a dead load,
which is largely fixed by the weight.
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Strength Requirements
Q
Slide No. 6
ENCE 355 Assakkaf
ACI Code Provisions
In assigning strength reduction factors, the
degree of ductility and the importance of
the member as well as the degree of
accuracy with which the strength of the
member can be established are
considered.
The ACI Code provides for these variables
by using the following factors as provided
in Table 1.
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Strength Requirements
Slide No. 7
ENCE 355 Assakkaf
Table 1. Strength Reduction Factors
Type of Loading
Bending
0.90
Shear and Torsion
0.85
Compression members (spirally reinforced)
0.75
Compression Members (tied)
0.70
Bearing on Concrete
0.70
Slide No. 8
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Strength Requirements
Q
ENCE 355 Assakkaf
ACI Code Provisions
When word design is used throughout the
ACI Code, it indicates that the load factors
are included.
The subscript u is used to indicate design
loads, moments, shears, and forces.
For example, the design load wu = 1.4wDL + 1.7 wLL
and the required or design moment
strength for dead and live loads is
M u = 1.4M DL + 1.7 M LL
where 1.4 and 1.7 are the load factors.
Slide No. 9
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Strength Requirements
Q
ENCE 355 Assakkaf
ACI Requirements for Dead and Live
Loads
For dead and live loads, the ACI Code
specifies design loads, design shears, and
design moments be obtained from service
loads by the using the relation
U = 1.4D +1.7L
(3)
Slide No. 10
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Strength Requirements
Q
ENCE 355 Assakkaf
ACI Requirements for Strength
The ACI Code stipulates that the strength
(moment, shear, force) furnished shall
meet the following requirements
Rn 1.4D +1.7L
(4)
Where
= strength reduction factor as provided in Table 1
Rn = nominal or design strength (stress, moment, force, etc.)
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Slide No. 11
ENCE 355 Assakkaf
Rectangular Beam Analysis for
Moment
Q
The analysis of a reinforced concrete
beam implies that we know precisely
what comprises the section of the
beam.
The following data are known:
1.
2.
3.
4.
5.
Tension bar size or number (or As).
Beam width (b).
Effective depth (d) or total depth (h).
Compressive strength of concrete ( f c ).
Yield strength of steel (fy).
Slide No. 12
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
ENCE 355 Assakkaf
Rectangular Beam Analysis for
Moment
Q
Variables that need to be found or
answered include the following:
1. Find the strength Mn.
2. Check the adequacy of a given beam, or
3. Find an allowable load that the beam can
carry.
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Slide No. 13
ENCE 355 Assakkaf
Rectangular Beam Analysis for
Moment
Q
Example 1
Determine if the simply supported beam
shown in Fig. 1 is adequate as governed
by the ACI Code. The prescribed loads are
as follows:
wD = 0.80 kip/ft (excludes beam weight)
wL = 0.80 kip/ft
Assume that the compressive strength of
concrete is 4,000 psi, while the yield
strength of steel is 60,000 psi.
Slide No. 14
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
ENCE 355 Assakkaf
Rectangular Beam Analysis for
Moment
Q
Example 1 (contd)
12 in.
12 kips
wD + wL
20 in.
4-#9
bars
10 ft
17.5 in.
10 ft
Slide No. 15
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
ENCE 355 Assakkaf
Rectangular Beam Analysis for
Moment
Q
Example 1 (contd)
Area for No. 9 bar = 1.00 in 2 (see Table 2 or Table A - 2 Text)
Therefore, As = 4(1.00) = 4.00 in 2
Next we need to find the maximum and minimum
Reinforcement for this beam as specified by the ACI .
max = 0.75 b
Asmax = 0.75 Asb
b =
ACI Code
0.85 f c1 87,000 0.85(4 )(0.85) 87
=
= 0.02851
f + 87,000
fy
60
60 + 87
y
Therefore, max = 0.75 b = 0.75(0.02851) = 0.0214
Slide No. 16
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
ENCE 355 Assakkaf
Rectangular Beam Analysis for
Moment
Table 2. ASTM Standard - English Reinforcing Bars
Bar Designation
#3 [#10]
#4 [#13]
#5 [#16]
#6 [#19]
#7 [#22]
#8 [#25]
#9 [#29]
#10 [#32]
#11 [#36]
#14 [#43]
#18 [#57]
Diameter
in
0.375
0.500
0.625
0.750
0.875
1.000
1.128
1.270
1.410
1.693
2.257
Area
in2
0.11
0.20
0.31
0.44
0.60
0.79
1.00
1.27
1.56
2.25
4.00
Weight
lb/ft
0.376
0.668
1.043
1.502
2.044
2.670
3.400
4.303
5.313
7.650
13.60
Note: Metric designations are in brackets
Slide No. 17
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
ENCE 355 Assakkaf
Rectangular Beam Analysis for
Moment
Q
Example 1 (contd)
As , min =
As , min
As , min
3 f c
200
bw d
bw d
fy
fy
ACI
12 in.
20 in.
3 4,000
(12)(17.5) 200 (12)(17.5)
=
60,000
60,000
= 0.664 0.700
4-#9
bars
17.5 in.
Therefore, take As , min = 0.70 in 2
Calculate the steel ratio for this beam:
=
As
4
=
= 0.0191
bd 12(17.5)
Slide No. 18
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
ENCE 355 Assakkaf
Rectangular Beam Analysis for
Moment
Q
Example 1 (contd)
12 in.
Since = 0.0191 < max = 0.0214, failure
by yielding is assured.
20 in.
2
2
Also, As = 4.00 in > 0.70 in OK
17.5 in.
4-#9
bars
Note that max = 0.75 b = 0.0214 can be obtained directly
from from Table 3 (Table A-5 Text).
Also note that As,min can be obtained from Table 3 (Table
A-5 Text) as follows
As,min = 0.0033 b d = 0.0033 (12)(17.5) = 0.693 .70 in2
Slide No. 19
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
ENCE 355 Assakkaf
Rectangular Beam Analysis for
Moment
Table A-5 Textbook
f c (psi )
Table 3
Design Constants
Values used in
the example.
3 f c 200
f y
f y
3,000
4,000
5,000
6,000
0.0050
0.0050
0.0053
0.0058
3,000
4,000
5,000
6,000
0.0040
0.0040
0.0042
0.0046
3,000
4,000
5,000
6,000
0.0033
0.0033
0.0035
0.0039
3,000
4,000
5,000
6,000
0.0027
0.0027
0.0028
0.0031
max = 0.75 b
Fy = 40,000 psi
0.0278
0.0372
0.0436
0.0490
Fy = 50,000 psi
0.0206
0.0275
0.0324
0.0364
Fy = 60,000 psi
0.0161
0.0214
0.0252
0.0283
Fy = 75,000 psi
0.0116
0.0155
0.0182
0.0206
Recommended Design Values
b
k (ksi)
0.0135
0.0180
0.0225
0.0270
0.4828
0.6438
0.8047
0.9657
0.0108
0.0144
0.0180
0.0216
0.4828
0.6438
0.8047
0.9657
0.0090
0.0120
0.0150
0.0180
0.4828
0.6438
0.8047
0.9657
0.0072
0.0096
0.0120
0.0144
0.4828
0.6438
0.8047
0.9657
10
Slide No. 20
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
ENCE 355 Assakkaf
Rectangular Beam Analysis for
Moment
Q
Example 1 (contd)
12 in.
N C = NT
0.85 f cba = As f y
a=
As f y
0.85 f cb
4(60 )
= 5.88 in.
0.85(4 )(12 )
20 in.
17.5 in.
4-#9
bars
a
5.88
= 17.5
= 14.6 in.
2
2
Therefore,
M n = As f y Z = 0.85 f cbaZ
Z =d
3,504
ft - kips
12
Hence, M n = 292 ft - kips (based on Steel)
M n = 4(60)(14.6) = 3,504 in - kips =
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Slide No. 21
ENCE 355 Assakkaf
Rectangular Beam Analysis for
12 kips
Moment
Example 1 (contd)
wD + wL
Service Loads:
The beam weight is to be calculated:
Beam weight = Volume 0.150 kip/ft
10 ft
10 ft
12
kip
20
Weight = ft ft 1ft 0.15
= 0.25 kip /ft
12
ft
12
Total uniform dead load, wD = 0.25 + 0.80 =1.05 kips/ft
Total uniform dead load, wL = 0.80 = kips/ft
Using Eq. 3
U = 1.4D +1.7L
ACI Code
11
Slide No. 22
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
ENCE 355 Assakkaf
Rectangular Beam Analysis for
Moment
Example 1 (contd)
wu = 1.4wD + 1.7 wL
ACI Code
Rn 1.4D +1.7L
= 1.4(1.05) + 1.7(0.80) = 2.83 kips/ft
Pu = 1.7 PL = 1.7(12) = 20.4 kips
wu L2 Pu L 2.83(20) 12(20)
+
=
+
= 243.5 ft - kips
8
4
8
4
Check ACI Code Requirement:
2
Mu =
Rn (1.4M D +1.7M L = Mu )
[0.9Mn = 0.9(292) = 262.8 ft - kips] > [Mu = 243.5 ft - kips] OK
Therefore the beam is adequate
Slide No. 23
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
ENCE 355 Assakkaf
Rectangular Beam Analysis for
Moment
Example 1 (contd)
Pu = 12 (1.7) = 20.4 kips
wu = 2.83 kips/ft
Alternative way for finding Mu
wu = 1.4wD + 1.7 wL
= 1.4(1.05) + 1.7(0.80) = 2.83 kips/ft
The factored maximum moment
can be obtained from the
moment diagram directly:
M u = 243.5 ft - kips
10 ft
10 ft
38.5 k
38.5 k
38.5 k
10.2 k
Shear V
10.2 k
38.5 k
243.5 ft-k
Moment M
12
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Introduction to Slabs
Q
Slide No. 24
ENCE 355 Assakkaf
Slabs are considered specialized type
of bending members.
They are used both in structural steel
and reinforced concrete construction.
Types of Slabs:
One-way Slab
Two-way Slab
Flat Slab
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Introduction to Slabs
Q
Slide No. 25
ENCE 355 Assakkaf
Typical Structure (1)
13
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Introduction to Slabs
Q
Typical Structure (2)
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Introduction to Slabs
Q
Slide No. 26
ENCE 355 Assakkaf
Slide No. 27
ENCE 355 Assakkaf
Floor-Column Systems
14
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Introduction to Slabs
Q
Floor-Column Systems
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Introduction to Slabs
Q
Slide No. 28
ENCE 355 Assakkaf
Slide No. 29
ENCE 355 Assakkaf
One-Way Slab
A one-way slab can be defined as a
structural reinforced concrete slab
supported on two opposite sides so that
the bending occurs in one direction only,
that is, perpendicular to the supported
edges.
15
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Introduction to Slabs
Q
One-Way Slab
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Introduction to Slabs
Q
Slide No. 30
ENCE 355 Assakkaf
Slide No. 31
ENCE 355 Assakkaf
Two-Way Slab
A two-way slab can be defined as a
structural reinforced concrete slab
supported along four edges so that the
bending occurs in two directions
perpendicular to each other.
However, If the ratio of the lengths of the
two perpendicular sides is in excess of 2,
the slab may be assumed to act as a oneway slab with bending primarily occurring
in the short direction.
16
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Introduction to Slabs
Q
Slide No. 32
ENCE 355 Assakkaf
Flat Slab
A specific type of twoway slab is categorized
as a flat slab. A flat
slab may be defined as
a concrete slab
reinforced in two or
more directions,
generally without
beams or girders to
transfer the loads to the
supporting members.
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
One-Way Slab: Analysis for
Moment
Q
Slide No. 33
ENCE 355 Assakkaf
In this course, we are concerned
primarily with one-way slab that is
assumed to be a rectangular beam with
width b = 12 in. as shown in Fig. 1.
When loaded with uniformly distributed
load, the slabs deflects so that it has
curvature, and therefore bending
moment, in only one direction (Fig. 1).
17
Slide No. 34
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
One-Way Slab: Analysis for
Moment
Q
One-Way Slab Design
ENCE 355 Assakkaf
Figure 1
12
Analyze this strip
as a beam
The procedure for finding Mn for one-way slab is almost identical to
that of a beam.
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
One-Way Slab: Analysis for
Moment
Q
Slide No. 35
ENCE 355 Assakkaf
ACI Code Requirements for Slabs
Minimum Steel Area, As,min:
For grade 40 or 50 steel:
As = 0.0020bh
(5a)
For grade 60 steel:
As = 0.0018bh
(5b)
Concrete protection:
Concrete protection for reinforcement in slabs
must be not less than 0.75 in.
For surfaces exposed to weather and ground,
min. protection is 2 in (#6 to #18) and 1.5 in (#5)
18
Slide No. 36
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
One-Way Slab: Analysis for
Moment
Q
ENCE 355 Assakkaf
Example 2
The one-way slab shown spans 12 ft from
center of the support to the center of
support. Calculate Mn and determine the
service live load (psf) that the slab may
carry. Use f c = 3,000 psi and fy = 40,000
psi.
Section A-A
A
3
clear
4
12 ft
#8 @ 6 o.c
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
One-Way Slab: Analysis for
Moment
Slide No. 37
ENCE 355 Assakkaf
Example 2 (contd)
Analyze a 12-in wide strip of slab:
For f c = 3,000 psi and fy = 40,000 psi
max = 0.0278 from Table 3 (Table A - 5 Text)
As , min = 0.0020(12)(8) = 0.19 in 2
As = 2(0.79) = 1.58 in 2 > 0.19 in 2
OK
d = 8 0.75 0.5 = 6.75 in.
A
1.58
= 0.0195 < 0.0278 OK
= s =
bd 12(6.75)
a=
As f y
0.85 f cb
b = 12 in.
8
clear
#8 @ 6 o.c
1.58(40 )
= 2.07 in.
0.85(3)(12 )
19
Slide No. 38
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
One-Way Slab: Analysis for
Moment
ENCE 355 Assakkaf
Table 2. ASTM Standard - English Reinforcing Bars
Bar Designation
#3 [#10]
#4 [#13]
#5 [#16]
#6 [#19]
#7 [#22]
#8 [#25]
#9 [#29]
#10 [#32]
#11 [#36]
#14 [#43]
#18 [#57]
Diameter
in
0.375
0.500
0.625
0.750
0.875
1.000
1.128
1.270
1.410
1.693
2.257
Area
in2
0.11
0.20
0.31
0.44
0.60
0.79
1.00
1.27
1.56
2.25
4.00
Weight
lb/ft
0.376
0.668
1.043
1.502
2.044
2.670
3.400
4.303
5.313
7.650
13.60
Note: Metric designations are in brackets
Slide No. 39
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
ENCE 355 Assakkaf
One-Way Slab: Analysis for
Moment
Table A-5 Textbook
f c (psi )
Table 3
Design Constants
Values used in
the example.
3 f c 200
f y
f y
3,000
4,000
5,000
6,000
0.0050
0.0050
0.0053
0.0058
3,000
4,000
5,000
6,000
0.0040
0.0040
0.0042
0.0046
3,000
4,000
5,000
6,000
0.0033
0.0033
0.0035
0.0039
3,000
4,000
5,000
6,000
0.0027
0.0027
0.0028
0.0031
max = 0.75 b
Fy = 40,000 psi
0.0278
0.0372
0.0436
0.0490
Fy = 50,000 psi
0.0206
0.0275
0.0324
0.0364
Fy = 60,000 psi
0.0161
0.0214
0.0252
0.0283
Fy = 75,000 psi
0.0116
0.0155
0.0182
0.0206
Recommended Design Values
b
k (ksi)
0.0135
0.0180
0.0225
0.0270
0.4828
0.6438
0.8047
0.9657
0.0108
0.0144
0.0180
0.0216
0.4828
0.6438
0.8047
0.9657
0.0090
0.0120
0.0150
0.0180
0.4828
0.6438
0.8047
0.9657
0.0072
0.0096
0.0120
0.0144
0.4828
0.6438
0.8047
0.9657
20
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
One-Way Slab: Analysis for
Moment
Q
Slide No. 40
ENCE 355 Assakkaf
Example 2 (contd)
a
2.07
= 6.75
= 5.72 in.
2
2
1.58(40)(5.72 )
M n = As f y Z =
= 30.13 ft - kips
12
Therefore,
Z =d
M n = 0.9(30.13) = 27.1 ft - kips
wu L2
8
27.1(8) 27.1(8)
=
= 1.51 k/ft
wu =
L2
(12)2
M u = M n = 27.1 =
CHAPTER 2c. RECTANGULAR R/C BEAMS: TENSION STEEL ONLY
Slide No. 41
ENCE 355 Assakkaf
One-Way Slab: Analysis for
Moment
ACI Code
Q
Example 2 (contd)
wu = 1.4 wD + 1.7 wL
wD = weight of slab =
Rn 1.4D +1.7L
8(12)
(0.150) = 0.10 k/ft
144
1.51 = 1.4(0.10) + 1.7 wL
1.7 wL = 1.51 1.4(0.10 )
Hence,
wL =
1.51 1.4(0.1)
= 0.806 k/ft = 806 psf
1.7
21