API 650 Desain Tangki

The document discusses the introduction of API Standard 650 for welded steel tanks for oil storage. It provides an overview of the standard's scope, references, definitions, materials, design, fabrication, erection and inspection requirements. It also summarizes the standard's appendices which provide additional guidelines for topics like small tanks, aluminum tanks, foundations, floating roofs, leak detection and seismic design. The presentation then covers tank types and designs according to API 650 and 620 standards based on vapor pressure, including atmospheric and low pressure storage tanks with various roof types. It also discusses the key aspects of tank engineering covered by API 650 such as technical data sheets, drawings, design calculations and safety components.

Uploaded by

Ahmad Fadhli
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
4K views52 pages

API 650 Desain Tangki

The document discusses the introduction of API Standard 650 for welded steel tanks for oil storage. It provides an overview of the standard's scope, references, definitions, materials, design, fabrication, erection and inspection requirements. It also summarizes the standard's appendices which provide additional guidelines for topics like small tanks, aluminum tanks, foundations, floating roofs, leak detection and seismic design. The presentation then covers tank types and designs according to API 650 and 620 standards based on vapor pressure, including atmospheric and low pressure storage tanks with various roof types. It also discusses the key aspects of tank engineering covered by API 650 such as technical data sheets, drawings, design calculations and safety components.

Uploaded by

Ahmad Fadhli
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Introduction to API 650
  • Appendices Overview
  • Tank Design Details
  • Technical Data and Drawing
  • Design and Calculation
  • Construction Procedures
  • Wind Load Calculation
  • Seismic Design

10/7/2021

KURSUS INSPEKTUR TANGKI PENIMBUN

REKAYASA TANGKI – API 650

DISELENGGARAKAN OLEH :
KPDM - DIREKTORAT JENDERAL MINYAK DAN GAS BUMI
DIPRESENTASIKAN OLEH :
SUHERMIN, MT
(API 653 AUTHORIZED TANK INSPECTOR)

PENGENALAN API STANDARD 650


“Welded Steel Tanks for Oil Storage”
TWELFTH EDITION, MARCH 2013; ADDENDUM 2: JANUARY 2016

ISI
 SCOPE
 REFERENCES
 DEFINITIONS
 MATERIALS
 DESIGN
 FABRICATION
 ERECTION
 METHODS OF INSPECTING JOINTS
 WELDING PROCEDURE AND WELDER QUALIFICATIONS
 MARKING

1
10/7/2021

PENGENALAN API STANDARD 650


“Welded Steel Tanks for Oil Storage”
APPENDIX
 Appendix A Optional Design Basis for Small Tanks
 Appendix AL Aluminum Storage Tanks
 Appendix B Recommendations for Design and Construction of
Foundations for Aboveground Oil Storage Tanks
 Appendix C External Floating
 Appendix D Technical Inquiries
 Appendix E Seismic Design of Storage Tanks
 Appendix EC Commentary on Appendix E
 Appendix F Design of Tanks for Small internal Pressures
 Appendix G Structurally-Supported Aluminum Dome Roofs

PENGENALAN API STANDARD 650


“Welded Steel Tanks for Oil Storage”
APPENDIX
 Appendix H Internal Floating Roofs
 Appendix I Undertank Leak Detection and Subgrade Protection
 Appendix J Shop-Assembled Storage Tanks
 Appendix K Sample Application of the Variable-Design-Point
Method to Determine Shell-Plate Thickness K-1
 Appendix L API Std 650 Storage Tank Data Sheet
 Appendix M Requirements for Tanks Operating at Elevated
Temperatures
 Appendix N Use of New Materials That Are Not Identified
 Appendix O Recommendations for Under-Bottom Connections
 Appendix P Allowable External Loads on Tank Shell Openings
 Appendix R Load Combinations.

2
10/7/2021

PENGENALAN API STANDARD 650


“Welded Steel Tanks for Oil Storage”
APPENDIX
 Appendix S Austenitic Stainless Steel Storage Tanks
 Appendix SC Stainless and Carbon Steel Mixed Materials Storage
Tanks
 Appendix T NDE Requirements Summary
 Appendix U Ultrasonic Examination In Lieu of Radiography
 Appendix V Design of Storage Tanks for External Pressure
 Appendix W Commercial and Documentation Recommendations
 Appendix X Duplex Stainless Steel Storage Tanks
 Appendix Y API Monogram

PENGENALAN API STANDARD 650


“Welded Steel Tanks for Oil Storage”
STATUS APPENDIX DARI API 650

3
10/7/2021

TANGKI PENIMBUN ATMOSFERIK (API 650)


Pressure: Atm – 2.5 psig

Tangki Penimbun Atap Tetap

TANGKI PENIMBUN ATMOSFERIK (API 650)

Tangki Penimbun Atap Terapung External

4
10/7/2021

TANGKI PENIMBUN ATMOSFERIK (API 650)

Tangki Penimbun Atap Terapung External (Double Deck)

TANGKI PENIMBUN ATMOSFERIK (API 650)

Tangki Penimbun Atap Terapung External (Pontoon)

5
10/7/2021

TANGKI PENIMBUN ATMOSFERIK (API 650)

Tangki Penimbun Atap Terapung Internal

TANGKI PENIMBUN ATMOSFERIK (API 650)

Tangki Penimbun Atap Terapung Internal

6
10/7/2021

TANGKI PENIMBUN BERTEKANAN RENDAH (API 620)


Pressure: 2.5 – 15 psig

Tangki dengan vapor dome roof

Plain Hemispheroids Noded Hemispheroids

TANGKI PENIMBUN BERTEKANAN RENDAH (API 620)

Tangki LPG –
Double wall

Plain Spheroids

Tangki LNG –
Double wall

Noded Spheroids

7
10/7/2021

TANGKI PENIMBUN BERTEKANAN RENDAH (API 620)

TANGKI PENIMBUN DENGAN DINDING/ATAP/DASAR DOBEL

BENTUK DAN TIPE TANGKI


 TEKANAN VAPOR DARI CAIRAN YANG SIMPAN DALAM
TANGKI ATAU TEKAN INTERENAL DESAIN,
MENENTUKAN STANDARD, BENTUK DAN TIPE TANGKI
YANG DIPAKAI

8
10/7/2021

RUANG LINGKUP
REKAYASA TANGKI - API 650
 Technical Data (Tank Data Sheet)
 Technical Drawing
 Design & Calculation
 Working Procedure (Fabrication & Erection
Procedure)
 NDT & Testing Procedure
 Welding Procedure Specification
 Tank Safety Appurtenances

TECHNICAL DATA
(Tank Data Sheet)
TANGGUNG JAWAB PIHAK PEMBELI
Personil yang menyiapkan Data Sheet harus memiliki
pengalaman dalam desain tangki, dia harus memastikan aturan
dengan akurat dan komplit. Pihak pembeli bertanggung jawab
penuh untuk initiating and completing the Data Sheet

TANGGUNG JAWAB PIHAK MANUFACTURER


Pihak Manufacturer harus melengkapi Data Sheet seperti yang
diminta untuk untuk menjelaskan proposal dan menyediakan
informasi yang relevan yang diminta pada semua dengan tanda
asterisk (*) yang telah disediakan oleh pihak Pembeli. Data
Sheet harus diserahkan semasa proyek dikerjakan seperti pada
W.1.2(2).

9
10/7/2021

TECHNICAL DATA (Tank Data Sheet)

TECHNICAL DRAWING
GAMBAR TEKNIS TANGKI PENIMBUN

 General Arrangement
 Shell Plate Arrangement & Details
 Bottom Plate Arrangement & Details
 Roof Plate Arrangement & Details
 Roof Structure Details
 Nozzle Layout Details
 Welding Sequences Details
 Water Sprinkle & Splash Plate Details

10
10/7/2021

3 D DRAWING

TECHNICAL DRAWING
GENERAL ARRANGEMENT

11
10/7/2021

TECHNICAL DRAWING
SHELL PLATE ARRANGEMENT & DETAILS

TECHNICAL DRAWING
BOTTOM PLATE ARRANGEMENT & DETAILS

12
10/7/2021

TECHNICAL DRAWING
ROOF PLATE ARRANGEMENT & DETAILS

13
10/7/2021

TECHNICAL DRAWING
ROOF STRUCTURE DETAILS

TECHNICAL DRAWING
WATER SPRINKLER DETAILS

14
10/7/2021

DESIGN & CALCULATION – API 650


BEBAN / LOAD DALAM DESAIN TANGKI

 Beban Mati (Dead Load)  Beban Salju (Snow)


 Design External Pressure  Beban Isi Cairan
 Design Internal Pressure (Store Liquid)
 Hydrostatic Test  Test Pressure
 Internal Floating Roof Loads  Beban Angin (Wind)
 Minimum Roof Live Load  Beban External
 Beban Gempa (Seismic)

DESIGN & CALCULATION – API 650


I. DESIGN CONSIDERATION – BEBAN / LOAD
 Dead Load: Berat tangki atau komponen tangki,
termasuk corrosion allowance
 Design External Pressure: (Desain Tekanan Luar),
tidak boleh lebih kecil dari 0.25 kPa (1 in water).
Refer ke Appendix V utk tekanan luar lebih besar dari
0.25 kPa (1 in. of water).
 Design Internal Pressure: tidak melebihi 18 kPa
(2.5 lbf/in2)
 Hydrostatic Test: beban yang disebabkan oleh

pengisian air pada tangki hingga level cairan desain


 Minimum Roof Live Load: 1kPa (20 lb/ft2) secara

horizontal pada atap

15
10/7/2021

DESIGN & CALCULATION – API 650


I. DESIGN CONSIDERATION – BEBAN / LOAD
 Internal Floating Roof Loads:
1) Dead load of internal floating roof (Df) termasuk berat
dari flotation compartments, seal dan semua other atap
terapung lainnya dan komponen yang menempel.
2) Internal floating roof uniform live load (Lf1) (0.6 kPa
[12.5 lbf/ft2]) jika tidak ada automatic drains, (0.24 kPa
[5 lbf/f2]) jika automatic drains tersedia).
3) Internal floating roof point load (Lf2) jika setidaknya
dua orang berjalan dimanapun pada atap. Suatu beban
2.2 kN [500 lbf] pada 0.1 m2 [1 ft2] dimanapun pada
atap menunjukkan dua orang berjalan

DESIGN & CALCULATION – API 650


I. DESIGN CONSIDERATION – BEBAN / LOAD
 Seismic: Beban seismic ditentukan sesuai dengan
Appendix E1 – E6
 Snow: Beban snow ditentukan sesuai dengan ASCE 7

 Store Liquid: Beban yang disebabkan pengisian cairan


dengan G tertentu sampai level desain
 Test Pressure: sesuai dengan F.4.4 dan F.7.6

 Wind: Desain Tekanan angin (PWS and PWR) ditentukan


menggunakan Desain kecepatan angin (V)
PWS (Desain Tekanan angin pada dinding) : 0.86 kPa (V/190)²,
([18 lbf/ft²] [V/120]²) pada area tertentu
PWR (Desain Tekanan angin pada atap) : 1.44 kPa (V/190)², atau
([30 lbf/ft² [V/120]²) pada area tertentu

16
10/7/2021

DESIGN & CALCULATION – API 650


KOMBINASI BEBAN
a) Fluid and Internal Pressure: DL + F + Pi
b) Hydrostatic Test: DL + Ht + Pt
c) Wind and Internal Pressure: DL + W + Fp Pi
d) Wind and External Pressure: DL + W + Fpe Pe
e) Gravity Loads:
1) DL + (Lr or Su or Sb) + Fpe Pe
2) DL + Pe + 0.4(Lr or Su or Sb)
f) Seismic: DL + F + E + 0.1Sb + Fp Pi
g) Gravity Loads for Fixed Roofs with Suspended
Floating Roofs:
1) DL + Df + (Lr or S) + Pe + 0.4(Pfe or Lf1 or Lf2)
2) DL + Df + (Pfe or Lf1 or Lf2) + 0.4[(Lr or S) + Fpe

DESIGN & CALCULATION – API 650


KOMBINASI BEBAN
a) Fluid and Internal Pressure: DL + F + Pi
b) Hydrostatic Test: DL + Ht + Pt
c) Wind and Internal Pressure: DL + W + Fp Pi
d) Wind and External Pressure: DL + W + Fpe Pe
e) Gravity Loads:
1) DL + (Lr or Su or Sb) + Fpe Pe
2) DL + Pe + 0.4(Lr or Su or Sb)
f) Seismic: DL + F + E + 0.1Sb + Fp Pi
g) Gravity Loads for Fixed Roofs with Suspended Floating
Roofs:
1) DL + Df + (Lr or S) + Pe + 0.4(Pfe or Lf1 or Lf2)
2) DL + Df + (Pfe or Lf1 or Lf2) + 0.4[(Lr or S) + Fpe Pe]

17
10/7/2021

DESIGN & CALCULATION – API 650


KAPASITAS TANGKI

 Kapasitas Maksimum
/ Maximum Capacity
volume dari produk
dalam tangki ketika
tangki diisi sampai
batas desain cairan /
design liquid level (H)

 Kapasitas Jaringan /
Net Working Capacity
volume dari produk yang dalam tangki pada kondisi operasi normal.
Kapasitas jaringan sama dengan kapasitas maksimum dikurangi
dengan volume sisa pada tangki, dikurangi aturan batas proteksi
tumpah (overfill protection).

DESIGN & CALCULATION – API 650


HARDNESS / KEKERASAN LASAN
a. Untuk service H2S, kekerasan pada lasan dan HAZ
harus sesuai dengan spesifikasi tambahan H2S (Data
Sheet, Line 5)
b. Jika dispesifikasikan oleh pihak pembeli, kekerasan
lasan untuk material dinding Group IV, IVA, V, or VI
harus dievaluasi dengan salah satu metode ini.
1. WPQT untuk harus mencakup uji kekerasan pada lasan dan HAZ
dari pelat uji. Metode pengujian harus disetujui bersama
2. Semua lasan oleh lasan otomatis harus diuji kekerasannya pada
permukaan sisi produk. Kecuali dispesifikasikan, satu pengujian
dilakukan untuk setiap lasan vertikal dan tiap 30 m (100 ft) dari
lasan melingkar

18
10/7/2021

DESIGN & CALCULATION – API 650


II. DESAIN TANGKI

Tangki dapat dibagi menjadi tiga bagian utama : Dasar,


Dinding, dan Atap. Dalam design tangki, dinding adalah
bagian yang paling penting untuk menahan tekanan cairan.

2.1 Design Dasar Tangki

Dasar tangki terbuat dari pelat baja dengan ketebalan


minimum 6 mm, diluar corrosion allowance yang di
dihubungkan dengan pelat lainnya dengan system lapis
ulang, dan di las dengan filled penuh.

DESIGN & CALCULATION – API 650


DESAIN DASAR TANGKI

2.1 Design Dasar Tangki (lanjutan)

Transfer beban dengan tebal pelat dasar yang lebih tipis tidak
dimungkinkan. Pengecualian dari hal tersebut dengan memakai
pelat melingkar (annular plate) yang bertindak sebagai bagian
transisi antara dinding dan dasar tangki.

Pelat melingkar dengan ketebalan (biasa nya lebih besar dari


tebal pelat dasar) ini berada di bawah dinding tangki mengalami
stress yang besar di karenakan pembengkokan yang terjadi
oleh tekanan cairan horizontal yang mendesak bagian bawah
dari dinding tangki.
Pelat melingkar digunakan sesuai dengan kondisi pada API 650
para 5.5. Sambungan pada pelat melingkar adalah lasan jenis
butt dengan backing strip.

19
10/7/2021

TIPE DASAR TANGKI


 Desain dasar tangki sangat penting karena sedimen, air atau
settlement dapat terjadi.
 Korosi biasa terjadi paling buruk pada dasar tangki dan sangat
menentukan life time tangki
 Desain harus mepertimbangkan kemudahan untuk memindahkan
keberadaan air atau sisa produk dan kemudahan proses
pembersihan tangki

TIPE DASAR TANGKI

20
10/7/2021

TIPE DASAR TANGKI

TIPE DASAR TANGKI

21
10/7/2021

DESIGN & CALCULATION – API 650


DESAIN DASAR TANGKI

ANNULAR BUTT WELD

BOTTOM LAYOUT

DESIGN & CALCULATION – API 650


DESAIN DASAR TANGKI

ANNULAR–TO–BOTTOM JOINT
THREE PLATE LAP JOINT

22
10/7/2021

DESIGN & CALCULATION – API 650


DESAIN DASAR TANGKI

Spasi Sambungan Three Plate pada Annular

DESIGN & CALCULATION – API 650


DRIP RING

 Jika dispesifikasikan (Data Sheet, Line 12), drip ring fondasi harus dibuat
untuk menghindari masuknya air ke celah antara dasar tangki dan
fondasi
 Drip ring harus memenuhi ketentuan sbb:
1. Material harus carbon steel dengan tebal minimum 3 mm (1/8-in.)
2. Semua sambungan radial antara bagian drip ring harus continuously
seal-welded
3. Drip ring harus memanjang paling tidak 75 mm (3 in.) dari ujung
fondasi dan turun ( sampai 90°)
4. Bagian atas dan bawah drip ring dan bagian atas dari FPP harus
dicoating

23
10/7/2021

DESIGN & CALCULATION – API 650


DESAIN PELAT ANNULAR TANGKI

 Pelat annular diperlukan jika pelat dinding (course 1) didesain


dengan material Group IV, IVA, V, or VI, dengan ketentuan:
 maximum product stress untuk course 1 lebih besar
dari 160 MPa (23,200 lbf/in.2) atau
 hydrostatic test stress untuk course 1 lebih besar dari 171
MPa (24,900 lbf/in.2)

 Lebar pelat annular pada sisi dalam dinding paling tidak 600
mm (24 in.) dari bagian dalam dinding dan lasan lap dengan
pelat dasar
 Lebar pelat annular pada sisi luar dinding paling tidak 2”
(50mm)

DESIGN & CALCULATION – API 650


DESAIN PELAT ANNULAR TANGKI

 Lebar pelat annular yang lebih besar diperlukan


sesuai dengan:

24
10/7/2021

DESIGN & CALCULATION – API 650


DESAIN PELAT ANNULAR TANGKI

 Stress yang dipakai adalah maksimum stress pada dinding lapis


pertama (yang lebih besar antara product stress atau
hydrostatic test stress).

 Product Stress = [(td – CA)/Corroded t ] Sd …………Edisi 12

DESIGN & CALCULATION – API 650


DESAIN DINDING TANGKI

2.2 Design Dinding Tangki

Dinding tangki dibuat dari sejumlah pelat, biasanya dengan


tinggi 1.5 – 2.5 m (6 – 8 feet). Tebal pelat menurun secara
gradual keatas dikarenakan beban cairan horizontal yang lebih
kecil.

Tebal pelat pada puncak dinding dibatasi dengan minimum


5 – 10 mm, tergantung pada diameter tangki.

Dinding tangki dilengkapi dengan sejumlah asessoris dan


mounting seperti tangga, nozzle untuk pipa dan sambungan
instrument, manhole dll

25
10/7/2021

DESIGN & CALCULATION – API 650


PERHITUNGAN TEBAL DINDING (API 650 5.6.3)
Perhitungan tebal pelat dinding dapat dilakukan dengan beberapa
metoda antara lain : Metoda 1-Foot, Metoda Variable design
(biasanya dipakai untuk tangki ukuran diameter 200 feet keatas dan
memakai program komputer)

Perhitungan ketebalan dinding tangki berdasarkan metode 1– Foot adalah


sebagai berikut :

 dengan : td = tebal desain dinding tangki (inch)


 D = Diameter minimal tangki (feet)
 H = Level cairan dalam tangki (feet)
 G = Spesifik graviti dari cairan yang simpan dalam tangki
 CA = Corrosion allowance (in)
 Sd = Stress yang diizinkan untuk kondisi desain (lbf/in2)

DESIGN & CALCULATION – API 650


PERHITUNGAN TEBAL DINDING (API 650 5.6.3)

 Sd dan St tergantung dari jenis material yang dipakai,


sesuai dengan tabel 5-2
 Spesifikasi material yang diterima: ASTM, CSA, ISO,
EN dan National Standard (grade 235, 250 dan 275)

26
10/7/2021

DESIGN & CALCULATION – API 650


DESAIN DINDING TANGKI

 Tebal dinding tangki yang dipakai adalah nilai yang


terbesar dari tebal dinding desain (td) termasuk
corrosion allowance atau tebal dinding hidrostatik
test (tt), tetapi tebal dinding tangki tidak boleh lebih
kecil dari persyaratan pada API 650 5.6.1.1 atau
tabel dibawah ini:

DESIGN & CALCULATION – API 650


DESAIN DINDING TANGKI

2.2 Design Dinding Tangki (Lanjutan)

Untuk nozzle yang lebih besar dari 2“, pelat penguat diperlukan
untuk mengimbangi berkurangnya kekuatan yang disebabkan
lobang pada dinding. Tergantung dari ukuran dan tebal pelat
dinding, nozzle yang lebih besar difabrikasi di shop dan di stress
relieved sebelum di pasang.

Tangki dengan atap terapung dilengkapi dengan wind girder


utama (penahan angin) untuk menjaga kebulatan tangki saat
menahan beban angin. Penahan angin utama ini diletakkan
pada dekat puncak tangki. Penahan angin tambahan kadang
kadang diperlukan baik untuk tangki atap tetap maupun atap
terapung, untuk menghindari penekukan (buckling) pada
dinding tangki yang disebabkan angin dan / atau vakum.

27
10/7/2021

DESIGN & CALCULATION – API 650


SHELL PLATE & LAYOUT DRAWING

DESIGN & CALCULATION – API 650


SHELL MANHOLE

28
10/7/2021

DESIGN & CALCULATION – API 650


SHELL NOZZLE & REINFORCEMENT PLATE

DESIGN & CALCULATION – API 650


DIMENSI SHELL NOZZLE & MANHOLE

29
10/7/2021

DESIGN & CALCULATION – API 650


MINIMUM WELD REQUIREMENT FOR OPENING IN SHELLS

DESIGN & CALCULATION – API 650


MINIMUM WELD REQUIREMENT FOR OPENING IN SHELLS

30
10/7/2021

DESIGN & CALCULATION – API 650


DESAIN ATAP TANGKI

2.3 Design Atap Tangki

Seluruh atap dan struktur


penyangga harus di design untuk
menahan beban mati + beban
hidup seragam tidak kurang dari
20 lbf/ft2 luas projeksi atap. Pelat
atap harus mempunyai tebal
nominal minimum 3/16 inci
(5mm).

Tebal yang lebih besar mungkin LAP WELD


dibutuhkan untuk atap swasangga

DESIGN & CALCULATION – API 650


DESAIN ATAP TANGKI

Atap yang di-design dengan


frangible joint harus memenuhi:
Untuk Diameter diatas 15m (50 feet)
 Lasan filet kontinu antara pelat atap
dan siku atap tidak melebihi 3/16 in
 Kemiringan atap pada pautan siku
puncak tidak lebih dari 2 in dalam
12 in
 Tipe Roof-to-top angle compression
ring sesuai dengan details a - e pada
Figure F-2.
 Roof support members tidak boleh
dilas ke atap tangki.
ROOF FRANGIBLE JOINT
 Luas penampang lintang pertemuan
atap ke dinding A, harus lebih kecil
dari :

31
10/7/2021

DESIGN & CALCULATION – API 650


DESAIN ATAP TANGKI

Untuk Diameter lebih besar dari 9 m


(30 feet) dan lebih kecil dari 15 m (50 feet)

 Memenuhi semua persyaratan untuk


diameter tangki diatas 15m (50 feet)
 Tinggi tangki 9 m (30 ft) atau lebih besar
 Kemiringan atap pada pautan siku puncak
tidak lebih dari 3/4:12
 Lekatan (termasuk nozzles dan manholes)
pada dinding tangki harus didesain paling
tidak 100 mm (4 in.) dari vertical shell
movement tanpa rupture
 Lasan pada dasar tangki adalah butt-
welded.

DESIGN & CALCULATION – API 650


SAMBUNGAN ATAP TANGKI KE TOP ANGLE

 Pelat atap harus dilas pada sisi atas dengan lasan fillet penuh atau
lasan butt
 Untuk atap yang frangible, pelat atap harus menempel pada top
angle dengan lasan fillet pada sisi atas saja
 Untuk tangki dengan diameter lebih kecil atau sama dengan 9 m
(30 ft) dengan atap jenis cone dengan penyangga / supported cone
roof, ujung atas dari dinding boleh dibuat / flanged sebagai ganti
dari top angle.
 Ukuran top angle tidak boleh lebih kecil dari ukuran pada tabel ini

32
10/7/2021

DESIGN & CALCULATION – API 650


MANHOLE ATAP TANGKI

DESIGN & CALCULATION – API 650


NOZZLE ATAP TANGKI

33
10/7/2021

DESIGN & CALCULATION – API 650


PERHITUNGAN DESAIN

NO DESKRIPSI PEMERIKSAAN KRITERIA PENERIMAAN

1 Shell, roof, and bottom API 650 5.6 (Desain Shell), 5.4 dan 5.5 (Desain
Bottom), 5.10 (Desain Roof)
2 Opening Reinforcement API 650 5.7.8.4

3 Tank Stability API 650 5.11

4 Wind girder requirement API 650 5.9

5 Support and shell around support API 650 Appendix P

6 Anchor bolt API 650 Appendix F.7

7 Internal (column, rafter, girder) API 650 5.10.3.4 (Column)

8 Perhitungan Venting API 2000

DESIGN & CALCULATION – API 650


PERHITUNGAN TEBAL DINDING (API 650 5.6.3)

Perhitungan Tebal Dinding dengan Metoda Variable-Design-Point


 Dengan memakai prosedur ini biasanya terjadi reduksi tebal

dinding dan berat material, tetapi yang lebih penting adalah


potensi untuk konstruksi tangki dengan diameter yang lebih
besar dengan pengurangan tebal pelat.
 Desain dengan metoda variable-design-point memberikan tebal

dinding pada titik desain yang dihasilkan dari kalkulasi ini relatif
dekat dengan stres keliling dari dinding tangki. Metoda ini dapat
digunakan jika Pembeli tidak menspesifikasikan untuk memakai
metoda 1-foot dan jika memenuhi kondisi ini:
 L = (6Dt)0.5, (in.),

 D = diameter tangki, (ft),

 t = tebal dinding terbawah, diluar corrosion allowance (in.),

 H = maximum design liquid level, (ft).

34
10/7/2021

DESIGN & CALCULATION – API 650


PERHITUNGAN TEBAL DINDING (API 650 5.6.3)

Perhitungan Tebal Dinding dengan Metoda Elastic Analysis


 Untuk tangki dengan L/H lebih besar dari 1000/6 (2 in US

Customary units), penentuan ketebalan dinding tangki harus


berdasarkan metoda elastic analysis dengan mengkalkulasi
tekanan keliling / circumferential stress dari dinding hingga lebih
rendah dari stres yang diizinkan sesuai tabel Tables 5-2a dan 5-
2b.
 Batasan kondisi untuk menganalisis dengan mengasumsi
momen plastik penuh yang disebabkan oleh yielding dari pelat
dinding dan kondisi zero radial growth.

DESIGN & CALCULATION – API 650


PERHITUNGAN PELAT PENGUAT DASAR API 650 5.7.8.4

Lebar minimal pelat penguat dasar pada clean out door (COD)
harus 250 mm di tambah gabungan antara tebal pelat badan pada
COD tersebut dan pelat penguat dinding.

 Tebal pelat penguat dasar ditentukan berdasarkan rumus:

 Dimana:
 tb = tebal minimum pelat penguat dasar, mm
 h = tinggi vertikal bukaan, mm
 b = lebar horizontal bukaan, mmi
 H = permukaan cairan maksimum desain, m
 G = berat jenis, tidak kurang dari 1

35
10/7/2021

DESIGN & CALCULATION – API 650


PREHEAT TREATMENT (API 650 7.2.1.2)

Preheat harus dilakukan jika temperatur metal dibawah temperatur


pada tabel 7-1.

DESIGN & CALCULATION – API 650


POST WELDED HEAT TREATMENT (API 650 5.7.4)

PWHT dilakukan untuk menghilangkan tegangan thermal yang


terjadi karena proses pengelasan. Kondisi kondisi dimana proses ini
perlu dilakukan sbb:
 Semua sambungan tipe flush pada dinding tangki atau fitting tipe flush
COD
 Pada material dinding tangki kelompok I, II, III atau IIIA, semua
sambungan bukaan dengan NPS 12 atau lebih atau pada thickened
insert plate dengan tebal lebih dari 25 mm (1 in).
 Pada material dinding tangki kelompok IV, IVA, V atau VI, Semua
sambungan bukaan yang memakai penguat pada dinding atau pada
thickened insert plate dengan tebal lebih dari 12.5 mm (1/2 in).

36
10/7/2021

DESIGN & CALCULATION – API 650


WIND LOAD ON TANK (OVERTURNING STABILITY)

 Tangki tidak memerlukan anchor / stabil berdasarkan


beban angin jika memenuhi persyaratan:

DESIGN & CALCULATION – API 650


WIND LOAD ON TANK (OVERTURNING STABILITY)

 Mpi = (Load internal pressure x luas penampang atap) x D/2

 Mf = Berat Liquid x D/2

 Mdl = (Berat shell + Berat roof) x d/2

 Mw = (pressure wind horizontal x H x H/2) + (Pressure wind


vertical x luas penampang atap x D/2)

37
10/7/2021

DESIGN & CALCULATION – API 650


WIND LOAD ON TANK (OVERTURNING STABILITY)

 Mpi = momen pada sambungan shell-to-bottom disebabkan


design internal pressure,
 Mw = overturning moment pada sambaungan shell-to-bottom
joint yang disebabkan tekanan angin horizontal dan vertikal
 MDL = momen pada sambungan shell-to-bottom joint yang
disebabkan oleh berat shell dan bagian roof yang di support
oleh shell
 MF = momen pada sambungan shell-to-bottom disebabkan
liquid dengan berat liquid wa seperti didefinisikan pada E.2.2
(menggunakan SG 0.7 dan tinggi ½ design liquid height H

DESIGN & CALCULATION – API 650


WIND LOAD ON TANK (OVERTURNING STABILITY)

38
10/7/2021

DESIGN & CALCULATION – API 650


KOMBINASI BEBAN TANGKI

 Fluid and Internal Pressure:


 Hydrostatic Test:
 Wind and Internal Pressure:
 Wind and External Pressure:
 Gravity Loads:
 Seismic:
 Gravity Loads for Fixed Roofs with Suspended
Floating Roofs:

PROSEDUR KONSTRUKSI TANGKI


 RENCANA INSPEKSI DAN PENGUJIAN
(INSPECTION & TEST PLAN)
 PROSEDUR KERJA
 PROSEDUR PEMERIKSAAN MATERIAL MASUK
 PROSEDUR FABRIKASI
 PROSEDUR EREKSI
 PROSEDUR PENGUJIAN
 PROSEDUR PEMERIKSAAN KETEGAKAN
 PROSEDUR PEMERIKSAAN PEAKING, BANDING DAN
ROUNDESS
 PROSEDUR PENGUJIAN DIESEL/ PENETRATING OIL
 PROSEDUR VACUUM BOX TES
 PROSEDUR PNEUMATIK REINFORCEMENT PAD

39
10/7/2021

PROSEDUR KONSTRUKSI TANGKI

 PROSEDUR UJI HIDROSTATIK


 PROSEDUR NDT
 PROSEDUR UJI CAIRAN PENETRAN / MAGNETIK
PARTIKEL
 PROSEDURE UJI RADIOGRAPHI
 PROSEDUR UJI ULTRASONIK
 PROSEDUR UJI TOFD (JIKA DIPERLUKAN)
 PROSEDUR PERBAIKAN (TERMASUK CACAT LASAN)
 PROSEDUR PENGECATAN
 PROSEDUR SURFACE PREPARATION / COATING
 PROSEDUR DETEKSI HOLIDAY/PINHOLE

API 650 – KALKULASI


BEBAN ANGIN

40
10/7/2021

API 650 – DESAIN


KALKULASI BEBAN ANGIN

Contoh Kalkulasi Desain Seismik - Tangki Penimbun

Diameter : 12,196 meter


Tinggi : 7,315 meter
Tinggi Cairan : 7,315 meter
Zone Seismik :2
Material : A 283 Gr C, Fy = 30 ksi
Design External Pressure : 2”WC (0.072 psig)
Design Internal Pressure : 4”WC (0.144 psig)
Spesifik Gravity : 0.85
Corrosion Allowance : 0.0 inch
Wind Velocity : 20.00 mph

Tebal Metal
 Pelat Dinding Course #1 - #5 : 0.25 inch (termasuk CA)
 Pelat Dasar : 0.25 inch (termasuk CA)

API 650 – DESAIN


KALKULASI BEBAN ANGIN

WIND OVERTURNING STABILITY CHECK

 wa [N.m] : 1085,056
 Mw - moment due to wind (hor+ver) press [N.m] : 428,397
 Mpi - moment due to internal pressure [N.m] : 705,257
 Mf - moment due to tank liquid [N.m] : 81774,3
 Mdl - moment due to shell & roof [N.m] : 1022263

Persyaratan stabil berdasarkan beban angin:


1. 0.6 (428,397) + 705,257 < 1022263 /1.5
705,256 < 681508 OK
2. 428,397 + 0.4 (705,257) < (1022263 + 81774,3)/2
710,499 < 552018 OK
 Tangki Stabil, Anchors tidak diperlukan berdasarkan API 650 5.11

41
10/7/2021

API 650 – DESAIN & KALKULASI


WIND GIRDER

API 650 – DESIGN


KALKULASI WIND GIRDER

42
10/7/2021

API 650 – DESIGN


KALKULASI WIND GIRDER

Tank Diameter : 130 feet


Tank Height : 48 feet
Design Wind : 90 mph
Shell Thickness : ¼ inch

1. API 650 Paragaf 5.9.6


Z = 0.0001 D2H2
D = Diameter Tangki, feet
H2 = Tinggi Dinding Tangki, feet

Z = 0.0001 (130)2 (48)


= 81.1 In3

2. Penyesuaian Kecepatan Angin

Z’ = 81.1 (90/100)2 = 65.7 In3

API 650 – DESIGN


KALKULASI WIND GIRDER

3. API 650 Tabel 5.20 dan Gambar 5.20

Lihat Detail e, untuk b = 24 dan t = ¼’

Z’ = 71.72 In3 > 65.7 In3

43
10/7/2021

API 650 – DESIGN


KALKULASI WIND GIRDER

 Lebar bersih wind girder 24 inch.


Buat tambahan sesuai dengan
gambar:
 3 inch untuk flange bagian
luar dan painter trolley
 2-1/2 inch handrail

 3 inch untuk top angle

 Total tambahan 8-1/2 inch

 Gunakan detail e, dengan b =


32-1/2 inch

API 650 – DESIGN


KALKULASI WIND GIRDER

INTERMEDIATE WIND GIRDER


Open Top Tank
• Diameter : 180 feet
• Tinggi : 48 feet
• Kec Angin Desain : 102 mph
• Jarak antara dasar
tangki and wind girder : 44.5 feet

Tebal dinding tangki


• Course 1 : 0.960 inch
• Course 2 : 0.760 inch
• Course 3 : 0.600 inch
• Course 4 : 0.443 inch
• Course 5 : 0.313 inch
• Course 6 : 0.313 inch

44
10/7/2021

KALKULASI WIND GIRDER


INTERMEDIATE WIND GIRDER

1. Hitung maximum tinggi dinding yang tidak di perkuat (unstiffened), H1

Dimana: t = 0.313 inch


D = 180 feet

H1 = 600,000 (0.313) SQRT [(0.313/180)^3]


= 13.6 feet

2. Koreksi Kecepatan Angin

H1 = H1’ (100/v)^2 = 13.6 (100/102)^2 = 13.1 feet

KALKULASI WIND GIRDER


INTERMEDIATE WIND GIRDER

3. Kalkulasi lebar transformasi setiap course dinding tangki yang berada dibawah
wind girder, sesuai dengan API 650 3.9.7.2a

Wtr1 =8 SQRT [ (0.313/0.960)^3 ] = 0.5 feet


Wtr2 =8 SQRT [ (0.313/0.760)^3 ] = 0.9 feet
Wtr3 = 8 SQRT [ (0.313/0.60)^3 ] = 1.6 feet
Wtr4 = 8 SQRT [ (0.313/0.443)^3 ] = 3.3 feet
Wtr5 = 8 SQRT [ (0.313/0.313)^3 ] = 12.5 feet

4. Jumlah Lebar yang ditransformasi dari setaip course adalah Wtr = 18.8
feet
Karena tinggi dari dinding yang ditransformasi lebih besar dari
maximum tinggi dari dinding yang tidak diperkuat (unstiffened), maka
intermediate wind girder diperlukan

45
10/7/2021

KALKULASI WIND GIRDER


INTERMEDIATE WIND GIRDER

5. Tentukan lokasi intermediate wind girder


Agar stabilitas dinding, letakkan wind girder ditengah-tengah lebar yang
ditransformasi sesuai dengan API 650 3.9.7.3.1
½ Wrt = 9.4 feet.
Karena lebar transformasi ini lebih kecil dari Wtr5, maka lokasi intermediate wind
girder pada course 5 dejauh 9.4 dibawah top wind girder.

6. Tentukan apakah dipelukan wind girder lainnya dibawah intermendiate wind


girder dengan prosedur perhitung yang sama.

Jarak antara top dan intermediate dan dasar dinding tangki


= 16 – 3.5 – 9.4 = 3.1 feet

7. Rekalkulasi tinggi dinding tangki yang ditransformasi = 3.1 feet

Jumlah tinggi tangki yang ditransformasi sekarang adalah 9.4 feet (1/2 dari Wtr)

KALKULASI WIND GIRDER


INTERMEDIATE WIND GIRDER

8. Bandingkan tinggi dinding tangki


Karena tinggi dinding yang ditransformasikan lebih kecil dari tinggi maximum
dinding yang tidak diperkuat (unstiffened), wind girder tambahan tidak
diperlukan (API 650 3.9.7.3)

9. Tentukan Modulus section yang diperlukan untuk wind girder

Dengan D = 180 feet dan H1 = 9.4 feet

Z = 0.0001 (180^2) (9.4)


= 30.5 In^3

10. Koreksi Kecepatan Angin

H1 = H1’ (100/v)^2 = 30.5 (100/102)^2 = 31.7 feet

Pilih jenis wind girder dengan mudulus section seperti diatas. Lihat API 650
Gambar 3-20

46
10/7/2021

API 650 – APPENDIX E


DESAIN SEISMIK TANGKI

API 650 – DESAIN SEISMIK TANGKI


KRITERIA TANGKI STABIL BERDASARKAN BEBAN SEISMIC

47
10/7/2021

API 650 – DESAIN SEISMIK TANGKI

 Mrv : Ringwall moment – Portion of the total overturning moment that


acts at the base of the shell perimeter Nm (ft.lb.)
 wt : Tank and roof weight acting at base of shell N/m (lbf/ft)
 Av : Vertical earthquake acceleration coefficient, %g
 wa : Resisting force of tank content per unit length of shell
circumference that maybe be used to resist the shell overturning
moment, N/m (lbf/ft)
 Ws : Total weight of tank shell and appurtenances, N (lbf)
 wrs : Roof loading acting on the shell, including 10% of the specified
snow load, n/m (lbf/ft)

API 650 – DESAIN SEISMIK TANGKI

 Ringwall Moment, Mrw:

 Slab Moment, Ms:

48
10/7/2021

API 650 – KALKULASI


DESAIN SEISMIK TANGKI

KALKULASI DESAIN SEISMIC


API 650 APPENDIX E

Contoh Kalkulasi Desain Seismik - Tangki Penimbun

Diameter : 19 feet
Tinggi : 30 feet
Tinggi Cairan : 29 feet
Zone Seismik :2
Material : A 283 Gr C, Fy = 30 ksi
Design External Pressure : 2”WC (0.072 psig)
Design Internal Pressure : 4”WC (0.144 psig)
Spesifik Gravity : 0.85
Corrosion Allowance : 0.0 inch
Wind Velocity : 20.00 mph

Tebal Metal
 Pelat Dinding Course #1 - #5 : 0.25 inch (termasuk CA)
 Pelat Dasar : 0.25 inch (termasuk CA)

49
10/7/2021

KALKULASI DESAIN SEISMIC


API 650 APPENDIX E

SEISMIC DATA
 Minimum Yield Strength of Bottom Plate [lb./sq.in] : 30000.
 Minimum Yield Strength of Weld Material [lb./sq.in] : 30000.
 Nominal Thickness of Bottom Plate (tb) [in] : 0.2500
 Seismic Use Group (SUG) : 2.0000
 Friction Factor : 0.4000
 Importance Factor : 1.0000
 Earthquake Type :M
 Site Class : 1.0000
 Spectral Acceleration Adjustment Coefficient (K) : 1.5000
 Scaling Factor (Q) : 0.6667
 Transtiional Period (TL) : 0.1000
 Mapped maximum earthquake for short periods (Ss) : 0.7500
 Mapped maximum earthquake for 1 sec periods (S1) : 0.3750
 Mapped maximum earthquake for 0 sec period (S0) : 0.3000

KALKULASI DESAIN SEISMIC


API 650 APPENDIX E

Site-Specific Ground Motion

 Design Fluid Weight [lb] : 0.43534E+06

 Sp -design level peak accel for non ASCE : 0.0000


 Ss -MCE at period of 0.2 seconds : 0.7500
 S0 -MCE at period of 0.0 seconds : 0.3000
 S1 -MCD at period of 1.0 seconds : 0.3750
 SDS-design spectral accel parameter : 0.4000

 FA -acceleration based site coefficient : 0.8000


 FV -velocity based site coefficient : 0.8000
 TS - FvS1 / FaSs : 0.5000
 TC -convective sloshing period [sec] : 2.5195

50
10/7/2021

KALKULASI DESAIN SEISMIC


API 650 APPENDIX E
 Ac -convective spectral accel parameter : 0.23630E-02
 Ai -impulsive spectral accel parameter : 0.11429
 Wc -effective convective fluid weight [lb] : 65600.
 Wi -effective impulsive fluid weight [lb] : 0.37317E+06
 Vc -convective liquid base shear [lb] : 155.02
 Vi -impulsive liquid base shear [lb] : 45250.
 V -total design base shear [lb] : 45250.
 VS -shear resistance [lb] : 0.17914E+06
 Xc -ring wall convective moment arm [ft] : 23.861
 Xi -ring wall impulsive moment arm [ft] : 12.714
 XCS-slab convective moment arm [ft] : 23.897
 XIS-slab impulsive moment arm [ft] : 15.640
 WS -shell+appurtenances weight [lb] : 14626.
 Wrs-roof, framing 10% snow weight [lb] : 3943.2

 Mrw-ringwall overturning moment [ft.lb] : 0.58052E+06


 Ms -slab overturning moment [ft.lb] : 0.70530E+06

KALKULASI DESAIN SEISMIC


API 650 APPENDIX E

 AV -vertical acceleration parameter : 0.56000E-01


 Ge -effective specific gravity : 0.83096
 wa -resisting annulus force [lb./in] : 48.838
 wt -tank + roof weight at shell base [lb./in] : 25.924

 J -the anchorage ratio : 1.8065


 L -reqd min annular plate projection [ft] : 0.0000

 Anchorage ratio too large, anchors needed

51
10/7/2021

KALKULASI DESAIN SEISMIC


API 650 APPENDIX E

ANCHOR BOLT DETAILS - Section 5.12


API-650 11th Edition, June 2007

Allowable
CASES UPLIFT [lb] Bolt Stress Load/Bolt [lb]
[lb/sq.in]
Design Pressure 0.89441E+06 15000 0.11180E+06
Test Pressure 2000
Failure Pressure 0.21655E+07 28800 0.27069E+06
Wind Loading 28800
Seismic OPE 0.10365E+06 28800 12956
Design Press + Wind 0.89578E+06 20000 0.11197E+06
Design Press + Seismic 0.10166E+07 28800 0.12708E+06

KALKULASI DESAIN SEISMIC


API 650 APPENDIX E

Anchor bolts are required.

 Number of Bolts :8
 Bolts Diameter : 3.5 in
 Max Bolt Stress : 35220 lb/sq.in
 Bolt Spacing : 7.46 feet

52