RTWF 300 HE High Vi C500D1 R515B

The document outlines the technical specifications and information requirements for the comfort chiller model RTWF 300 HE High Vi C500D1 R515B, including its cooling capacity, energy efficiency ratios, and power consumption in various modes. It specifies the chiller's rated cooling capacity, efficiency at different outdoor temperatures, and environmental impact through the Global Warming Potential (GWP) of the refrigerant. Additionally, it emphasizes the prohibition against altering the provided data and the legal implications of misuse.

Uploaded by

Federico
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
72 views1 page

RTWF 300 HE High Vi C500D1 R515B

The document outlines the technical specifications and information requirements for the comfort chiller model RTWF 300 HE High Vi C500D1 R515B, including its cooling capacity, energy efficiency ratios, and power consumption in various modes. It specifies the chiller's rated cooling capacity, efficiency at different outdoor temperatures, and environmental impact through the Global Warming Potential (GWP) of the refrigerant. Additionally, it emphasizes the prohibition against altering the provided data and the legal implications of misuse.

Uploaded by

Federico
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

REGULATION (EU) N.

2016/2281
Technical documentation (SEER)

Rev/202408

Information requirements for comfort chillers

Model(s): RTWF 300 HE High Vi C500D1 R515B

Outdoor side heat exchanger of chiller: water/brine

Indoor side heat exchanger of chiller: water

Type: compressor driven vapour compression

Driver of compressor: electric motor

Rated cooling capacity Prated,c 1011.0 kW Seasonal space cooling energy efficiency ηs,c 259 %

Declared cooling capacity for part load at given outdoor temperatures Tj Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy
factor for part load at given outdoor temperatures Tj

Tj = +35°C Pdc 1011 kW Tj = +35°C EERa 5.08 kW/kW

Tj = +30°C Pdc 745 kW Tj = +30°C EERb 6.16 kW/kW

Tj = +25°C Pdc 479 kW Tj = +25°C EERc 7.42 kW/kW

Tj = +20°C Pdc 212 kW Tj = +20°C EERd 6.67 kW/kW

Degradation coefficient (*) Cdc 0.980

Power consumption in modes other than active mode

Off mode Poff 0.000 kW Crankcase heater mode Pck 0.000 kW

Thermostat-off mode Pto 0.450 kW Standby mode Psb 0.970 kW

Other items

Capacity control variable For air-to-water chillers: air flow rate, m³/h
outdoor measured
Sound power level, outdoor Lwa dB(A)
For water/brine-to-water chillers: Rated 208 m³/h
GWP of the refrigerant 293 eq kg brine or water flow rate, outdoor side heat
CO2 exchanger

Contact details: TRANE - 88190 Golbey - France

(*) If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.

Attempting to alter the values in the datasheet is strictly forbidden and Trane shall not be liable for any misuse of the data provided or generated. Trane will also undertake any appropriate legal
action to protect its interests in case of violation of this prohibition.