ke – FRXX
MULTI RANGE, TIME
ADJUSTED FLASHER RELAY General:
► 16 Time interval selection It is microprocessor controlled. It is possible to make 16 different time interval selections by using the dip-switch that is
located near the equipment.
► 230 Vac or 24 V ac/dc
T T T T T T T
► TIME INTERVAL SELECTION:
You may select the desired time interval
by using the 1,2,3,4 numbered switches
off of the dip-switch that are at the side of
(t) the equipment. The time selection table is
Time given below.
Adj.
on
Min - Max Min - Max
0,1 – 1sec 9 sec - 15 min
1 2 3 4 1 2 3 4
0,1 – 5sec 18 sec – 30 min
1 2 3 4 1 2 3 4
0,1 – 10sec 36 sec – 60 min
1 2 3 4 1 2 3 4
0,3 – 30sec 3 min – 5 hrs
1 2 3 4 1 2 3 4
0,6 – 60sec 6 min – 10 hrs
1 2 3 4 1 2 3 4
1 – 100sec 9 min – 15 hrs
1 2 3 4 1 2 3 4
A1 15
3 sec - 5 min 15 min – 25 hrs
230 Vac 1 2 3 4 1 2 3 4
A2 6 sec – 10 min 18 min – 30 hrs
16 18 1 2 3 4 1 2 3 4
A3 15
24 Vac/dc
A2 16 18
Simple Connection :
► THE TIME ADJUSTMENT SCALER:
TECHNICAL DATA: The scaler of the adjustment potentiometer located on
the equipment, can be set between 0,1 to 1.
Operational Voltage (Un) When you select your adjustment with the dip-switch, L1
A1 – A2 terminals : 230 Vac it can be adjusted at the range specified by the L2
A3 – A2 terminals : 24 Vac or 24 Vdc interval mode, by the steps of 1%. L3
Operating Range : (0.8 – 1.1)xUn 24 Vac
(Un nominal voltage) 24 Vdc
Frequency : 50/60 Hz Example :
Contact Current : Max. 5 A / 240 VAC
Power Consumption : < 8 VA
Device Protection 1sec–100sec
Class : IP20 1 2 3 4
Connector Protection N
Class : IP00 If you had already selected the time interval mode
Ambient Temperature : -5°C....+50°C above, in the situation of the potentiometer becoming
Connection Type : To connection rail maximum, the relay would have counted 100 sec; K1
in electrical panel while in minimum, it would have counted 1 sec. You
Dimensions : 23x82x80 mm can do your adjustment at steps of 1 sec. (The min. T1
value in the table is the adjustment step period)
Load
16 mm
mm
80
N
23 mm 35 mm
82 mm