Power System 1 EPO520
Chapter 4 – Power System Protection (Overcurrent)
Introduction
When faults occur, excessive currents will flow in the power system.
These fault currents can be several orders of magnitude larger than normal operating currents
If not removed quickly, they may cause:
o Insulation damage
o Conductor melting
o Mechanical damage to windings and busbars
o Fire and explosion
It is therefore important to have power system protection in order to:
o Remove the faulted equipment from the system
o Maintain the unfaulted system in order to continue service
System Protection Components
Protection systems have three basic components:
1. Instrument transformer
2. Relays
3. Circuit-breakers
Figure 10.1 shows a simple overcurrent protection schematic with:
1. One type of instrument transformer, i.e. the current transformer (CT)
2. An overcurrent relay (OC)
3. A circuit breaker (CB) for a single phase line
Figure 10.1: Overcurrent protection schematic
D. Johari, FKE UiTM 1
Power System 1 EPO520
The function of the current transformer (CT):
o To reproduce secondary current which will activate the relays
o It converts primary currents I (kA range) to secondary currents I’ (~ 0-5A range) for
convenience of measurement, with the following advantages:
Safety: Provide electrical isolation from the power system so that personnel working
with relays will work in a safer environment.
Economy: Lower level inputs enable relays to be smaller, simpler & less expensive.
Accuracy: Accurately reproduce power system currents & voltages over wide operating
ranges
The function of the overcurrent (OC) relay:
o To discriminate between normal operation and fault condition
o Receive signal (or current) from the secondary winding of the current transformer.
o Has an operating coil, which is connected to the CT secondary winding & a set of contacts.
o When I’ exceeds a specified “pick up” value, the operating coil causes the contacts to close.
o When the relay contacts close, the trip coil of the circuit breaker is energized, which then
causes the circuit breaker to open
The function of the circuit breaker (CB):
o To separate between the faulty and non-faulty parts in power systems
D. Johari, FKE UiTM 2
Power System 1 EPO520
Instrument Transformer
There are two basic types of instrument transformers:
o Voltage transformers (VT) formerly called potential transformer (PT)
o Current transformers (CT)
Figure 10.2 shows a schematic representation for the VT and CT
o The VT reduces the primary voltage and the CT reduces the primary current to much lower,
standardized levels suitable for operation of relays.
Figure10. 2: VT and CT schematic
For system protection purposes, VTs are generally considered to be sufficiently accurate.
o Therefore, the VT is usually modelled as an ideal transformer, where
1
V ' V
n
V’ is a scaled-down representation of V and is in phase with V
o Standard VT ratios are given in Table 10.1.
Table 10.1: Standard VT ratios
Voltage Ratios
1:1 2:1 2.5:1 4:1 5:1 20:1 40:1
60:1 100:1 200:1 300:1 400:1 600:1 800:1
1000:1 2000:1 3000:1 4500:1
D. Johari, FKE UiTM 3
Power System 1 EPO520
For current transformer,
o Standard CT ratios are given in Table 10.2.
Table 10.2: Standard CT ratios
Current Ratios
50:5 100:5 150:5 200:5 250:5 300:5 400:5
450:5 500:5 600:5 800:5 900:5 1000:5 1200:5
1500:5 1600:5 2000:5 2400:5 2500:5 3000:5 3200:5
4000:5 5000:5 6000:5
o An approximate equivalent circuit of a CT is shown in Figure 10.7
Figure 10.7: CT equivalent circuit
Where Z’ = CT secondary leakage impedance
Xe = (Saturable) CT excitation reactance
ZB = Impedance of terminating device (such as relay, including leads)
o The total impedance ZB of the terminating device is called the burden
o Associated with the CT equivalent circuit is an excitation curve that determines the
relationship between the CT secondary voltages E’ and excitation current Ie.
o Excitation curves for a multiratio bushing CT with ANSI classification C100 are shown in
Figure 10.8.
D. Johari, FKE UiTM 4
Power System 1 EPO520
Figure 10.8: Excitation curves for a multi ratio bushing CT with a C100 ANSI accuracy classification
o Using the CT equivalent circuit and excitation curves, the following procedure can be used
to determine CT performance.
STEP 1 Assume a CT secondary output current I’
STEP 2 Compute E’ = (Z’ + ZB) I’
STEP 3 Using E’, find Ie from the excitation curve
STEP 4 Compute I = n (I’ + Ie)
STEP 5 Repeat steps 1 to 4 for different values of I’, then plot I’ versus I
o The CT error is given by:
Ie
CT error 100 0 0
I ' I e
D. Johari, FKE UiTM 5
Power System 1 EPO520
Example 1 (Glover 10.1)
Evaluate the performance of the multiratio CT in Figure in 10.8 with a 100:5 CT ratio, for the
following secondary output currents and burdens:
a) I’ = 5 A, ZB = 0.5
b) I’ = 8 A, ZB = 0.8
c) I’ = 15 A, ZB = 1.5
Also, compute the CT error for each output current.
D. Johari, FKE UiTM 6
Power System 1 EPO520
Example 2 (Glover 10.2)
An overcurrent relay set to operate at 8A is connected to the multiratio CT in Figure 10.8 with a
100:5 CT ratio. Will the relay detect a 200A primary fault current if the burden ZB is
a) 0.8
b) 3.0
D. Johari, FKE UiTM 7
Power System 1 EPO520
Overcurrent Relays
There are two types of overcurrent relays:
o Instantaneous overcurrent relays
o Time-delay overcurrent relays
Input to the overcurrent relay operating coil is the CT secondary current I’.
Instantaneous overcurrent relays respond to the magnitude of their input current, as shown by
the trip and block regions in Figure 10.9.
o If the magnitude of I’ exceeds a specified adjustable current magnitude IP, called the pickup
current, the relay contacts close instantaneously to energize the circuit breaker trip coil.
o If I’ is less than IP, then the relay contacts remain open, blocking the trip coil.
Figure 10.9: Instantaneous overcurrent relay block and trip regions
Time-delay overcurrent relays also respond to the magnitude of their input current but with an
intentional time delay.
o As shown, the time delay depends on the magnitude of the relay input current.
o If I’ is a large multiple of IP, then the relay operate (or trips) after a small time delay
o For smaller multiples of IP, the relay trips after a longer time delay
o If I’ < IP, the relay remains in the blocking position.
Figure 10.10: Time-delay overcurrent relay block and trip regions
D. Johari, FKE UiTM 8
Power System 1 EPO520
For a typical time-delay overcurrent relay, the characteristic curves are shown in Figure 10.12.
o These relays have two settings:
1. Current tap setting: The pickup current, IP in amperes
2. Time dial setting: The adjustable amount of time delay
Figure 10.12: Typical time curves type CO-8 time-delay overcurrent relay
The characteristic curves are usually shown with operating time in seconds versus relay input
current as a multiple of the pickup current.
o This inverse time characteristic can be shifted up or down by adjustment of the time dial
setting.
o Although discrete time dial settings are shown in Figure 10.12, intermediate values can be
obtained by interpolating between the discrete curves.
D. Johari, FKE UiTM 9
Power System 1 EPO520
Example 3 (Glover 10.3)
The CO-8 relay with a pick-up current of 6 A and a time-dial setting of 1 is used with the 100:5 CT
in Example 1. Determine the relay operating time for each case.
D. Johari, FKE UiTM 10
Power System 1 EPO520
Radial System Protection
Many radial systems are protected by time-delay overcurrent relays.
These relays are coordinated to operate in sequence so that they interrupt minimum load
during faults.
o The breaker closest to the fault opens, while other upstream breakers with larger time
delays remain closed
Figure 10.16: Single line diagram of a 34.5kV radial system
Consider a fault at P1 to the right of breaker B3 for the radial system of Figure 10.16.
o For this fault we want breaker B3 to open while B2 (and B1) remains closed.
o Under these conditions, only load L3 is interrupted.
o We could select a longer time delay for the relay at B2, so that B3 operates first.
o Thus, for any fault to the right of B3, B3 provides primary protection.
o Only if B3 fails to open will B2 open, after time delay, thus providing backup protection.
Similarly, consider a fault at P2 between B2 and B3.
o We want B2 to open while B1 remains closed.
o Under these conditions, loads L2 and L3 are interrupted.
o Since the fault is closer to the source, the fault current will be larger than the previous fault
considered.
o B2, set to open for the previous, smaller fault current after time delay, will open more
rapidly for this fault.
o We also select the B1 relay with a longer time delay than B2, so that B2 opens first.
o Thus, B2 provides primary protection for faults between B2 and B3, as well as backup
protection for faults to the right of B3.
o Similarly, B1 provides primary protection for faults between B1 and B2, as well as backup
protection for further downstream faults.
The coordination time interval is the time interval between the primary and remote backup
protective devices.
o It is the difference between the time that the backup relaying operates and the time that
circuit breakers clear the fault under primary relaying.
o Typically, coordination time intervals are from 0.2 to 0.5 seconds to account for factors such
as CT error.
D. Johari, FKE UiTM 11